Plan Review Details - Permit 11040378
Plan Review Stops For Permit 11040378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-06 Cont ID  
Sent By rmcdouga Date 2011-05-06 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2011-05-06 Time 07:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-02 Cont ID  
Sent By rmcdouga Date 2011-05-02 Time 07:24 Rev Time 0.00
Received By rmcdouga Date 2011-05-02 Time 07:24 Sent To  
Notes
2011-05-02 09:42:522007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE PLANS SPECIFY EXPOSURE CATEGORY B, THE STRUCTURE
 IS LOCATED APPROXIMATELY 658 FEET FROM THE INTRACOASTAL
 WATERWAY IT IS EXPOSURE C PER FBC R301.2.1.4.3. PLEASE
 CORRECT.
  
 2) THE COMPONENT AND CLADDING PRESSURES ARE TOO LOW FOR
 EXPOSURE C. PLEASE REVISE WINDOW AND DOOR PRESSURES ON
 THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2011-05-02 Cont ID  
Sent By rmcdouga Date 2011-05-02 Time 10:35 Rev Time 0.00
Received By rmcdouga Date 2011-05-02 Time 10:35 Sent To  
Notes
2011-05-02 10:42:06ELECTRIC SUB-PERMIT #07110572 FOR MASTER #07070546 WAS
 FINALED AND CLOSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-04-19 Cont ID  
Sent By rlecky Date 2011-04-19 Time 11:01 Rev Time 0.00
Received By rlecky Date 2011-04-19 Time 10:49 Sent To  
Notes
2011-04-19 11:01:06PROVIDE AN ELECTRIC PLAN. LOCATE EXISTING SERVICE, MAIN
 DISCONNECTS AND PANELS ON THE FLOOR PLAN. PROVIDE AN
 ELECTRICAL RISER DIAGRAM FOR THE NEW SERVICE. NEC
 110.26
 RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11
 ALL NEW RECEPTACLES WITHIN THE DWELLING SHALL BE
 PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER.
 NEC 210-12 (B)
 SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE NEW
 CAPACITY IS SUFFICIENT. NEC 220
  
 REMODELING OF AN EXISTING STRUCTURE SHALL INCLUDE
 INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT ALREADY
 EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. FBC R313
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-06 Cont ID  
Sent By rmcdouga Date 2011-05-06 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2011-05-04 Time 07:59 Sent To  
Notes
2011-05-04 07:59:52SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-02 Cont ID  
Sent By rmcdouga Date 2011-05-02 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2011-04-19 Time 09:04 Sent To  
Notes
2011-04-19 09:04:17SENT TO R1.

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-05-02 Cont ID  
Sent By rmcdouga Date 2011-05-02 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2011-05-02 Time 09:44 Sent To  
Notes
2011-05-02 09:54:05FINAL OUT PLUMBING FOR EXPIRED PERMIT # 07070549

Review Stop Z ZONING
Rev No 1 Status N Date 2011-05-02 Cont ID  
Sent By rmcdouga Date 2011-05-02 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2011-05-02 Time 09:43 Sent To  
Notes
2011-05-02 09:44:27REISSUE OF EXPIRED PERMIT 07070546