Plan Review Details - Permit 11040284
Plan Review Stops For Permit 11040284
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-06-01 Cont ID  
Sent By shill Date 2011-06-01 Time 09:07 Rev Time 0.00
Received By shill Date 2011-06-01 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-05-10 Cont ID  
Sent By shill Date 2011-05-10 Time 11:20 Rev Time 0.00
Received By shill Date 2011-05-10 Time 11:19 Sent To  
Notes
2011-05-10 11:26:10****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE OPENING 4, BOTTOM CONNECTION TYPE "D", ANCHOR
 SPACING OF 7" CIRCLED ON PRODUCT APPROVAL IS IN THE
 SECOND COLUMN OF THE 8'0" ROW (PAGE 13). THE SECOND
 COLUMN REQUIRES USE OF ALL POINTS SOLID SET. TAPCONS
 CANNOT BE USED FOR THIS SPAN (SEE "-" IN THE TAPCON
 ROW, WHICH IS THE FIRST ROW OF THE 8'0" SECTION OF THE
 CHART).
  
 ALSO NOTE THAT D WALL SILL MOUNTED W/12 WAS CIRCLED,
 NOT ALLOWED FOR THIS CONNECTION TYPE, BUT IS ALLOWED
 FOR D WALL SILL MOUNTING W/14. PLANS WERE NOT REDLINED
 AS I DO NOT KNOW HOW THIS WILL AFFECT THE JOB OR IF
 THIS MOUNTING TYPE IS POSSIBLE FOR THIS APPLICATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-19 Cont ID  
Sent By shill Date 2011-04-19 Time 15:37 Rev Time 0.00
Received By shill Date 2011-04-19 Time 15:37 Sent To  
Notes
2011-04-19 15:42:57****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. INSTALLATION SCHEDULE, SHUTTER CONNECTION MOUNTING
 TYPES A AND I REQUIRE POURED CONCRETE SUBSTRATE. PLEASE
 NOTE THAT MOST CBS STRUCTURES HAVE A POURED CONCRETE
 TOP CONNECTION SUBSTRATE, CONCRETE BLOCK AT BOTTOM.
  
 2. A 2 1/2" EDGE DISTANCE REQUIRES A .35 FACTOR, SEE
 CHART ON SHEET 14. THIS HAS NOT BEEN APPLIED TO THE
 ANCHOR SPACING.
  
 3. WALL PRESURES PROPOSED ON THE INSTALLATION SCHEDULE
 ARE +47/-62 PSF. IT APPEARS THAT CONTRACTOR USED THE
 COLUMN FOR -60PSF, BUT -62 PSF IS A GREATER PRESSURE
 THAN -60PSF. THE NEXT COLUMN MUST BE USED, -75PSF.
  
 4. CONNECTION TYPE L HAS BEEN CIRCLED ON SHEET 15, BUT
 I HAS BEEN SPECIFIED ON THE INSTALLATION SCHEDULE. THE
 INFORMATION MARKED ON THE PRODUCT APPROVAL IS TO
 CORRELATE WITH THE INSTALLATION SCHEDULE.
  
 5. THE QUALIFIER IS TO REVIEW ALL PERMIT DOCUMENTS
 PRIOR TO SUBMITTAL. PLEASE HAVE THE QUALIFIER REVIEW
 THE INSTALLATION SCHEDULE AND CONTACT ME IF HE NEEDS
 ASSISTANCE. WHEN RESUBMITTING, CONTRACTOR IS TO STATE
 THAT HE HAS REVIEWED THE INSTALLATION SCHEDULE AND THAT
 IT COMPLIES WITH THE REQUIREMENTS OF THE PRODUCT
 APPROVAL AND FBC.
  
 6. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
 INCLUDE ROOM DESIGNATION AND OPENING TYPE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-10 Cont ID  
Sent By shill Date 2011-05-10 Time 11:26 Rev Time 0.00
Received By shill Date 2011-05-09 Time 14:13 Sent To  
Notes
2011-05-09 14:13:45TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-19 Cont ID  
Sent By shill Date 2011-04-19 Time 15:43 Rev Time 0.00
Received By shill Date 2011-04-12 Time 08:34 Sent To  
Notes
2011-04-13 08:34:18TO MISC 1