Plan Review Stops For Permit 11040253 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2011-07-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-07-08 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-07-08 |
Time |
13:59 |
Sent To |
|
|
Notes |
2011-07-08 14:17:25 | BUILDING PROVISO | | | | 1) SUBMIT TWO SETS OF WALL DETAILS THAT SPECIFY THE | | FILE NUMBER OR DESIGN NUMBER OF THE ONE HOUR FIRE-RATED | | SEPARATION WALL BETWEEN THE TWO UNITS. ANSI/UL 263 IS | | THE TEST METHOD AND ACCEPTANCE CRITERIA. | | | | 2) SUBMIT TWO SETS OF CORRECTED ENERGY CALCULATIONS. | | THE ONES THAT WERE SUBMITTED ARE INCORRECT. THE NUMBER | | OF WINDOWS AND DOORS IN EACH UNIT ARE INCORRECT. THE | | PLANS SHOW A GABLE ROOF NOT A HIP. THIS COMMENT WAS | | UNDER MECHANICAL REVIEW IN THE FIRST REVIEW. THE FORM | | DOES NOT SPECIFY TWO UNITS. THE COMMON WALL BETWEEN THE | | TWO UNITS IS NOT LISTED ON THE FORM. THERE ARE ONLY TWO | | DOORS AND THE FORM LISTS THREE. THE FORM ONLY LISTS 8 | | WINDOWS AND THE ELEVATION PLANS SHOW 14. | | | | 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR | | NON-IMPACT RATED WINDOWS. IMPACT PROTECTION IS REQUIRED | | BY FBC R301.2.1.2 AND FBC EXISTING BUILDING 606.4. | | UNLESS THERE ARE EXISTING STORM PANELS, SUBMIT TWO | | COPIES OF PRODUCT APPROVALS AND AN INSTALLATION | | SCHEDULE FOR THE STORM PANELS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2011-06-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-06-15 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-06-15 |
Time |
16:47 |
Sent To |
|
|
Notes |
2011-06-15 17:06:20 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) SPECIFY THE FILE NUMBER OR DESIGN NUMBER OF THE ONE | | HOUR FIRE-RATED SEPARATION WALL BETWEEN THE TWO UNITS. | | ANSI/UL 263 IS THE TEST METHOD AND ACCEPTANCE CRITERIA. | | | | 2) THE ENERGY CALCULATIONS ARE INCORRECT. THE NUMBER OF | | WINDOWS AND DOORS IN EACH UNIT ARE INCORRECT. THE PLANS | | SHOW A GABLE ROOF NOT A HIP. THIS COMMENT WAS UNDER | | MECHANICAL REVIEW IN THE FIRST REVIEW. THE FORM DOES | | NOT SPECIFY TWO UNITS. THE COMMON WALL BETWEEN THE TWO | | UNITS IS NOT LISTED ON THE FORM. THERE ARE ONLY TWO | | DOORS AND THE FORM LISTS THREE. THE FORM ONLY LISTS 8 | | WINDOWS AND THE ELEVATION PLANS SHOW 14. PLEASE | | CORRECT. | | | | 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR | | NON-IMPACT RATED WINDOWS. IMPACT PROTECTION IS REQUIRED | | BY FBC R301.2.1.2 AND FBC EXISTING BUILDING 606.4. | | UNLESS THERE ARE EXISTING STORM PANELS, SUBMIT TWO | | COPIES OF PRODUCT APPROVALS AND AN INSTALLATION | | SCHEDULE FOR THE STORM PANELS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2011-05-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-05-13 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-04-25 |
Time |
12:01 |
Sent To |
|
|
Notes |
2011-05-13 16:05:04 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) SUBMIT DETAIL OF THE ONE HOUR FIRE-RATED SEPARATION | | WALL INCLUDE THE FILE NUMBER FOR THE TESTED ASSEMBLY | | BEING USED. SHOW COMPLIANCE WITH FBC R317.1 WHICH | | REQUIRES THE WALL TO EXTEND TO THE UNDERSIDE OF THE | | ROOF SHEATHING. | | | | 2) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA "A-9" BFE 13'. ALL NEW EQUIPMENT SERVICING THE | | DWELLINGS WILL BE REQUIRED TO BE 6" ABOVE THE BASE | | FLOOD ELEVATION WHICH IS A MINIMUM OF 13'-6". | | | | 3) THE PLANS HAVE AN AREA TABULATION THAT INDICATE 3 | | UNITS AND THERE ARE ONLY 2 UNITS SHOWN. TO AVOID | | CONFUSION PLEASE REVISE. NOTE: PERMIT #09080470 TO | | CONVERT THIS STRUCTURE FROM 3 UNITS TO 2 WAS ISSUED AND | | NEVER COMPLETED. | | | | 4) THERE WAS WORK DONE UNDER EXPIRED PERMIT # 09080470 | | THAT WAS NOT INSPECTED. THESE ISSUES WILL NEED TO BE | | ADDRESSED BEFORE A NEW PERMIT CAN BE ISSUED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2011-07-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-07-08 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-07-08 |
Time |
15:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2011-04-25 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2011-04-25 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2011-04-25 |
Time |
12:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2011-07-07 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2011-07-07 |
Time |
|
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2011-07-07 |
Time |
|
Sent To |
|
|
Notes |
2011-07-07 17:41:45 | PASSED: | | | | NO CONFLICT WITH CITY OF WPB PUBLIC UTILITIES. | | | | MANUEL JULIAN GONZALEZ | | CSD ENGINEERING REVIEW | | ENGINEERING SERVICES DEPARTMENT | | 401 CLEMATIS STREET | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2011-06-14 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2011-06-14 |
Time |
|
Rev Time |
0.25 |
Received By |
mgonzale |
Date |
2011-06-14 |
Time |
|
Sent To |
|
|
Notes |
2011-06-14 15:54:56 | PASSED | | | | NO CONFLICTS WITH CITY OF WEST PALM BEACH PUBLIC | | UTILITIES. | | | | MANUEL JULIAN GONZALEZ | | CSD ENGINEERING REVIEW | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2011-07-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-07-08 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-06-23 |
Time |
16:55 |
Sent To |
|
|
Notes |
2011-07-08 13:46:20 | 7/8/11 ROUTED TO RM DESK | 2011-06-24 07:24:44 | RESUB WAS COMBINED WITH THE PREVIOUSLY DENIED PLANS AND | | SENT TO ZONING. THE BUILDING ISSUES WILL BE ADDRESSED | | BY PROVISO AFTER ZONING HAS GIVEN APPROVAL. RM | | | | | 2011-06-23 16:56:25 | INCOMING SENT TO MCDOUGALS DESK. JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2011-06-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-06-15 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-06-07 |
Time |
08:59 |
Sent To |
|
|
Notes |
2011-06-07 08:59:40 | IN ZONING BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2011-05-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-05-13 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-04-12 |
Time |
11:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2011-06-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-06-15 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-06-15 |
Time |
16:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2011-05-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-05-13 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-05-13 |
Time |
15:08 |
Sent To |
|
|
Notes |
2011-05-13 15:33:48 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) THE SPECIFY THE DUCT SIZES, GRILL SIZES AND CFMS FOR | | EACH DROP FOR THE A/C SUPPLIES FOR UNIT B. CITY | | AMENDMENTS 106.3.5.4 | | | | 2) THE ENERGY CALCULATIONS ARE INCORRECT. THE NUMBER OF | | WINDOWS AND DOORS IN EACH UNIT ARE INCORRECT. THE PLANS | | SHOW A GABLE ROOF NOT A HIP. THE EXTERIOR WALLS ARE | | INCORRECT. THE ENERGY FORM SPECIFIES THE COOLING | | SYSTEMS AS 14 SEER AND ONE OF THE UNITS IS SPECIFIED AS | | 13 SEER ON THE MECHANICAL PLAN. FBC 13-101.2.3 PLEASE | | CORRECT. | | | | 3) THE EQUIPMENT SIZING CALCULATIONS DO NOT MATCH THE | | SPECIFIED EQUIPMENT. FBCR M1401.3 | | | | 4) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA "A-9" BFE 13'. ALL NEW EQUIPMENT SERVICING THE | | DWELLINGS WILL BE REQUIRED TO BE 6" ABOVE THE BASE | | FLOOD ELEVATION WHICH IS A MINIMUM OF 13'-6". | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2011-06-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-06-15 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-06-15 |
Time |
16:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2011-05-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-05-13 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-05-13 |
Time |
12:12 |
Sent To |
|
|
Notes |
2011-05-13 15:08:41 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) SUBMIT 2 COPIES OF A PLUMBING SANITARY ISOMETRIC | | RISER DIAGRAM. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2011-07-07 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2011-07-07 |
Time |
17:59 |
Rev Time |
1.00 |
Received By |
lfranco |
Date |
2011-06-28 |
Time |
14:48 |
Sent To |
ENG |
|
Notes |
2011-07-07 18:01:18 | PLANNING AND ZONING: **** PASSED ***** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | 2. THIS PROPERTY IS ZONED SF14 AND WAS PREVIOUSLY | | APPROVED FOR TWO UNITS. THREE UNITS WILL NOT BE | | ALLOWED. SEE COMMENTS BELOW. | | RESUBMITTAL: COMMENT ADDRESSED | | | | 3. PURSUANT TO SECTION 94-303 OF THE ZONING AND LAND | | DEVELOPMENT REGULATIONS ("ZLDR"): PARKING: ONE (1) | | PARKING SPACE SHALL BE PROVIDED FOR THE APARTMENT AND | | TWO (2) FOR THE PRINCIPAL STRUCTURE ON SITE. SEE | | COMMENT #4 FOR ADDITIONAL REQUIREMENTS. | | | | 4. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED | | OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | NON-DUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. | | RESPONSE TO RE-SUBMITTAL: SEE COMMENT #5. | | | | 5. PURSUANT TO SECTION 94-313. VEHICULAR ACCESS TO | | STREETS. ONLY ONE (1) ACCESS POINT IS ALLOWED FOR | | RESIDENTIAL DEVELOPMENTS LESS THAN 75 UNITS. THE SITE | | PLAN (SP-1) AND SURVEY SHOW TWO (2) EXISTING | | APPROACHES. THE SOUTHEAST APPROACH DOES NOT HAVE A | | DRIVE WAY; PROVIDE PROOF THAT A PERMIT FOR THE ROW | | APPROACH WAS APPROVED BY THE ENGINEERING DEPARTMENT. | | REGARDLESS OF THE PERMIT, ONLY ONE (1) ACCESS POINT IS | | ALLOWED FOR THIS PROPERTY. COORDINATE WHICH APPROACH | | WILL BE KEPT AND HOW THE VEHICULAR MANEUVERING AND | | PARKING WILL BE PROVIDED ON THE PROPERTY TO MEET | | COMMENT #2. | | | | (1) NUMBER OF ACCESS POINTS. | | A. ALL PROJECTS SHALL HAVE ACCESS TO A PUBLIC | | RIGHT-OF-WAY. THE NUMBER OF ACCESS POINTS SHALL BE AS | | FOLLOWS: | | TABLE INSET: | | | | TYPE OF DEVELOPMENT NUMBER OF ACCESS POINTS PREFERRED | | TYPE OF ACCESS | | RESIDENTIAL, < 75 UNITS 1 RESIDENTIAL OR MINOR | | COLLECTOR | | | | RESUBMITTAL: ONLY ONE ACCESS POINT/APPROACH OF A | | MAXIMUM OF 20' WIDE WILL BE ALLOWED. A U-DRIVE MAY ALSO | | BE PERMITTED PER PENDING CODE AMENDMENT, THE TWO (2) | | ACCESS POINTS HAVE TO BE A MAXIMUM OF 10 FEET EACH. | | HOWEVER, COMMENT NUMBER #4 NEEDS TO BE COMPLIED WITH | | (I.E. 25 FEET DEPTH X 100' WIDTH OF PROPERTY = 2500 SQ. | | FT. X .75 (75%) = 1875 SQ.FT. OF AREA TO BE LANDSCAPING | | (PERVIOUS AREA). SINCE THE SQ. FTG. IS MORE THAN 1,000 | | SQ. FT. THEN 1,000 SQ. FT. WILL BE THE MINIMUM REQUIRED | | LANDSCAPED AREA FOR THE FRONT PROPERTY AREA. | | SHOW CALCULATIONS ON SURVEY AND/OR PLANS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2011-06-09 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2011-06-09 |
Time |
18:28 |
Rev Time |
1.00 |
Received By |
lfranco |
Date |
2011-06-07 |
Time |
18:20 |
Sent To |
|
|
Notes |
2011-06-09 18:38:11 | PLANNING AND ZONING: **** FAILED ***** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | 2. THIS PROPERTY IS ZONED SF14 AND WAS PREVIOUSLY | | APPROVED FOR TWO UNITS. THREE UNITS WILL NOT BE | | ALLOWED. SEE COMMENTS BELOW. | | RESUBMITTAL: COMMENT ADDRESSED | | | | 3. PURSUANT TO SECTION 94-303 OF THE ZONING AND LAND | | DEVELOPMENT REGULATIONS ("ZLDR"): PARKING: ONE (1) | | PARKING SPACE SHALL BE PROVIDED FOR THE APARTMENT AND | | TWO (2) FOR THE PRINCIPAL STRUCTURE ON SITE. SEE | | COMMENT #4 FOR ADDITIONAL REQUIREMENTS. | | | | 4. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED | | OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | NON-DUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. | | RESPONSE TO RE-SUBMITTAL: SEE COMMENT #5. | | | | 5. PURSUANT TO SECTION 94-313. VEHICULAR ACCESS TO | | STREETS. ONLY ONE (1) ACCESS POINT IS ALLOWED FOR | | RESIDENTIAL DEVELOPMENTS LESS THAN 75 UNITS. THE SITE | | PLAN (SP-1) AND SURVEY SHOW TWO (2) EXISTING | | APPROACHES. THE SOUTHEAST APPROACH DOES NOT HAVE A | | DRIVE WAY; PROVIDE PROOF THAT A PERMIT FOR THE ROW | | APPROACH WAS APPROVED BY THE ENGINEERING DEPARTMENT. | | REGARDLESS OF THE PERMIT, ONLY ONE (1) ACCESS POINT IS | | ALLOWED FOR THIS PROPERTY. COORDINATE WHICH APPROACH | | WILL BE KEPT AND HOW THE VEHICULAR MANEUVERING AND | | PARKING WILL BE PROVIDED ON THE PROPERTY TO MEET | | COMMENT #2. | | | | (1) NUMBER OF ACCESS POINTS. | | A. ALL PROJECTS SHALL HAVE ACCESS TO A PUBLIC | | RIGHT-OF-WAY. THE NUMBER OF ACCESS POINTS SHALL BE AS | | FOLLOWS: | | TABLE INSET: | | | | TYPE OF DEVELOPMENT NUMBER OF ACCESS POINTS PREFERRED | | TYPE OF ACCESS | | RESIDENTIAL, < 75 UNITS 1 RESIDENTIAL OR MINOR | | COLLECTOR | | | | RESUBMITTAL: ONLY ONE ACCESS POINT/APPROACH OF A | | MAXIMUM OF 20' WIDE WILL BE ALLOWED. A U-DRIVE MAY ALSO | | BE PERMITTED PER PENDING CODE AMENDMENT, THE TWO (2) | | ACCESS POINTS HAVE TO BE A MAXIMUM OF 10 FEET EACH. | | HOWEVER, COMMENT NUMBER #4 NEEDS TO BE COMPLIED WITH | | (I.E. 25 FEET DEPTH X 100' WIDTH OF PROPERTY = 2500 SQ. | | FT. X .75 (75%) = 1875 SQ.FT. OF AREA TO BE LANDSCAPING | | (PERVIOUS AREA). SINCE THE SQ. FTG. IS MORE THAN 1,000 | | SQ. FT. THEN 1,000 SQ. FT. WILL BE THE MINIMUM REQUIRED | | LANDSCAPED AREA FOR THE FRONT PROPERTY AREA. | | SHOW CALCULATIONS ON SURVEY AND/OR PLANS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2011-04-28 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2011-04-28 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2011-04-28 |
Time |
11:46 |
Sent To |
|
|
Notes |
2011-04-28 11:48:21 | PLANNING AND ZONING: **** FAILED ***** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | 3. THIS PROPERTY IS ZONED SF14 AND WAS PREVIOUSLY | | APPROVED FOR TWO UNITS. THREE UNITS WILL NOT BE | | ALLOWED. SEE COMMENTS BELOW. | | | | | | PLANNING AND ZONING: **** PASSED WITH PROVISO-REVISED | | SHEETS FOR ONE (1) NEW APPROACH AND DRIVEWAY PLUS A | | PERMIT FROM THE ENGINEERING DEPARTMENT FOR THE WORK ON | | ROW SHALL BE SUBMITTED PRIOR TO ANY BUILDING | | INSPECTION. LMF**** | | | | 1. RESPOND TO COMMENTS IN WRITING. REVISIONS MAY | | GENERATE NEW COMMENTS. | | | | 2. PURSUANT TO SECTION 94-303 OF THE ZONING AND LAND | | DEVELOPMENT REGULATIONS ("ZLDR"): PARKING: ONE (1) | | PARKING SPACE SHALL BE PROVIDED FOR THE APARTMENT AND | | TWO (2) FOR THE PRINCIPAL STRUCTURE ON SITE. SEE | | COMMENT #3 FOR ADDITIONAL REQUIREMENTS. | | | | 3. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED | | OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | NON-DUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. | | RESPONSE TO RE-SUBMITTAL: SEE COMMENT #4. | | | | 4. PURSUANT TO SECTION 94-313. VEHICULAR ACCESS TO | | STREETS. ONLY ONE (1) ACCESS POINT IS ALLOWED FOR | | RESIDENTIAL DEVELOPMENTS LESS THAN 75 UNITS. THE SITE | | PLAN (SP-1) AND SURVEY SHOW TWO (2) EXISTING | | APPROACHES. THE SOUTHEAST APPROACH DOES NOT HAVE A | | DRIVE WAY; PROVIDE PROOF THAT A PERMIT FOR THE ROW | | APPROACH WAS APPROVED BY THE ENGINEERING DEPARTMENT. | | REGARDLESS OF THE PERMIT, ONLY ONE (1) ACCESS POINT IS | | ALLOWED FOR THIS PROPERTY. COORDINATE WHICH APPROACH | | WILL BE KEPT AND HOW THE VEHICULAR MANEUVERING AND | | PARKING WILL BE PROVIDED ON THE PROPERTY TO MEET | | COMMENT #2. | | | | (1) NUMBER OF ACCESS POINTS. | | A. ALL PROJECTS SHALL HAVE ACCESS TO A PUBLIC | | RIGHT-OF-WAY. THE NUMBER OF ACCESS POINTS SHALL BE AS | | FOLLOWS: | | TABLE INSET: | | | | TYPE OF DEVELOPMENT NUMBER OF ACCESS POINTS PREFERRED | | TYPE OF ACCESS | | RESIDENTIAL, < 75 UNITS 1 RESIDENTIAL OR MINOR | | COLLECTOR | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | |
|
|