Plan Review Details - Permit 11030737
Plan Review Stops For Permit 11030737
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-04-13 Cont ID  
Sent By rmcdouga Date 2011-04-13 Time 10:48 Rev Time 0.00
Received By rmcdouga Date 2011-04-13 Time 10:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-04 Cont ID  
Sent By rmcdouga Date 2011-04-04 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2011-04-04 Time 10:45 Sent To  
Notes
2011-04-04 10:52:042007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) STRUCTURES THAT EXCEED 60 FT IN HEIGHT REQUIRE
 ENGINEERING TO DETERMINE WIND DESIGN PRESSURES. SUBMIT
 TWO COPIES OF SIGNED AND SEALED DESIGN COMPONENT AND
 CLADDING WIND LOAD PRESSURE CALCULATIONS FOR THE
 OPENINGS FROM A FLORIDA LICENSED ENGINEER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-13 Cont ID  
Sent By rmcdouga Date 2011-04-13 Time 10:48 Rev Time 0.00
Received By rmcdouga Date 2011-04-13 Time 08:46 Sent To  
Notes
2011-04-13 08:48:20TO R MCDOUGAL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-04 Cont ID  
Sent By rmcdouga Date 2011-04-04 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2011-03-29 Time 07:47 Sent To  
Notes
2011-03-30 07:48:24SENT TO MISC 1