Plan Review Details - Permit 11030536
Plan Review Stops For Permit 11030536
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-03-31 Cont ID  
Sent By jgomez Date 2011-03-31 Time 14:01 Rev Time 0.00
Received By jgomez Date 2011-03-31 Time 13:13 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-03-21 Cont ID  
Sent By jgomez Date 2011-03-21 Time 15:27 Rev Time 0.00
Received By jgomez Date 2011-03-21 Time 15:20 Sent To PC
Notes
2011-03-21 15:55:40RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- WIND LOAD CALCULATIONS NEED TO HAVE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE. AND, BY NOTE #2 ON WIND LOAD SCHEDULE
 SUBMITTED.
  
 2- REVISE SHUTTERS INSTALLATION SCHEDULE:
 A) SHUTTERS SPAN IS INCORRECT. SHUTTER SPAN FOR THE
 ACCORDION SHUTTERS IS TAKEN IN THE VERTICAL DIMENSION.
 SEE SHEET 5 OF 28 OF SHUTTERS DRAWINGS SUBMITTED AND
 REVISE AS REQUIRED. ***NOTE: TAKE INTO CONSIDERATION
 THE MINIMUM EDGE DISTANCE (3") WHEN CALCULATING THE
 SHUTTERS SPAN.
  
 B) PROPOSED SHUTTER SILL INSTALLATION (D) FOR OPENINGS
 2 AND 3 IS NOT ALLOWED. SEE SHEET 13 OF 28 OF SHUTTERS
 DRAWINGS SUBMITTED. ACCORDING TO THE SHUTTER SPAN AND
 TYPE OF ANCHOR SELECTED (TAPCON) THIS INSTALLATION IS
 NOT ALLOWED. REVISE AS REQUIRED.
  
 C) REVISE ANCHOR SPACING FOR OPENING #1. TOP AND
 BOTTOM. ACCORDING TO THE CALCULATED DESIGN PRESSURES
 NEED TO USE 9" SPACING NOT 10". SEE SHEET 13 OF 28.
  
 D) REVISE ANCHOR SPACING FOR OPENING #2 ON HEADER SIDE.
 ACCORDING TO THE SHUTTER SPAN TAPCON NEED TO BE SPACED
 AT 7" NOT 10". SEE SHEET 13 OF 28.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-31 Cont ID  
Sent By jgomez Date 2011-03-31 Time 14:00 Rev Time 0.00
Received By jgomez Date 2011-03-30 Time 15:49 Sent To  
Notes
2011-03-30 16:05:49INCOMING SENT TO JULIO GOMEZ DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-21 Cont ID  
Sent By jgomez Date 2011-03-21 Time 15:20 Rev Time 0.00
Received By jgomez Date 2011-03-21 Time 15:20 Sent To  
Notes
***NONE***