Plan Review Details - Permit 11030144
Plan Review Stops For Permit 11030144
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-03-07 Cont ID  
Sent By wjolin Date 2011-03-07 Time 15:11 Rev Time 0.00
Received By wjolin Date 2011-03-07 Time 15:02 Sent To  
Notes
2011-03-07 15:11:03501 SOUTH SAPODILLA AVENUE
 PERMIT #11030144
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDES TYPE, OTHERWISE
 EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS ARE
 REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-07 Cont ID  
Sent By wjolin Date 2011-03-07 Time 15:02 Rev Time 0.00
Received By wjolin Date 2011-03-04 Time 15:48 Sent To FIRE
Notes
2011-03-04 15:49:12SENT TO FIRE BOX.