Plan Review Details - Permit 11030040
Plan Review Stops For Permit 11030040
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-01-25 Cont ID  
Sent By wjolin Date 2012-01-25 Time 11:58 Rev Time 0.00
Received By wjolin Date 2012-01-25 Time 11:12 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-01-18 Cont ID  
Sent By wjolin Date 2012-01-18 Time 13:14 Rev Time 0.00
Received By wjolin Date 2012-01-18 Time 10:04 Sent To M
Notes
2012-01-18 13:14:092100 NORTH FLORIDA MANGO ROAD
 PERMIT #11030040
 MASTER #10080396
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 24, BUILDINGS LESS THAN 40 FT IN HEIGHT, A
 BACKFLOW PREVENTER SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT BUT AT LEAST AS FAR FROM THE BUILDING
 AS THE HEIGHT OF THE WALL FACING THE BACKFLOW
 PREVENTER.
  
 PROVIDE LOCKABLE CAPS ON FIRE DEPARTMENT CONNECTION.
 PROVIDE WEATHERPROOF SIGNAGE FOR FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE CHAIN AND LOCK ON BACKFLOW PREVENTER.
  
 THE HYDRAULIC CALCULATIONS SUBMITTED WERE NOT SIGNED
 AND SEALED BY THE ENGINEER.
  
 DESIGN AREA #1 HAS LIGHT HAZARD SPACING UP TO 14.5'X14'
 (203 SQ.FT.); HOWEVER, THE HYDRAULIC CALCULATIONS DO
 NOT INDICATE ANY SPRINKLERS HAVING A FLOW OF 20.3
 GALLONS PER MINUTE.
  
 THE REDUCED AREA HYDRAULIC CALCULATIONS SUPPORT THREE
 SPRINKLERS SUPPLIED FROM A 1-1/4" BRANCHLINE; HOWEVER,
 SEVERAL BRANCH LINES HAVE ANYWHERE FROM 4-10 SPRINKLERS
 LOCATED WITHIN A SPAN OF 37' FEET ON THE BRANCH LINE
 WHICH WOULD RESULT IN A GREATER HYDRAULIC DEMAND ON THE
 SYSTEM. PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE
 ADDITIONAL SPRINKLERS.
  
 PROVIDE HYDRAULIC CALCULATIONS FOR THE ORDINARY HAZARD
 AREA (STORAGE #18 AND #19).
  
 FOUR SOFFITS 8'-0" AFF DO NOT APPEAR TO HAVE COVERAGE.
 SEE HALL #37 AND LOBBY #11 WITH ADJACENT RESTROOMS.
  
 SUBMIT PRODUCT DATA FOR SIDEWALL SPRINKLERS. ADD
 SIDEWALL SPRINKLER COUNT TO SPRINKLER SCHEDULE.
  
 THE SPRINKLER RISER DOES NOT APPEAR TO BE ACCESSIBLE.
 THE SPRINKLER RISER DETAIL DOES NOT INDICATE AN ALARM
 CHECK VALVE OR WATERFLOW SWITCH, INSPECTOR'S TEST
 CONNECTION, MAIN DRAIN, PRESSURE GAUGE ETC.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-03-15 Cont ID  
Sent By wjolin Date 2011-03-15 Time 10:15 Rev Time 0.00
Received By wjolin Date 2011-03-15 Time 08:47 Sent To M
Notes
2011-03-15 10:15:392100 NORTH FLORIDA MANGO ROAD
 PERMIT #11030040
 MASTER #10080396
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 PROVIDE SPRINKLER PROTECTION FOR EMERGENCY GENERATOR
 ROOM ATTACHED TO SOUTHWEST AREA OF BUILDING.
  
 TYCO EC-8 EXTENDED COVERAGE SPRINKLERS ARE NOT UL
 LISTED FOR ORDINARY HAZARD APPLICATIONS SUCH AS STORAGE
 ROOMS AND LOADING ZONE. REVISE HYDRAULIC CALCULATIONS.
  
 THE HYDRAULIC CALCULATION FOR THE EXTERIOR OVERHANG
 SHOULD INCLUDE ALL SPRINKLERS PROTECTING THIS SPACE.
 EXTENDED COVERAGE SPRINKLER NOT LISTED FOR ORDINARY
 HAZARD APPLICATIONS. REVISE CALCULATIONS.
  
 THE HYDRAULIC AREA FOR THE KITCHEN WAS CALCULATED
 PERPENDICULAR TO THE BRANCH LINES. NFPA 13 REQUIRES THE
 HYDRAULIC AREA TO BE MEASURED PARALLEL TO BRANCH LINES.
 REVISE CALCULATIONS.
  
 PROVIDE SPRINKLER COVERAGE BELOW OVERHEAD GARAGE DOORS
 IN STORAGE ROOM 19.
  
 PROVIDE LOCKABLE CAPS ON FIRE DEPARTMENT CONNECTION.
 PROVIDE WEATHERPROOF SIGNAGE FOR FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE CHAIN AND LOCK ON BACKFLOW PREVENTER.
  
 SPRINKLER DESIGN SHALL CONFORM TO THE 2002 EDITION OF
 NFPA 13.
  
 JOB VALUE ON PERMIT APPEARS TO BE UNDERVALUED AT 1.41
 DOLLARS PER SQUARE FOOT. JOB VALUE SHALL INCLUDE TOTAL
 CONTRACT AMOUNT INCLUDING MATERIALS, LABOR AND
 OVERHEAD/PROFIT. PROVIDE A SIGNED COPY OF THE OFFICIAL
 CONTRACT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-01-30 Cont ID  
Sent By hmoser Date 2012-01-30 Time 11:05 Rev Time 0.00
Received By hmoser Date 2012-01-20 Time 10:57 Sent To  
Notes
2012-01-23 10:57:38SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-23 Cont ID  
Sent By jgomez Date 2012-01-18 Time 10:46 Rev Time 0.00
Received By jgomez Date 2012-01-06 Time 17:00 Sent To  
Notes
2012-01-23 10:46:56LAST REVIEW DONE BY FIRE ON 1/18/12. JG.
2012-01-06 17:00:33SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-21 Cont ID  
Sent By hmoser Date 2011-03-21 Time 09:01 Rev Time 0.00
Received By hmoser Date 2011-03-02 Time 12:03 Sent To  
Notes
2011-03-02 12:04:14INCOMING SENT TO FIRE BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-01-30 Cont ID  
Sent By hmoser Date 2012-01-30 Time 11:05 Rev Time 0.00
Received By hmoser Date 2012-01-30 Time 10:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-03-21 Cont ID  
Sent By hmoser Date 2011-03-21 Time 08:55 Rev Time 0.00
Received By hmoser Date 2011-03-21 Time 08:55 Sent To  
Notes
2011-03-21 09:01:12PLANS DENIED
 PROVIDE PIPE SIZE ON ALL SPRINKLER PIPE.
 REFER TO SECTION 7.7.1.1.3 DISSIMILAR PIPING MATERIALS.
 REFER TO SECTION 8.4.7.2.2 NFPA 13
 PLAN REVIEW BY HAROLD MOSER 561-805-6732