Plan Review Details - Permit 11020658
Plan Review Stops For Permit 11020658
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-17 Cont ID  
Sent By rlecky Date 2011-05-17 Time 12:40 Rev Time 0.00
Received By rlecky Date 2011-05-17 Time 12:36 Sent To  
Notes
2011-05-17 12:36:44RESTAMP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-03-14 Cont ID  
Sent By rlecky Date 2011-03-14 Time 08:38 Rev Time 0.00
Received By rlecky Date 2011-03-14 Time 08:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-03-14 Cont ID  
Sent By eschneid Date 2011-05-16 Time 10:14 Rev Time 0.00
Received By rlecky Date 2011-03-14 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-05-17 Cont ID  
Sent By rlecky Date 2011-05-17 Time 12:36 Rev Time 0.00
Received By rlecky Date 2011-05-10 Time 11:15 Sent To  
Notes
2011-05-10 11:15:20SENT TO ZONING BOX FOR ERIC'S REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-17 Cont ID  
Sent By rlecky Date 2011-05-17 Time 12:35 Rev Time 0.00
Received By rlecky Date 2011-04-19 Time 08:18 Sent To  
Notes
2011-04-19 08:19:09TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-14 Cont ID  
Sent By rlecky Date 2011-03-14 Time 08:38 Rev Time 0.00
Received By rlecky Date 2011-02-28 Time 16:12 Sent To  
Notes
2011-02-28 16:12:49SENT TO ZONING BOX.

Review Stop Z ZONING
Rev No 3 Status P Date 2011-05-16 Cont ID  
Sent By eschneid Date 2011-05-16 Time 09:46 Rev Time 0.50
Received By eschneid Date 2011-05-12 Time 15:26 Sent To E
Notes
2011-05-16 10:14:08PASSED
  
 WEST SIGN
  
 MAX ALLOWED - 51.1 SQ. FT.
 APPROVED SIGN - 15.75 SQ. FT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446

Review Stop Z ZONING
Rev No 2 Status F Date 2011-05-04 Cont ID  
Sent By eschneid Date 2011-05-04 Time 10:25 Rev Time 0.50
Received By eschneid Date 2011-05-04 Time 10:25 Sent To  
Notes
2011-05-04 10:49:30FAILED
  
 1) REPEAT COMMENT - THE CITY'S SIGN REGULATIONS ONLY
 PERMIT ONE WALL SIGN PER BUSINESS PLUS TWO ADDITIONAL
 SIGNS FOR THE BUILDING - SECTION 94-408(D)(1)D. THIS
 PERMIT IS FOR THE INSTALLATION OF TWO SIGNS AND PERMIT
 NO. 11020659 IS FOR THE INSTALLATION OF TWO SIGNS FOR A
 TOTAL OF FOUR SIGNS ON THE CANOPIES. THIS EXCEEDS THE
 NUMBER OF WALL SIGNS PERMITTED. NOTE: STAFF LOCATED NO
 PERMITS FOR THE EXXON SIGNS, SO THERE IS NO
 GRANDFATHERED SIGNAGE ON THE CANOPIES. NO INFORMATION
 WAS PROVIDED TO SHOW WHICH ONE OF THE FOUR SIGNS HAS
 BEEN REMOVED FROM THE PERMIT APPLICATION.
  
 2) REPEAT COMMENT - THE SURVEY PROVIDED WITH THE
 APPLICATION DOES NOT INDICATE WHERE THE SIGNAGE WILL BE
 LOCATED.
  
 3) REPEAT COMMENT - THE CANOPY DRAWINGS ARE NOT
 ACCURATE. THE SITE DOES NOT CONTAIN A CANOPY WITH THREE
 PUMP ISLANDS. THE SURVEY AND PHOTOS SHOW ONE CANOPY AT
 50 FEET X 20 FEET AND ONE AT 30 FEET X 20 FEET, YET THE
 CANOPY DRAWINGS SHOW BOTH CANOPIES AS 30 FEET LONG.
  
 4) REPEAT COMMENT - THE SIGN DETAILS SHOW THE MEASURE
 POINT FOR THE SIGN HEIGHT (X) BUT NOT THE LENGTH (Y) SO
 STAFF IS UNABLE TO VERIFY SIGNAGE SIZE.
  
 5) NORTH ELEVATION ALLOWS A MAXIMUM OF 29.1 SQUARE FEET
 AND WEST ELEVATION ALLOWS A MAXIMUM OF 51.1 SQUARE
 FEET. SIGNS AS SHOWN ON THE ORIGINAL PERMIT CONFORM TO
 SIZE (SUBJECT TO VERIFICATION REQUIRED BY 4 ABOVE).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446

Review Stop Z ZONING
Rev No 1 Status F Date 2011-03-08 Cont ID  
Sent By eschneid Date 2011-03-08 Time 13:40 Rev Time 0.75
Received By eschneid Date 2011-03-08 Time 13:40 Sent To E
Notes
2011-03-08 13:46:28FAILED
  
 1) THE CITY'S SIGN REGULATIONS ONLY PERMIT ONE WALL
 SIGN PER BUSINESS PLUS TWO ADDITIONAL SIGNS FOR THE
 BUILDING - SECTION 94-408(D)(1)D. THIS PERMIT IS FOR
 THE INSTALLATION OF TWO SIGNS AND PERMIT NO. 11020659
 IS FOR THE INSTALLATION OF TWO SIGNS FOR A TOTAL OF
 FOUR SIGNS ON THE CANOPIES. THIS EXCEEDS THE NUMBER OF
 WALL SIGNS PERMITTED. NOTE: STAFF LOCATED NO PERMITS
 FOR THE EXXON SIGNS, SO THERE IS NO GRANDFATHERED
 SIGNAGE ON THE CANOPIES.
  
 2) PROVIDE PHOTOS OF THE NORTH, WEST AND SOUTH SIDES OF
 THE BUILDING. ANY SIGNAGE IN EXCESS OF THREE SIGNS
 SHALL BE REMOVED.
  
 3) THE SURVEY PROVIDED WITH THE APPLICATION DOES NOT
 INDICATE WHERE THE SIGNAGE WILL BE LOCATED.
  
 4) THE CANOPY DRAWINGS ARE NOT ACCURATE. THE SITE DOES
 NOT CONTAIN A CANOPY WITH THREE PUMP ISLANDS. THE
 SURVEY SHOWS ONE CANOPY AT 50 FEET X 20 FEET AND ONE AT
 30 FEET X 20 FEET, YET THE CANOPY DRAWINGS SHOW BOTH
 CANOPIES AS 30 FEET LONG.
  
 5) PROVIDE ELEVATION DRAWINGS OR PHOTOS OF THE
 ELEVATIONS OF THE BUILDING ON WHICH THE SIGNS ARE TO BE
 MOUNTED WITH THE HEIGHT AND WIDTH DIMENSIONS SHOWN.
 STAFF WILL USE THESE DIMENSIONS TO CALCULATE THE
 ALLOWABLE SIGN AREA. NOTE: USING THE INFORMATION
 PROVIDED, THE SIGNS EXCEED THE ALLOWED SIGNAGE AMOUNT.
  
 6) THE SIGN DETAILS SHOW THE MEASURE POINT FOR THE SIGN
 HEIGHT (X) BUT NOT THE LENGTH (Y).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446