Plan Review Details - Permit 11020296
Plan Review Stops For Permit 11020296
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-03-14 Cont ID  
Sent By shill Date 2011-03-14 Time 10:23 Rev Time 0.00
Received By shill Date 2011-03-14 Time 10:23 Sent To  
Notes
2011-03-14 10:25:36****PROVISO****
 ****REVISION REQURED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. (2ND REVIEW COMMENT) - THE ANCHOR SPACING DOES NOT
 COMPLY WITH REQUIREMENTS OF THE PRODUCT APPROVAL. FOR
 INSTANCE, SEE OPENING 1. C2 CONNECTION TYPE, BLOCK
 SUBSTRATE, -70PSF REQUIRES 4" SPACING, SEE CHART ON
 SHEET 10. THIS COMMENT APPLIES TO OTHER OPENINGS.
 PLEASE CHECK ALL AND REVISE INSTALLATION SCHEDULE AS
 REQUIRED.
  
 3RD REVIEW - SOME ITEMS ON THE INSTALLATION SCHEDULE
 HAVE BEEN REVISED, BUT OTHERS HAVE NOT AND DO NOT
 COMPLY WITH THE ANCHOR SCHEDULE. FOR INSTANCE, OPENING
 1, TOP STILL STATES THAT ANCHOR SPACING PROPOSED IS 12"
 WITH C2 CONNECTION TYPE AND BLOCK SUBSTRATE.
  
 REVISE ANCHOR SPACING TO COMPLY WITH THE REQUIREMENTS
 OF THE PRODUCT APPROVAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-03-01 Cont ID  
Sent By shill Date 2011-03-01 Time 14:49 Rev Time 0.00
Received By shill Date 2011-03-01 Time 14:49 Sent To  
Notes
2011-03-01 14:49:50****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE ANCHOR SPACING DOES NOT COMPLY WITH REQUIREMENTS
 OF THE PRODUCT APPROVAL. FOR INSTANCE, SEE OPENING 1.
 C2 CONNECTION TYPE, BLOCK SUBSTRATE, -70PSF REQUIRES 4"
 SPACING, SEE CHART ON SHEET 10. THIS COMMENT APPLIES TO
 OTHER OPENINGS. PLEASE CHECK ALL AND REVISE
 INSTALLATION SCHEDULE AS REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-02-15 Cont ID  
Sent By shill Date 2011-02-15 Time 12:38 Rev Time 0.00
Received By shill Date 2011-02-15 Time 12:38 Sent To  
Notes
2011-02-15 12:44:12****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. HOW HAS IT BEEN DETERMINED THAT SUBSTRATE, BOTTOM,
 IS CONCRETE RATHER THAN FILLED CMU? THIS CONFLICTS WITH
 OUR RECORDS. PLEASE ADDRESS BY EITHER REVISING
 INSTALLATION SCHEDULE OR PROVIDE MORE INFORMATION.
  
 2. ON THE PRODUCT APPROVLA, CIRCLE DETAILS USED FOR THE
 ARMOR SCREEN. I WAS UNABLE TO LOCATE 2.5" EDGE
 DISTANCE, 191" SPAN, 12" ANCHOR SPACING.
  
 3. INSTALLATION SCHEDULE SPECIFIES TAPCONS FOR ARMOR
 SCREEN. THIS FASTENER IS NOT ONE WHICH IS AN OPTION IN
 THE PRODUCT APPROVAL. SUBMIT EITHER SITE SPECIFIC
 ENGINEERING OR REVISE.
  
 4. WHEN RESUBMITTING, DO NOT HIGHLIGHT THE INSTALLATION
 SCHEDULE AS IT IS DIFFICULT TO READ AND CANNOT BE
 PROPERLY SCANNED.
  
 5. SPAN IS NOT CLEAR. WITH A 2.5" EDGE DISTANCE, SPAN
 SHOULD NOT BE THE SAME AS OPENING SIZE. PLEASE REVISE.
  
 6. PROVIDE ROOM DESIGNATION FOR THE EMERGENCY MEANS OF
 ESCAPE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-03-14 Cont ID  
Sent By shill Date 2011-03-14 Time 10:25 Rev Time 0.00
Received By shill Date 2011-03-07 Time 14:07 Sent To  
Notes
2011-03-07 14:07:19SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-28 Cont ID  
Sent By jgomez Date 2011-02-28 Time 11:50 Rev Time 0.00
Received By jgomez Date 2011-02-28 Time 11:49 Sent To  
Notes
2011-02-28 11:50:19SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-15 Cont ID  
Sent By shill Date 2011-02-15 Time 12:44 Rev Time 0.00
Received By shill Date 2011-02-11 Time 15:31 Sent To  
Notes
2011-02-11 15:32:13TO MISC 1 BOX