Plan Review Details - Permit 11010719
Plan Review Stops For Permit 11010719
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-24 Cont ID  
Sent By rmcdouga Date 2011-02-24 Time 08:49 Rev Time 0.00
Received By rmcdouga Date 2011-02-24 Time 08:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-02-11 Cont ID  
Sent By rmcdouga Date 2011-02-11 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2011-02-11 Time 09:27 Sent To E
Notes
2011-02-11 11:44:202007 FBC W/2009 REVISIONS
  
 1) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE
 2007 FBC EXISTING BUILDING CODE. APPEARS TO BE A LEVEL
 3 ALTERATION.
  
 2) SPECIFY THE DESIGN CRITERIA ON THE PLANS. THIS
 INCLUDES THE BASIC WINDSPEED, EXPOSURE CATEGORY AND
 COMPONENT AND CLADDING PRESSURES FOR THE WINDOWS AND
 DOORS,
  
 3) ASTM C 926 REQUIRES 7/8" THICK STUCCO APPLIED IN
 THREE-COATS WHEN APPLIED VERTICALLY TO A METAL LATH
 OVER A SOLID BASE. PLEASE CORRECT.
  
 4) FBC R703.2 REQUIRES A WATER-RESISTIVE BARRIER TO BE
 APPLIED OVER SHEATHING ON EXTERIOR WALLS. SHOW
 COMPLIANCE.
  
 5) SHOW COMPLIANCE WITH FBC R703.6.3 FOR THE REQUIRED
 BOND BREAK BETWEEN THE STUCCO AND THE WATER-RESISTIVE
 BARRIER.
  
 6) PRODUCT APPROVALS WERE SUBMITTED FOR A NON-IMPACT
 RATED OUT SWING GLAZED DOOR. FBC R301.2.1.2 REQUIRES
 GLAZED OPENINGS TO BE PROTECTED FROM WIND-BORNE DEBRIS.
 SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR STORM
 PANELS. SPECIFY THE MOUNTING METHOD, ANCHOR TYPE AND
 ANCHOR SPACING THAT WILL BE USED.
  
 7) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
 THE STAMPED PLANS AND A COPY OF THE PAID RECEIPT ARE
 REQUIRED TO BE SUBMITTED TO THE CITY CONSTRUCTION
 SERVICES DEPARTMENT BEFORE THE PERMIT IS ISSUED.
  
 8) SPECIFY HOW THE 2 X 4 PT TOP PLATE WILL BE ATTACHED
 TO THE CONCRETE BEAM IN WALL SECTION A.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-02-23 Cont ID  
Sent By rlecky Date 2011-02-23 Time 14:39 Rev Time 0.00
Received By rlecky Date 2011-02-23 Time 14:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-02-11 Cont ID  
Sent By rlecky Date 2011-02-11 Time 15:28 Rev Time 0.00
Received By rlecky Date 2011-02-11 Time 15:09 Sent To  
Notes
2011-02-11 15:27:57PROVIDE ELECTRICAL PLAN AND PERMIT. SHOW LOCATION AND
 SIZE OF EXISTING CIRCUITS AND PANELBOARD.
 PROVIDE ELECTRICAL RECEPTACLES AS REQUIRED. NEC 210.52,
 406.11
 PROVIDE GFCI PROTECTION AS REQUIRED. NEC 210.8
 PROVIDE LIGHTING OUTLETS AS REQUIRED. NEC 210.70
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2011-02-24 Cont ID  
Sent By jpapa Date 2011-02-24 Time 10:26 Rev Time 0.00
Received By jpapa Date 2011-02-24 Time 10:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-02-02 Cont ID  
Sent By fmittner Date 2011-02-02 Time 13:58 Rev Time 0.00
Received By fmittner Date 2011-01-31 Time 09:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-22 Cont ID  
Sent By lmartine Date 2011-02-22 Time 16:18 Rev Time 0.00
Received By lmartine Date 2011-02-22 Time 16:18 Sent To  
Notes
2011-02-22 16:19:04GAVE TO LECKY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-22 Cont ID  
Sent By lmartine Date 2011-02-11 Time 09:27 Rev Time 0.00
Received By lmartine Date 2011-02-02 Time 15:27 Sent To  
Notes
2011-02-02 15:30:36SENT TO R13.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2011-02-25 Cont ID  
Sent By jgomez Date 2011-02-25 Time 12:55 Rev Time 0.00
Received By jgomez Date 2011-02-25 Time 12:55 Sent To  
Notes
2011-02-25 12:57:23NO FEES DUE. SEE STAMPED PLANS BY MAB. DATED 2/25/11.
2011-02-24 08:53:32NEEDS REVIEW

Review Stop Z ZONING
Rev No 2 Status P Date 2011-02-24 Cont ID  
Sent By jpapa Date 2011-02-24 Time 10:27 Rev Time 0.00
Received By jpapa Date 2011-02-24 Time 10:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-02-02 Cont ID  
Sent By fmittner Date 2011-02-02 Time 13:58 Rev Time 0.00
Received By jpapa Date 2011-02-24 Time 10:27 Sent To  
Notes
2011-02-02 13:59:07OWNER TO SUBMIT TWO SURVEYS FOR RECORDS.