Plan Review Details - Permit 11010591
Plan Review Stops For Permit 11010591
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-03 Cont ID  
Sent By rmcdouga Date 2011-02-03 Time 07:47 Rev Time 0.00
Received By rmcdouga Date 2011-02-03 Time 06:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-01-31 Cont ID  
Sent By rmcdouga Date 2011-01-31 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2011-01-31 Time 11:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-31 Cont ID  
Sent By rmcdouga Date 2011-01-31 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2011-01-31 Time 11:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-03 Cont ID  
Sent By rmcdouga Date 2011-02-03 Time 06:59 Rev Time 0.00
Received By rmcdouga Date 2011-02-03 Time 06:59 Sent To  
Notes
2011-02-03 06:59:34TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-31 Cont ID  
Sent By rmcdouga Date 2011-01-31 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2011-01-26 Time 14:10 Sent To  
Notes
2011-01-26 14:11:08IN SWIMMING POOL BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-02-03 Cont ID  
Sent By rmcdouga Date 2011-02-03 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2011-02-03 Time 08:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-01-31 Cont ID  
Sent By rmcdouga Date 2011-01-31 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2011-01-31 Time 14:18 Sent To  
Notes
2011-01-31 15:07:02DENIED BY PLUMBING
  
 1) SUBMIT SPECIFICATIONS FOR THE 1 HP PUMP THAT WILL BE
 INSTALLED.
  
 2) THE PUMP CURVE CHART ON SHEET 2 APPEARS TO INDICATE
 A FLOW RATE OF 89 GPM AT A TDH OF 50. SUBMIT THE TDH
 CALCULATIONS SHOWING HOW THE 50 FEET OF HEAD WAS
 DETERMINED. OTHERWISE, THE MAXIMUM FLOW RATE OF THE
 PUMP WILL BE USED. THIS WOULD BE 112 GPM FOR PUMP CURVE
 G ON SHEET 2.
  
 3) ON SHEET 2 THE SUCTION PIPING IS SHOWN AS 2". AT 89
 GPM THE FLOW RATE IN 2" PIPE IS MORE THAN THE 8 FEET
 PER SECOND ALLOWED BY CODE SECTION FBC R4101.6.3.
 PLEASE CORRECT.
  
 4) IF THE MAXIMUM CAPACITY OF THE PUMP OF 112 GPM IS
 USED THE FLOW RATE IN THE 2" RETURN PIPES EXCEED THE 10
 FEET PER SECOND ALLOWED BY CODE. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2011-01-25 Cont ID  
Sent By fmittner Date 2011-01-25 Time 16:12 Rev Time 0.00
Received By fmittner Date 2011-01-25 Time 16:12 Sent To  
Notes
2011-01-25 16:13:03SETBACKS OK PER AMY STELLY. FHM APPROVED PERMIT
 1-25-11. RETURNED PERMIT TO CUSTOMER.