Plan Review Details - Permit 11010469
Plan Review Stops For Permit 11010469
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2011-10-28 Cont ID  
Sent By shill Date 2011-10-28 Time 08:54 Rev Time 0.00
Received By shill Date 2011-10-28 Time 08:54 Sent To  
Notes
2011-10-28 08:54:57SEE REVISION #11100657

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-17 Cont ID  
Sent By shill Date 2011-10-17 Time 10:14 Rev Time 0.00
Received By shill Date 2011-10-17 Time 10:14 Sent To  
Notes
2011-10-17 10:14:48SEE MECHANICAL COMMENTS
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-17 Cont ID  
Sent By shill Date 2011-10-17 Time 10:17 Rev Time 0.00
Received By shill Date 2011-10-14 Time 09:55 Sent To  
Notes
2011-10-14 09:55:21ON SH DESK (TO TYPE COMMENTS PER HM)
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2011-10-28 Cont ID  
Sent By shill Date 2011-10-28 Time 08:55 Rev Time 0.00
Received By shill Date 2011-10-28 Time 08:55 Sent To  
Notes
2011-10-28 08:55:14SEE REVISION #11100657

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-10-17 Cont ID  
Sent By shill Date 2011-10-17 Time 10:08 Rev Time 0.00
Received By shill Date 2011-10-17 Time 10:08 Sent To  
Notes
2011-10-17 10:14:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PER HAROLD MOSER, CHIEF MECHANICAL INSPECTOR, A
 SIGNED AND SEALED INSPECTION LETTER FROM THE ARCHITECT
 OF RECORD REQUIRED.
  
 2. DESIGNER OF RECORD TO REVIEW STRUCTURAL DETAIL
 PREPARED BY ANDREW MORGAN SERVICES, FS481.
  
 3. PROVIDE AN ORIGINAL "RTU TO ROOF SLAB DETAILS"
 (SIGNED, SEALED, AND DATED PER FS471) AND INCLUDE WIND
 DESIGN CRITERIA, FBC1603.1.4.
  
  
  