Plan Review Details - Permit 11010463
Plan Review Stops For Permit 11010463
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-06-03 Cont ID  
Sent By ddaniels Date 2011-06-03 Time 13:49 Rev Time 0.00
Received By ddaniels Date 2011-06-03 Time 13:49 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-01-27 Cont ID  
Sent By ddaniels Date 2011-01-27 Time 12:44 Rev Time 0.00
Received By ddaniels Date 2011-01-27 Time 12:21 Sent To M
Notes
2011-01-27 12:44:421/27/11 PLANS REVIEWED BY FIRE
  
 1. FIRE ENGINEER ON MASTER PERMIT APPLICATION SHOWS
 RICKY TERRELL P.E. IF HE IS NO LONGER THE P.E. SUBMIT
 NEW PLANS WITH THE CURRENT P.E.
  
 2. APPEARS THE DRAWINGS SUBMITTED ARE IDENTICAL TO THE
 ORIGINAL CONSTRUCTIONS DOCUMENTS REF #09070775.
  
 3. PROVIDE SPRINKLER HEAD LEGEND WITH MAKE, MODEL,
 QUANTITY.
  
 4. PROVIDE SPRINKLER SYMBOL CLARIFICATION
  
 5. PROVIDE SHOP DRAWINGS
  
 6. PROVIDE HYDRALIC CALCULATIONS
  
 7. PROVIDE CURRENT FLOW TEST RESULTS
  
 ***DENIED***
  
 CAPTAIN DANIELS
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-02 Cont ID  
Sent By hmoser Date 2011-02-02 Time 08:50 Rev Time 0.00
Received By hmoser Date 2011-01-24 Time 09:02 Sent To  
Notes
2011-01-24 09:02:36TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-02-02 Cont ID  
Sent By hmoser Date 2011-02-02 Time 08:49 Rev Time 0.00
Received By hmoser Date 2011-02-02 Time 08:49 Sent To  
Notes
***NONE***