Plan Review Stops For Permit 11010333 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2011-01-21 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2011-01-21 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2011-01-21 |
Time |
11:18 |
Sent To |
|
|
Notes |
2011-01-21 12:07:42 | APPROVED WITH PROVISO ON PLANS. | | | | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94 | | AT LEAST ONE WALL SWITCHED-CONTROLLED LIGHTING OUTLET | | SHALL BE INSTALLED IN EVERY HABITABLE ROOM. NEC 210.70 | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | RECEPTACLE OUTLET. NEC 210.52 (A)(2). | | ADDITIONAL RECEPTACLES ARE REQUIRED FOR ANY WALL SPACE | | MORE THAN 2 FEET IN WIDTH. NEC 210.52 (A) (2). | | BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC | | 210.12 | | THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2 | | GFCI PROTECTION IS REQUIRED FOR RECEPTACLES IN | | KITCHENS. NEC 210.8 | | | | ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718 | | |
|
|