Plan Review Details - Permit 11010251
Plan Review Stops For Permit 11010251
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-01-14 Cont ID  
Sent By wjolin Date 2011-01-14 Time 12:20 Rev Time 0.00
Received By wjolin Date 2011-01-14 Time 12:08 Sent To M
Notes
2011-01-14 12:20:54220 NORTH TAMARIND AVENUE
 PERMIT #11010251
 REVIEW COMMENTS - FIRE
  
 VERIFY 16-INCHES OF HORIZONTAL DISTANCE EXISTS BETWEEN
 FRYER AND SURFACE FLAMES OF RANGE. IF 16-INCHES CANNOT
 BE ENSURED, A STEEL BAFFLE AT LEAST 8-INCHES IN HEIGHT
 IS REQUIRED TO SEPARATE THE GREASE FROM OPEN FLAMES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-19 Cont ID  
Sent By hmoser Date 2011-01-19 Time 13:39 Rev Time 0.00
Received By hmoser Date 2011-01-14 Time 08:30 Sent To  
Notes
2011-01-14 08:30:56SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-03-29 Cont ID  
Sent By hmoser Date 2011-03-29 Time 12:50 Rev Time 0.00
Received By hmoser Date 2011-03-29 Time 12:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-01-19 Cont ID  
Sent By hmoser Date 2011-01-19 Time 13:36 Rev Time 0.00
Received By hmoser Date 2011-01-19 Time 13:36 Sent To  
Notes
2011-01-19 13:39:34PLAN DENIED
 CAN NOT FIND PERMIT FOR THE EXISTING HOOD . EXISTING
 HOOD LOOKS LIKE A TYPE 2 ,APPLICATION CALLS FOR A TYPE
 1
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  
  
  
 HOOD PERMIT WAS ISSUED ON 3/28/11 OK TO ISSUE FIRE
 SUPPRESSION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732