Plan Review Details - Permit 11010175
Plan Review Stops For Permit 11010175
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-01-28 Cont ID  
Sent By ddaniels Date 2011-01-28 Time 14:33 Rev Time 0.00
Received By ddaniels Date 2011-01-28 Time 14:33 Sent To  
Notes
2011-01-28 14:35:031/25/11 PLANS REVIEWED BY FIRE ***APPROVED***
  
 CAPTAIN DANIELS
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-28 Cont ID  
Sent By shill Date 2011-01-28 Time 10:10 Rev Time 0.00
Received By shill Date 2011-01-28 Time 10:10 Sent To  
Notes
2011-01-28 10:10:38OK PER CAPT DANIELS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-01-14 Cont ID  
Sent By wjolin Date 2011-01-14 Time 11:30 Rev Time 0.00
Received By wjolin Date 2011-01-14 Time 10:45 Sent To M
Notes
2011-01-14 11:30:05205 DATURA STREET
 PERMIT #11010175
 MASTER #10080641
 REVIEW COMMENTS - FIRE
  
  
 FIRE SPRINKLER DOCUMENTS ARE REQUIRED TO BE SEALED BY A
 PROFESSIONAL ENGINEER WHEN 50 OR MORE FIRE SPRINKLERS
 ARE ADDED, DELETED OR ALTERED PER SECTION 105.3.1.2(2)
 OF THE FLORIDA BUILDING CODE.
  
 REVISE PERMIT APPLICATION TO REFLECT CORRECT NUMBER OF
 SPRINKLERS AND ADJUST JOB VALUE.
  
 SECOND FLOOR NORTH: PROVIDE SPRINKLER COVERAGE FOR
 SMALL CORNER AREA EAST OF STORAGE ROOM 4.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcdouga Date 2011-01-31 Time 07:26 Sent To  
Notes
2011-01-31 07:26:25SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-28 Cont ID  
Sent By shill Date 2011-01-28 Time 10:05 Rev Time 0.00
Received By shill Date 2011-01-24 Time 10:34 Sent To  
Notes
2011-01-24 10:35:03TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-19 Cont ID  
Sent By hmoser Date 2011-01-19 Time 12:24 Rev Time 0.00
Received By hmoser Date 2011-01-12 Time 13:26 Sent To  
Notes
2011-01-12 13:26:17SENT TO FIRE BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-28 Cont ID  
Sent By shill Date 2011-01-28 Time 10:05 Rev Time 0.00
Received By hmoser Date 2011-01-28 Time 10:05 Sent To  
Notes
2011-01-28 10:05:30OK PER HM
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-01-19 Cont ID  
Sent By hmoser Date 2011-01-19 Time 12:19 Rev Time 0.00
Received By hmoser Date 2011-01-19 Time 12:19 Sent To  
Notes
2011-01-19 12:23:52PLANS DENIED
 APPLICATION SAID ADD / RELOCATE 29 SPRINKLER PLANS SHOW
 35 SPRINKLER ALSO CHECK VALUE
 PLAN REVIEW BY HAROLD MOSER 561-805-6732