Plan Review Details - Permit 11010118
Plan Review Stops For Permit 11010118
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-03 Cont ID  
Sent By jwitmer Date 2011-02-03 Time 12:47 Rev Time 0.75
Received By jwitmer Date 2011-02-03 Time 12:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-10 Cont ID  
Sent By jwitmer Date 2011-01-10 Time 12:27 Rev Time 3.00
Received By jwitmer Date 2011-01-10 Time 07:30 Sent To  
Notes
2011-01-10 13:17:02BUILDING PLAN REVIEW
 PERMIT: 11010118
 ADD: 1 HARVARD CIRCLE
 CONT: SUFFOLK CONSTRUCTION
 TEL: (786)566-7689
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A.04 :
  
 1A) THE CONFERENCE ROOM DOORS# D101 INDICATE HARDWARE
 GROUP # 1 TO HAVE FLUSH BOLTS TOP & BOTTOM OF INACTIVE
 DOOR. PLEASE PROVIDE ADDITIONAL INFORMATION FOR THESE
 FLUSH BOLTS MEETING THE ACCESSIBILITY REQUIREMENTS AS
 IN HARDWARE GROUP 4.
  
 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS.1) GENERAL.
 ALTERATIONS TO EXISTING BUILDINGS AND FACILITIES SHALL
 COMPLY WITH THE FOLLOWING:
 B) IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3,
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. IF THE
 APPLICABLE PROVISION FOR NEW CONSTRUCTION REQUIRES THAT
 AN ELEMENT, SPACE, OR COMMON AREA BE ON AN ACCESSIBLE
 ROUTE, THE ALTERED ELEMENT, SPACE, OR COMMON AREA IS
 NOT REQUIRED TO BE ON AN ACCESSIBLE ROUTE EXCEPT AS
 PROVIDED IN SECTION 11-4.1.6(2), ALTERATIONS TO AN AREA
 CONTAINING A PRIMARY FUNCTION.
  
 11-4.1.3(7)(C) EACH DOOR THAT IS AN ELEMENT OF AN
 ACCESSIBLE ROUTE SHALL COMPLY WITH SECTION 11-4.13.
 11-4.13.9 DOOR HARDWARE. HANDLES, PULLS, LATCHES,
 LOCKS, AND OTHER OPERATING DEVICES ON ACCESSIBLE DOORS
 SHALL HAVE A SHAPE THAT IS EASY TO GRASP WITH ONE HAND
 AND DOES NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING, OR
 TWISTING OF THE WRIST TO OPERATE. LEVER-OPERATED
 MECHANISMS, PUSH-TYPE MECHANISMS, AND U-SHAPED HANDLES
 ARE ACCEPTABLE DESIGNS. WHEN SLIDING DOORS ARE FULLY
 OPEN, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE
 FROM BOTH SIDES. HARDWARE REQUIRED FOR ACCESSIBLE DOOR
 PASSAGE SHALL BE MOUNTED NO HIGHER THAN 48 INCHES (1219
 MM) ABOVE FINISH FLOOR.
  
 1B) BREAK ROOM 119 AND WINDOW # W119, TTHE WINDOW
 SCHEDULE DOESN'T INDICATE THE USE OF TEMPERED GLASS
 PLEASE PROVIDE COMPLIANCE WITH SECTION 2406.3 HAZARDOUS
 LOCATIONS 7. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE
 PANEL, OTHER THAN IN THOSE LOCATIONS DESCRIBED IN
 PRECEDING ITEMS 5 AND 6, WHICH MEETS ALL OF THE
 FOLLOWING CONDITIONS:
 7.1. EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9
 SQUARE FEET (0.84 M2);
 7.2. EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457 MM)
 ABOVE THE FLOOR;
 7.3. EXPOSED TOP EDGE GREATER THAN 36 INCHES (914 MM)
 ABOVE THE FLOOR; AND
 7.4. ONE OR MORE WALKING SURFACE(S) WITHIN 36 INCHES
 (914 MM) HORIZONTALLY OF THE PLANE OF THE GLAZING.
  
 1C) STORAGE DOOR D100B & D117 ARE INDICATED IN THE DOOR
 SCHEDULE AS LESS THAN 32" CLEAR WIDTH, PLEASE REVIEW
 11-4.13.5 CLEAR WIDTH AND EXCEPTION #5.
  
 1D) STORAGE ROOM # 122 AND DOOR D 122. THIS STORAGE
 ROOM IS APPROXIMATELY 155 SQ FT WHICH WILL REQUIRE A
 SMOKE RATED WALL AND DOOR PLEASE REVIEW FBC-B SECTION
 508.2.2.1 AND TABLE 508.2 STORAGE ROOMS. WHERE TABLE
 508.2 PERMITS AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM
 WITHOUT A FIRE BARRIER, THE INCIDENTAL USE AREA SHALL
 BE SEPARATED FROM THE REMAINDER OF THE BUILDING BY
 CONSTRUCTION CAPABLE OF RESISTING THE PASSAGE OF SMOKE.
 THE PARTITIONS SHALL EXTEND FROM THE FLOOR TO THE
 UNDERSIDE OF THE FIRE-RESISTANCE-RATED FLOOR/CEILING
 ASSEMBLY OR FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY
 ABOVE OR TO THE UNDERSIDE OF THE FLOOR OR ROOF
 SHEATHING, OR SUB DECK ABOVE. DOORS SHALL BE SELF- OR
 AUTOMATIC CLOSING UPON DETECTION OF SMOKE IN ACCORDANCE
 WITH SECTION 715.4.7.3. DOORS SHALL NOT HAVE AIR
 TRANSFER OPENINGS AND SHALL NOT BE UNDERCUT IN EXCESS
 OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH NFPA 80.
  
 2) SHEET A.07 THE PLANS APPEAR TO NEED ADDITIONAL EXIT
 LIGHTS AT THE FOLLOWING LOCATIONS;
 1) DOOR D109A
 2) CORRIDOR 105 AT COORIDOR INTERSECTION TO EXIT
 DOORWAY.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-02-01 Cont ID  
Sent By rlecky Date 2011-02-01 Time 08:30 Rev Time 0.00
Received By rlecky Date 2011-02-01 Time 08:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-20 Cont ID  
Sent By rlecky Date 2011-01-20 Time 10:51 Rev Time 0.00
Received By rlecky Date 2011-01-20 Time 09:00 Sent To  
Notes
2011-01-20 09:56:20PROVISO:
  
 FEEDERS FROM "T1A" TO PANEL "L1A" AND "L1B" INCORRECTLY
 LABELLED ( REVERSED) AS TO MINIMUM SIZE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-02-14 Cont ID  
Sent By ddaniels Date 2011-02-14 Time 10:20 Rev Time 0.00
Received By ddaniels Date 2011-02-14 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-02-09 Cont ID  
Sent By wjolin Date 2011-02-09 Time 13:25 Rev Time 0.00
Received By wjolin Date 2011-02-09 Time 10:40 Sent To  
Notes
2011-02-09 13:12:451 HARVARD CIRCLE, SUITE #102
 PERMIT #11010118
 REVIEW COMMENTS - FIRE
 REVIEW NO. 2
  
 REPEAT COMMENT: FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS. NOTE: SEPARATE PLANS AND
 PERMITS ARE REQUIRED FOR THE INSTALLATION OF THE FIRE
 SPRINKLER SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-01-13 Cont ID  
Sent By wjolin Date 2011-01-13 Time 12:15 Rev Time 0.00
Received By wjolin Date 2011-01-12 Time 13:31 Sent To  
Notes
2011-01-12 14:04:411 HARVARD CIRCLE, SUITE #102
 PERMIT #11010118
 REVIEW COMMENTS - FIRE
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. NOTE: SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR THE INSTALLATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 THE PLANS SHOW DOORS WITH EXISTING CARD-READER ACCESS.
 INDICATE HOW EGRESS IS ACHIEVED.
  
 COORDINATE REFLECTED CEILING PLAN AND ELECTRICAL
 DRAWING EXIT SIGN LOCATIONS.
  
 FLUSH BOLTS ARE NOT PERMITTED AT THE TOP AND BOTTOM OF
 THE DOOR LEAF UNLESS THE RELEASING MECHANISM COMPLIES
 WITH SECTION 7.2.1.5.9.1 OF THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION (NFPA 101).
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOOR LOCATIONS.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-02-14 Cont ID  
Sent By ddaniels Date 2011-02-14 Time 10:22 Rev Time 0.00
Received By ddaniels Date 2011-02-14 Time 10:03 Sent To  
Notes
2011-02-14 10:04:10SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-14 Cont ID  
Sent By rmcdouga Date 2011-02-14 Time 10:02 Rev Time 0.00
Received By rmcdouga Date 2011-01-28 Time 09:52 Sent To  
Notes
2011-01-31 09:53:14B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-24 Cont ID  
Sent By hmoser Date 2011-01-24 Time 14:23 Rev Time 0.00
Received By hmoser Date 2011-01-07 Time 16:21 Sent To  
Notes
2011-01-07 16:24:26***************EXPEDITED***************
 B--5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-02-03 Cont ID  
Sent By jwitmer Date 2011-02-03 Time 12:55 Rev Time 0.20
Received By jwitmer Date 2011-02-03 Time 12:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-01-24 Cont ID  
Sent By hmoser Date 2011-01-24 Time 14:23 Rev Time 0.00
Received By hmoser Date 2011-01-24 Time 13:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-01-13 Cont ID  
Sent By lwagner Date 2011-01-13 Time 13:02 Rev Time 0.00
Received By lwagner Date 2011-01-13 Time 12:32 Sent To  
Notes
2011-01-13 13:03:33PLUMBING PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2011-01-19 Cont ID  
Sent By jroach Date 2011-01-19 Time 16:26 Rev Time 0.00
Received By jroach Date 2011-01-19 Time 16:26 Sent To  
Notes
***NONE***