Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-20 Cont ID  
Sent By ddaniels Date 2011-01-20 Time 15:33 Rev Time 0.00
Received By ddaniels Date 2011-01-20 Time 15:32 Sent To  
Notes
2011-01-20 15:33:191/20/11 PLANS REVIEWED COMMENTS ADDRESSED
 APPROVED
 CAPTAIN DANIELS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-01-11 Cont ID  
Sent By wjolin Date 2011-01-11 Time 13:53 Rev Time 0.00
Received By wjolin Date 2011-01-11 Time 11:48 Sent To M
Notes
2011-01-11 13:53:431919 NORTH FLAGLER DRIVE, 2ND FLOOR
 PERMIT #11010081
 MASTER #10070710
 REVIEW COMMENTS - FIRE
  
  
 CONFERENCE ROOM LOCATED TO THE WEST HAS TWO SPRINKLERS
 LOCATED IN THE 8-6 CEILING. THE SPRINKLER SPRAY WILL BE
 OBSTRUCTED BY THE 8-2 CEILING/SOFFIT.
  
 THE CORRIDOR SPRINKLER ADJACENT TO THE WOMEN'S RESTROOM
 IS LOCATED MORE THAN 7-6 FROM THE WALL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-20 Cont ID  
Sent By jgomez Date 2011-01-20 Time 11:08 Rev Time 0.00
Received By jgomez Date 2011-01-20 Time 11:08 Sent To FIRE
Notes
2011-01-20 11:09:22SENT TO FIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-13 Cont ID  
Sent By hmoser Date 2011-01-13 Time 11:45 Rev Time 0.00
Received By hmoser Date 2011-01-07 Time 14:07 Sent To  
Notes
2011-01-07 14:07:44INCOMING SENT TO FIRE. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-01-13 Cont ID  
Sent By hmoser Date 2011-01-13 Time 11:44 Rev Time 0.00
Received By hmoser Date 2011-01-13 Time 11:44 Sent To  
Notes
***NONE***