Plan Review Details - Permit 10120033
Plan Review Stops For Permit 10120033 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2010-12-09 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-12-10 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-12-09 |
Time |
12:20 |
Sent To |
M |
|
Notes |
2010-12-09 12:37:14 | 801 SOUTH OLIVE, SUITE #706 | | PERMIT #10120033 | | | | TO COMPLY WITH THE REQUIREMENTS FOR AN NFPA 13 SYSTEM, | | THE PLAN REFERENCES TO NFPA 13R WERE CROSSED OUT IN PEN | | AND INITIALED (JM) BY SPRINKLER CONTRACTOR. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2010-12-03 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-12-03 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-12-03 |
Time |
16:32 |
Sent To |
M |
|
Notes |
2010-12-03 16:57:17 | 801 SOUTH OLIVE AVENUE, UNIT #706 | | PERMIT #10120033 | | MASTER #10080601 | | REVIEW COMMENTS - FIRE | | | | A HIGH-RISE APARTMENT BUILDING EXISTS AT THIS ADDRESS; | | THEREFORE, THE SYSTEM MUST BE DESIGNED ACCORDING TO | | NFPA 13. SEVERAL GENERAL NOTES MAKE REFERENCE TO NFPA | | 13R WHICH IS APPLICABLE ONLY TO RESIDENTIAL OCCUPANCIES | | UP TO (AND INCLUDING) FOUR STORIES IN HEIGHT. | | | | SPRINKLER PROTECTION IS REQUIRED IN CLOSESTS AND | | PANTRIES PER NFPA 13 SECTION 8.14.8.2 (2002 EDITION). | | SPRINKLERS ARE NOT REQUIRED IN THESE SPACES IF THE | | DWELLING UNIT IS LOCATED WITHIN A HOTEL OR MOTEL. | | | | PROVIDE HYDRAULIC CALCULATIONS FOR THE FOUR MOST | | DEMANDING SPRINKLERS PER NFPA 13 SECTION 11.2.3.5. | | | | THE THREE NEW RESIDENTIAL SIDEWALL SPRINKLERS SUPPLIED | | BY THE BRANCH LINE DO NOT APPEAR TO BE CONNECTED TO THE | | REST OF THE SYSTEM. | | | | SPRINKLER PROTECTION IS REQUIRED BELOW SOFFITS GREATER | | THAN 8-INCHES IN WIDTH WHEN SIDEWALL SPRINKLERS ARE | | LOCATED IN THAT SOFFIT PER NFPA 13 SECTION 8.7.4.1.3.2. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | (561) 805-6730 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-12-10 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-12-10 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-12-09 |
Time |
12:20 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-12-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-12-06 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-12-01 |
Time |
16:39 |
Sent To |
|
|
Notes |
2010-12-01 16:39:50 | IN FIRE BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2010-12-10 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-12-10 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-12-10 |
Time |
13:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-12-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-12-06 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-12-06 |
Time |
10:29 |
Sent To |
|
|
Notes |
2010-12-06 10:38:49 | PLANS DENIED | | THREE SIDE WALL SPRINKLER HEAD ARE NOT CONNECTED TO | | MAIN . | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
|