Plan Review Details - Permit 10120033
Plan Review Stops For Permit 10120033
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-12-09 Cont ID  
Sent By hmoser Date 2010-12-10 Time 13:25 Rev Time 0.00
Received By wjolin Date 2010-12-09 Time 12:20 Sent To M
Notes
2010-12-09 12:37:14801 SOUTH OLIVE, SUITE #706
 PERMIT #10120033
  
 TO COMPLY WITH THE REQUIREMENTS FOR AN NFPA 13 SYSTEM,
 THE PLAN REFERENCES TO NFPA 13R WERE CROSSED OUT IN PEN
 AND INITIALED (JM) BY SPRINKLER CONTRACTOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-03 Cont ID  
Sent By wjolin Date 2010-12-03 Time 16:57 Rev Time 0.00
Received By wjolin Date 2010-12-03 Time 16:32 Sent To M
Notes
2010-12-03 16:57:17801 SOUTH OLIVE AVENUE, UNIT #706
 PERMIT #10120033
 MASTER #10080601
 REVIEW COMMENTS - FIRE
  
 A HIGH-RISE APARTMENT BUILDING EXISTS AT THIS ADDRESS;
 THEREFORE, THE SYSTEM MUST BE DESIGNED ACCORDING TO
 NFPA 13. SEVERAL GENERAL NOTES MAKE REFERENCE TO NFPA
 13R WHICH IS APPLICABLE ONLY TO RESIDENTIAL OCCUPANCIES
 UP TO (AND INCLUDING) FOUR STORIES IN HEIGHT.
  
 SPRINKLER PROTECTION IS REQUIRED IN CLOSESTS AND
 PANTRIES PER NFPA 13 SECTION 8.14.8.2 (2002 EDITION).
 SPRINKLERS ARE NOT REQUIRED IN THESE SPACES IF THE
 DWELLING UNIT IS LOCATED WITHIN A HOTEL OR MOTEL.
  
 PROVIDE HYDRAULIC CALCULATIONS FOR THE FOUR MOST
 DEMANDING SPRINKLERS PER NFPA 13 SECTION 11.2.3.5.
  
 THE THREE NEW RESIDENTIAL SIDEWALL SPRINKLERS SUPPLIED
 BY THE BRANCH LINE DO NOT APPEAR TO BE CONNECTED TO THE
 REST OF THE SYSTEM.
  
 SPRINKLER PROTECTION IS REQUIRED BELOW SOFFITS GREATER
 THAN 8-INCHES IN WIDTH WHEN SIDEWALL SPRINKLERS ARE
 LOCATED IN THAT SOFFIT PER NFPA 13 SECTION 8.7.4.1.3.2.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-10 Cont ID  
Sent By hmoser Date 2010-12-10 Time 13:24 Rev Time 0.00
Received By hmoser Date 2010-12-09 Time 12:20 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-06 Cont ID  
Sent By hmoser Date 2010-12-06 Time 10:39 Rev Time 0.00
Received By hmoser Date 2010-12-01 Time 16:39 Sent To  
Notes
2010-12-01 16:39:50IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-12-10 Cont ID  
Sent By hmoser Date 2010-12-10 Time 13:24 Rev Time 0.00
Received By hmoser Date 2010-12-10 Time 13:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-12-06 Cont ID  
Sent By hmoser Date 2010-12-06 Time 10:29 Rev Time 0.00
Received By hmoser Date 2010-12-06 Time 10:29 Sent To  
Notes
2010-12-06 10:38:49PLANS DENIED
 THREE SIDE WALL SPRINKLER HEAD ARE NOT CONNECTED TO
 MAIN .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732