Plan Review Details - Permit 10110665
Plan Review Stops For Permit 10110665
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-03 Cont ID  
Sent By wjolin Date 2010-12-03 Time 10:43 Rev Time 0.00
Received By wjolin Date 2010-12-01 Time 15:37 Sent To M
Notes
2010-12-01 17:05:05600 VILLAGE BOULEVARD
 PERMIT #10110665
 REVIEW COMMENTS - FIRE
  
 PROVIDE DUCT OPENING CLEANOUT AT CHANGE OF DIRECTIONS.
  
 INSTALL EXHAUST FAN IN VERTICAL POSITION OR PROVIDE
 EXHAUST FAN CUTSHEET SHOWING FAN IS UL LISTED FOR USE
 AT 45 DEGREE ANGLE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-16 Cont ID  
Sent By hmoser Date 2010-12-07 Time 08:59 Rev Time 0.00
Received By hmoser Date 2010-12-01 Time 13:54 Sent To  
Notes
2010-12-01 13:55:32****************EXPEDITED****************
 IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-12-16 Cont ID  
Sent By hmoser Date 2010-12-07 Time 08:49 Rev Time 0.00
Received By hmoser Date 2010-12-16 Time 13:55 Sent To  
Notes
2010-12-07 08:59:38PLAN DENIED
 EXHAUST DUCT NOTE # 2 AND THE PLANS DO NOT MATCH ,REFER
 TO SECTION 506.3.1.1 GREASE DUCT MATERIALS. 2007 FBC
 (M).
 SHALL HAVE MIN. 10 FT. DISTANCE FROM THE BOTTOM OF THE
 EXHAUST DUCT TO THE GRADE . REFER TO SECTION 506.3.12.3
 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732.