2010-11-30 17:34:31 | ELECTRIC PLAN REVIEW FAIL | | 1) 4-600 AND 1- 500 MCM THHN CONDUCTORS DO NOT FIT INTO | | A 3 1/2 PVC CONDUIT | | | | | | JOHN DICKINSON | | CONTRACT PLAN REVIEWER | | CELL 561-718-3230 |
|
|