Plan Review Details - Permit 10110533
Plan Review Stops For Permit 10110533
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-22 Cont ID  
Sent By jgomez Date 2010-12-22 Time 16:27 Rev Time 0.00
Received By jgomez Date 2010-12-22 Time 16:27 Sent To  
Notes
2010-12-22 16:33:51RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 ***NOTE: SINCE SAME PLANS ARE SUBMITTED FOR REAR
 BUILDINGS AND MAIN RESIDENCE AND TWO DIFFERENT PERMIT
 APPLICATIONS ARE PROVIDED, THEN THESE COMMENTS APPLY
 FOR BOTH PERMIT APPLICATIONS. ADDRESS COMMENTS FOR REAR
 BUILDINGS AND FOR MAIN RESIDENCE ACCORDINGLY.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.
  
 3- NEED TO PROVIDE EMERGENCY EGRESS FROM BEDROOM. SEC.
 R310 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 4- PROVIDE ENERGY CALCULATIONS. SEC. N1100.3 OF 2007
 FLORIDA RESIDENTIAL CODE CHAPTER 11. MAKE SURE CORRECT
 UPDATED FORM IS PROVIDED.
  
 5- ENGINEER OF RECORD TO SPECIFY ON PLANS TYPE OF
 ALTERATION AS REQUIRED BY SEC. 401.4 OF 2007
 FBC-EXISTING BUILDING.
  
 6- BATHROOM IS MISSING THE DIMENSIONS. SEC. R307.1.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ALL WINDOWS TO BE INSTALLED.
 B) ALL EXTERIOR DOORS TO BE INSTALLED.
 C) WINDOW MULLIONS AS SHOWN ON PLANS.
 C) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 D) ROOF SHINGLES.
 E) FLAT ROOF. IDENTIFY APPROVED ASSEMBLY TO BE USED AND
 PROVIDE CORRESPONDING RAS 117 CALCULATIONS. SEE GENERAL
 LIMITATION #7 TO SEE IF SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 8- SPECIFY HURRICANE OPENING PROTECTION AS REQUIRED BY
 SEC. R301.2.1.2 OF 2007 FLORIDA RESIDENTIAL CODE AND
 SEC. 606.4 OF 2007 FLORIDA BUILDING CODE-EXISTING.
 SPECIFY IF PROVIDING DOORS AND WINDOWS WITH IMPACT
 GLASS OR IF PROVIDING STORM SHUTTERS. STORM SHUTTERS
 REQUIRE PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR
 TO SUBMITTAL. SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 10- EXTERIOR ELEVATIONS SHOW ROOF OUTLOOKERS. WALL
 SECTION A/A1 SHOWS FASCIA BOARD. REVISE AS REQUIRED TO
 MATCH. SEC. 106.1.1 CITY AMENDMENTS TO FBC.
  
 11- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUE TO INCLUDE ALL LABOR, MATERIALS AND
 ENGINEERING FEES. REVISE AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC. SPECIFY VALUE FOR THE REAR BUILDINGS
 AND VALUE FOR THE MAIN RESIDENCE ON CORRESPONDING
 PERMIT APPLICATION. VALUE TO INCLUDE ALL MATERIALS,
 LABOR AND ENGINEERING FEES.
  
 12- WALL SECTION A/A1:
 A) INSTALLING R30 INSULATION DOESN'T ALLOW THE
 CROSS-VENTILATION REQUIRED BY SEC. R806 BECAUSE THERE
 IS NO ROOM. THE THICKNESS OF R-30 WILL FILL THE 2X10
 JOIST, THEREFORE LEAVING NO ROOM FOR AIR CIRCULATION.
 REVISE AS REQUIRED.
  
 B) 2X10 JOIST BLOCKING DOESN'T ALLOW THE CROSS
 VENTILATION REQUIRED BY SEC. R806. THERE IS NO ROOM FOR
 AIR CIRCULATION. REVISE AS REQUIRED.
  
 C) SPECIFY THE HURRICANE JOIST CONNECTORS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
  
 D) UPLIFT LOAD CALCULATIONS: CLARIFY WHY LATERAL LOADS
 ARE N.A. SEC. R301.
  
 13- SHEET A-1:
 A) SPECIFY SAFETY GLASS ON BATHROOM. SEC. R308.4.
  
 B) REVISE SCOPE OF WORK NOTES: * THERE IS STRUCTURAL
 WORK ON THIS PROJECT. NOTE #2 SAYS NO. REVISE AS
 REQUIRED.
  
 ** NOTE #5 SAYS NO WORK ON MAIN HOUSE. PERMIT
 APPLICATION CALLS FOR RENOVATION/REPAIRS, ETC.
 COORDINATE SCOPE OF WORK WITH CONTRACTOR. REVISE AS
 REQUIRED TO MATCH.
  
 14- SHEET A-2:
 A) PROVIDE SMOKE ALARM ON OFFICE/BEDROOM. SEC. R313.
 THIS ROOM HAS THE LAYOUT OF A BEDROOM ALSO.
  
 B) WOOD FRAMING DETAIL, WALL SECTION A/A-2 AND WOOD
 WALL INFILL DETAIL NEED TO SPECIFY 2 LAYERS OF WATER
 VAPOR BARRIER AS REQUIRED BY SEC. R703.6.3.
  
 15- WALL SECTION A/A-2:
 A) SPECIFY TRUSS CONNECTORS. SEC. R301.
  
 B) SHOW DOUBLE TOP PLATES. SEC. 106.1.1 CITY AMENDMENTS
 TO FBC.
  
 C) COORDINATE WALL SHEATHING NAILING SPACING WITH
 SPECIFICATIONS SHOWN ON WOOD FRAMING DETAIL AND WOOD
 WALL INFILL DETAIL. SEC. 106.1.1 CITY AMENDMENTS TO
 FBC.
  
 D) SPECIFY HOW PROVIDING WALL WOOD FRAMING FRAMING
 MEMBERS PROTECTION AGAINST DECAY AS REQUIRED BY SEC.
 R319.1.
  
 E) SPECIFY THE CLEARANCE FROM GRADE TO THE STUCCO TO
 VERIFY COMPLIANCE WITH THE TERMITE PROTECTION AS
 REQUIRED BY SEC. R704.
  
 16- SHEET A-3:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW
 ENTRY STAIR LANDING AND STAIRS TO SHOW COMPLIANCE WITH
 SEC. R311 AND R312. INCLUDE ALL THE REQUIRED
 DIMENSIONS.
  
 B) SPECIFY SAFETY GLASS ON BATHROOM WINDOW IF THE
 WINDOW IS GOING TO BE REPLACED. SEC. R308.4.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-12-30 Cont ID  
Sent By rlecky Date 2010-12-30 Time 11:22 Rev Time 0.00
Received By rlecky Date 2010-12-30 Time 11:07 Sent To  
Notes
2010-12-30 11:08:41 
 BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC
 210.12
 PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94
 THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2
 TAMPER -RESISTANCE RECEPTACLES REQUIRED. NEC 406.11,
 210.52
 MAXIMUM MAIN BREAKER FOR A RESIDENTIAL SERVICE USING
 2/0 COPPER CONDUCTORS IS 200 AMPERES. NEC TABLE 310.15
 DEDICATED GENERAL PURPOSE GFCI RECEPTACLE REQUIRED IN
 THE LAUNDRY ROOM. NEC 210.
 EACH BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210-11(C)(3)
 LAUNDRY AREA REQUIRES A RECEPTACLE NEC 210.52 (F)
 DRYER BRANCH CIRCUIT APPEARS UNDERSIZED.
 INSTA-HOT POWER USAGE INCORRECTLY LISTED. WIRE SIZES
 ARE INCORRECT.
 GFCI PROTECTED OUTLETS ARE REQUIRED FRONT AND BACK AT
 EACH RESIDENTIAL BUILDING AND AT THE LOCATION OF THE
 MECHANICAL EQUIPMENT . NEC 210-52 (E) (1), 210-63.
 INDICATE THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR
 AND ALL GROUNDING ELECTRODES FOR ALL BUILDINGS. NEC
 250- 52
 RECEPTACLE SPACING IN SEVERAL AREAS REQUIRES
 CORRECTION. NEC 210.52(A)(1)
 CARBON MONOXIDE DETECTORS REQUIRED. F.S. 553.885
  ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2010-12-17 Cont ID  
Sent By jpapa Date 2010-12-17 Time 16:50 Rev Time 0.00
Received By jpapa Date 2010-12-17 Time 16:50 Sent To  
Notes
2010-12-17 16:51:11***FAILED***
  
 1. PER SEC. 94-49 OF THE ZONING CODE, A CERTIFICATE OF
 APPROPRIATENESS IS REQUIRED FOR EXTERIOR ALTERATIONS TO
 HISTORIC PROPERTIES PRIOR TO SUBMITTAL FOR A BUILDING
 PERMIT. CONTACT JILLIAN PAPA, HISTORIC PRESERVATION
 PLANNER,AT 822-1454 FOR AND APPLICATION AND
 REQUIREMENTS.
  
 JILLIAN PAPA
 HISTORIC PRESERVATION PLANNER
 561-822-1454

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-30 Cont ID  
Sent By rlecky Date 2010-12-30 Time 11:15 Rev Time 0.00
Received By rlecky Date 2010-12-03 Time 08:57 Sent To  
Notes
2010-12-30 11:17:4612/30 FILED IN SMALL PLANS DENIED " TBD". RL
2010-12-03 08:57:50R13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-12-22 Cont ID  
Sent By jgomez Date 2010-12-22 Time 16:34 Rev Time 0.00
Received By jgomez Date 2010-12-22 Time 16:34 Sent To  
Notes
2010-12-22 16:36:02AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-12-29 Cont ID  
Sent By jgomez Date 2010-12-29 Time 11:22 Rev Time 0.00
Received By jgomez Date 2010-12-29 Time 11:22 Sent To  
Notes
2010-12-29 11:24:42RESIDENTIAL (R3) ALTERATION/RENOVATION MECHANICAL
 REVIEW CHECKLIST.
 207 FBC WITH 2009 REVISIONS.
  
 1- NO INFORMATION SUBMITTED FOR REVIEW. NEED COMPLETE
 PLANS AND A/C LOAD CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-12-29 Cont ID  
Sent By jgomez Date 2010-12-29 Time 11:24 Rev Time 0.00
Received By jgomez Date 2010-12-29 Time 11:24 Sent To  
Notes
2010-12-29 11:28:06RESIDENTIAL (R3) ALTERATION/RENOVATION PLUMBING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- SHEET A-1: PLUMBING RISER DIAGRAM IS MISSING THE
 CLOTHES WASHER.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status F Date 2010-12-17 Cont ID  
Sent By jpapa Date 2010-12-17 Time 16:54 Rev Time 0.00
Received By jpapa Date 2010-12-17 Time 16:54 Sent To  
Notes
2010-12-17 17:00:02***FAILED***
  
 1. PER TABLE III-! OF SEC. 94-71 IN THE ZONING CODE,
 ACCESSORY APARTMENTS ARE NOT PERMITTED WITHIN SF7-C4
 ZONING DISTRICT.
  
 JILLIAN PAPA
 HISTORIC PRESERVATION PLANNER
 561-822-1454