Plan Review Details - Permit 10110476
Plan Review Stops For Permit 10110476
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-11-22 Cont ID  
Sent By jgomez Date 2010-11-22 Time 13:57 Rev Time 0.00
Received By jgomez Date 2010-11-22 Time 13:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-11-20 Cont ID  
Sent By jgomez Date 2010-11-20 Time 12:05 Rev Time 0.00
Received By jgomez Date 2010-11-20 Time 12:05 Sent To PC
Notes
2010-11-20 12:16:30RESIDENTIAL (R3) ACCORDION SHUTTERS BUILDING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- AT LEAST ONE MEANS OF ESCAPE FROM THE HOUSE MUST BE
 PROVIDED WHEN THE ACCORDION SHUTTERS ARE CLOSED. SEC.
 R310.4 OF 2007 FLORIDA RESIDENTIAL CODE. SPECIFY WHERE
 IS THE REQUIRED MEANS OF ESCAPE. PARTIAL FLOOR PLAN
 SUBMITTED SHOWS EGRESS FROM THE BEDROOM. THIS ROOM IS
 HAVING ACCORDION SHUTTERS ALSO. NEED TO PROVIDE AT
 LEAST ONE MEANS OF ESCAPE WHEN SHUTTERS ARE UP.
  
 2- A) REVISE ANCHOR SPACING SHOWN ON THE INSTALLATION
 SCHEDULE WITH THE ANCHOR SPACING SHOWN ON SHUTTERS
 ANCHOR SCHEDULE ON SHEET 8 OF 16.
  
 B) REVISE OPENING SIZE SHOWN ON THE INSTALLATION
 SCHEDULE WITH THE OPENING SIZE SHOWN ON THE PARTIAL
 FLOOR PLAN SUBMITTED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-22 Cont ID  
Sent By jgomez Date 2010-11-22 Time 13:39 Rev Time 0.00
Received By jgomez Date 2010-11-22 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-20 Cont ID  
Sent By jgomez Date 2010-11-20 Time 12:16 Rev Time 0.00
Received By jgomez Date 2010-11-18 Time 12:24 Sent To  
Notes
2010-11-18 12:24:21BLDG <$5K
  