Plan Review Details - Permit 10110043
Plan Review Stops For Permit 10110043
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-11-17 Cont ID  
Sent By wjolin Date 2010-11-17 Time 10:42 Rev Time 0.00
Received By wjolin Date 2010-11-17 Time 10:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-11-03 Cont ID  
Sent By wjolin Date 2010-11-03 Time 15:34 Rev Time 0.00
Received By wjolin Date 2010-11-03 Time 15:22 Sent To M
Notes
2010-11-03 15:33:23505 SOUTH FLAGLER DRIVE SUITE #700
 PERMIT #10110043
 MASTER #10080742
  
 REVIEW COMMENTS - FIRE
  
 1) SPRINKLER SPRAY (X2) IS OBSTRUCTED BY 31-INCH WIDE
 SOFFIT FEATURED AT EAST/WEST AREA OF CONFERENCE ROOM
 #701. SOFFIT IS LOCATED 7-INCHES BELOW SPRINKLER
 ELEVATION.
  
 2) ARMOVERS EXCEEDING 12-INCHES IN LENGTH REQUIRE
 HANGERS WHEN SYSTEM PRESSURES EXCEED 100 PSI.
  
 3) SYSTEM PRESSURES EXCEEDING 100 PSI REQUIRE HANGERS
 (OR ALL-THREAD ROD) TO PREVENT UPWARD MOVEMENT OF END
 SPRINKLERS OR ARMOVERS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-16 Cont ID  
Sent By lmartine Date 2010-11-16 Time 15:37 Rev Time 0.00
Received By lmartine Date 2010-11-16 Time 15:37 Sent To  
Notes
2010-11-16 15:38:19IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-12 Cont ID  
Sent By hmoser Date 2010-11-12 Time 12:44 Rev Time 0.00
Received By hmoser Date 2010-11-12 Time 12:44 Sent To  
Notes
2010-11-01 15:25:31SENT TO FIRE BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-11-12 Cont ID  
Sent By hmoser Date 2010-11-12 Time 12:44 Rev Time 0.00
Received By hmoser Date 2010-11-12 Time 12:44 Sent To  
Notes
***NONE***