Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-10 Cont ID  
Sent By ddaniels Date 2011-01-10 Time 15:25 Rev Time 0.00
Received By ddaniels Date 2011-01-10 Time 15:25 Sent To  
Notes
2011-01-10 15:26:491/10/11 PLANS REVIEWED BY CAPTAIN DANIELS
 BATTERY CALCULATIONS APPROVED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-11-19 Cont ID  
Sent By wjolin Date 2010-11-19 Time 13:56 Rev Time 0.00
Received By wjolin Date 2010-11-19 Time 13:56 Sent To  
Notes
2010-11-19 13:56:241000 45TH STREET
 HOMELESS RESOURCE CENTER
 REVIEW COMMENTS - FIRE
 PERMIT #10110012
 PERMIT #10110013
 PERMIT #10110014
  
 *****APPROVED PROVISO*****
  
 SUBMIT BATTERY CALCULATIONS.
  
 DUCT SMOKE DETECTORS SHALL CAUSE A GENERAL FIRE ALARM.
  
 SYSTEM SHALL BE MONITORED BY A THIRD PARTY LISTED BY
 UL.
  
 COORDINATE/MONITOR FIRE SPRINKLER SYSTEM FLOW AND
 TAMPER SWITCH LOCATIONS AND BACKFLOW PREVENTER TAMPER
 SWITCHES.
  
 SMOKE DETECTOR IS NOT PERMITTED AT THE TOP OF THE
 ELEVATOR SHAFT UNLESS A FIRE SPRINKLER IS LOCATED AT
 THE TOP THE SHAFT.
  
 BUILDING 2 ONLY SHOWS A STROBE DEVICE AND TWO EXTERIOR
 HORN/STROBE DEVICES. PLEASE EXPLAIN LACK OF PULL
 STATIONS AND OTHER FIRE ALARM DEVICES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-10 Cont ID  
Sent By ddaniels Date 2011-01-10 Time 15:27 Rev Time 0.00
Received By ddaniels Date 2011-01-10 Time 15:26 Sent To  
Notes
2011-01-07 07:53:55TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-19 Cont ID  
Sent By wjolin Date 2010-11-19 Time 13:56 Rev Time 0.00
Received By wjolin Date 2010-11-19 Time 13:56 Sent To  
Notes
2010-11-01 14:07:49SENT TO FIRE BOX.