Plan Review Details - Permit 10100586
Plan Review Stops For Permit 10100586 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2010-11-04 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-11-04 |
Time |
17:20 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-11-04 |
Time |
17:20 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2010-10-28 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-10-28 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-10-28 |
Time |
12:06 |
Sent To |
M |
|
Notes |
2010-10-28 13:57:28 | 1920 WEKIVA WAY | | PERMIT #10100586 | | MASTER #10070788 | | | | REVIEW COMMENTS - FIRE | | | | 1) FIRE PROTECTION CONSTRUCTION DOCUMENTS ARE ALREADY | | SIGNED BY THE ENGINEER OF RECORD (ALVARO GONZALEZ). | | SHOP DRAWINGS SHALL NOT BE SIGNED AND SEALED BY A | | DIFFERENT ENGINEER (THOMAS TWOMEY). | | | | 2) CONSTRUCTION DOCUMENTS REQUIRE CERTAIN ROOMS TO BE | | DESIGNED AS ORDINARY HAZARD (STORAGE, FILES, ELECTRICAL | | ETC.). SHOP DRAWING SPRINKLER COVERAGE EXCEEDS 130 | | SQUARE FEET OF COVERAGE IN SOME OF THESE ROOMS. | | | | 3) PROVIDE SPRINKLER PROTECTION FOR SMALL ROOM #110B. | | | | 4) VERIFY PROPER SPRINKLER COVERAGE BELOW EXPOSED | | STRUCTURE IN ROOMS #119, #120 AND #121. | | | | 5) PROVIDE EXISTING CROSS MAIN SIZES ON SECOND FLOOR | | PLAN. | | | | 6) SHOW EXISTING SPRINKLER FLOOR CONTROL VALVE. | | | | 7) PROVIDE WATER SUPPLY DATA. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | 561-805-6730 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-11-04 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-11-04 |
Time |
17:20 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-11-04 |
Time |
17:20 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-11-02 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-11-02 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-10-22 |
Time |
17:02 |
Sent To |
|
|
Notes |
2010-10-22 17:02:45 | IN FIRE BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2010-11-15 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-11-15 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-11-15 |
Time |
08:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-11-02 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-11-02 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-11-02 |
Time |
14:53 |
Sent To |
|
|
Notes |
2010-11-02 14:55:39 | PLANS DENIED | | PLANS MUST BE SIGNED BY THE ENGINEER OF RECORD. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | |
|
|
|