Plan Review Details - Permit 10100391
Plan Review Stops For Permit 10100391
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-11-02 Cont ID  
Sent By shill Date 2010-11-02 Time 11:35 Rev Time 0.00
Received By shill Date 2010-11-02 Time 11:35 Sent To FIRE
Notes
2010-11-02 11:56:17****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 ITEMS FROM PROVISO LIST:
  
 1. ADDRESSED.
 2. PROVIDE A DETAIL FOR REQUIRED FIRE RATING, TENANT
 SEPARATION. THIS INCLUDES HORIZONTAL AND VERTICAL, FBC
 708.1. IT APPEARS THAT HORIZONTAL SEPARATION WAS
 REBUILT BETWEEN UNITS 4 AND 8, PLEASE ALSO NOTE
 AFFECTED SEPARATION BETWEEN UNIT 8 AND STAIRS,
 3. ADDRESSED.
 4. SPECIFY SOFFIT VENTING
 5. DETAIL FOR WINDOW INFILL LACKS BOND BREAK
 FBC1404.2.1.
  
 NEW COMMENTS:
  
 6. PLAN SHOWS A NEW ENTRY DOOR. SEE FBC715.4, SPECIFY
 REQUIRED FIRE RESISTANCE ON THE PLAN.
 7. PLEASE REVISE ASCE 7 REFERENCE TO CURRENT,
 (ASCE7-05) OR EXPLAIN USE OF ASCE 7-02. FBC35
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-11-03 Cont ID  
Sent By wjolin Date 2010-11-03 Time 11:18 Rev Time 0.00
Received By wjolin Date 2010-11-03 Time 10:55 Sent To  
Notes
2010-11-03 11:17:55442 16TH STREET
 TRACKING #10100391
 MASTER #10080385
  
 REVIEW COMMENTS - FIRE
  
 1) PROVIDE NEW DOOR INFORMATION (FIRE RATING, HARDWARE,
 CLOSERS ETC.).
  
 2) A ONE-HOUR FIRE SEPARATION (VERTICAL AND HORIZONTAL)
 IS REQUIRED BETWEEN DWELLING UNITS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-11-03 Cont ID  
Sent By wjolin Date 2010-11-03 Time 11:18 Rev Time 0.00
Received By wjolin Date 2010-10-18 Time 15:47 Sent To  
Notes
2010-10-18 15:48:10GAVE TO SAMANTHA