Plan Review Stops For Permit 10100189 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2010-10-13 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2010-10-13 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2010-10-13 |
Time |
14:50 |
Sent To |
|
|
Notes |
2010-10-13 15:57:09 | 807 NORTH FLAGLER DRIVE | | PERMIT NUMBER 10100189 | | "REPAIR FIRE ALARM DAMAGE BY ELECTRICAL SURGE" | | | | | | 1. ACCORDING TO THE NOTES ON THE DRAWINGS, "SYSTEM | | REPAIR DUE TO LIGHTNING DAMAGE, ALL HORN /STROBES, | | STROBES, NAC BOOSTERS, AND WIRE FOR AUDIO/VISUAL | | CIRCUITS EXISTING, E DENOTES EXISTING" | | | | 2. THE FIRE ALARM WORK SHALL COMPLY WITH NFPA 72, THE | | NATIONAL FIRE ALARM CODE, 2002 EDITION. | | | | 3. IN VIEWING THE DRAWINGS, IT APPEARS THAT ADDITIONAL | | DEVICES ARE NEEDED IN LEWIS HALL. SINCE DAMAGE OCCURRED | | TO THE FIRE ALARM SYSTEM DUE TO INCLEMENT WEATHER, THIS | | PERMIT APPLICATION WILL BE APPROVED WITH THE | | UNDERSTANDING THAT ADDITIONAL DEVICES NEEDS TO BE | | INSTALLED IN LEWIS HALL. | | | | 4. APPROPRIATE EQUIPMENT IS TO BE INSTALLED TO PREVENT | | LIGHTNING DAMAGE IN THE FUTURE. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-10-13 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2010-10-13 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2010-10-13 |
Time |
09:36 |
Sent To |
|
|
Notes |
2010-10-13 09:36:47 | SENT TO FIRE BOX. |
|
|
|