Plan Review Details - Permit 10100122
Plan Review Stops For Permit 10100122
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-28 Cont ID  
Sent By jwitmer Date 2010-10-28 Time 16:17 Rev Time 0.77
Received By jwitmer Date 2010-10-28 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-07 Cont ID  
Sent By jwitmer Date 2010-10-07 Time 15:13 Rev Time 0.55
Received By jwitmer Date 2010-10-07 Time 15:13 Sent To  
Notes
2010-10-07 15:26:12BUILDING PLAN REVIEW
 PERMIT:10100122
 ADD: 306 CLEMATIS ST
 CONT: JOE E HUGHES
 TEL: (561)312-2995
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET D-3 AND D-4 BOTH MAKE MENTION TO THE NEW YORK
 CODES. WE ARE CURRENTLY UNDER THE 2007 FLORIDA BUILDING
 CODE W/ 2009 SUPPLEMENTS AND THE 2007
 EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS. PLEASE
 UPDATE SHEETS.
  
 2) PLANS ARE FOR THE INTERIOR DEMO OF THE 1ST AND 2ND
 FLOORS ONLY AS DESCRIBED IN THTE PERMIT APPLICATION,
 WILL ANY WORK (DEMOLITION) OCCUR ON THE FLOORS ABOVE.
  
 3) PLANS DO NOT INDICATE HOW EGRESS TO THE THIRD FLOOR
 IS ACCOMPLISHED?
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2010-10-21 Cont ID  
Sent By dwise Date 2010-10-21 Time 17:38 Rev Time 0.00
Received By dwise Date 2010-10-21 Time 17:37 Sent To  
Notes
2010-10-21 17:39:08AS PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-10-20 Cont ID  
Sent By mcarsill Date 2010-10-20 Time 15:28 Rev Time 0.00
Received By mcarsill Date 2010-10-20 Time 15:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-10-07 Cont ID  
Sent By mcarsill Date 2010-10-07 Time 10:19 Rev Time 0.00
Received By mcarsill Date 2010-10-07 Time 09:40 Sent To  
Notes
2010-10-07 10:19:25306 CLEMATIS STREET
 PERMIT NUMBER 10100122
 "DEMOLISH INTERIOR PARTITIONS, CEILINGS AND
 FLOORING,ENCAPSULATE ASBESTOS TILE PER ENGINEER
 RECOMMENDATION, DEMO AND CAP ELECTRIC AND PLUMBING. 1ST
 AND 2ND FLOORS"
  
 1. ON SHEET D-1 PLANS MAKE REFERENCE TO THE STATE OF
 NEW YORK BUILDING CODE, ENERGY CODE OF NEW YORK, AND
 NEW YORK STATE LABOR DEPARTMENT. THE WORK DISPLAYED IS
 OCCURRING IN WEST PALM BEACH, FLORIDA. APPLICABLE CODES
 ARE THE FLORIDA BUILDING CODE AND THE FLORIDA FIRE
 PREVENTION CODE.
  
 2. ON SHEET D-1 NO. 308 IS LISTED ON THE PLANS BUT THE
 PERMIT APPLICATION INDICATES AN ADDRESS OF 306 CLEMATIS
 STREET. PLEASE CORRELATE INFORMATION.
  
 3. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NF 241.
  
 4. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS
 OFTEN AS NECESSARY.
  
 5. IF GASOLINE POWERED SAWS ARE PLANNED FOR USE
 INDOORS, PROPER VENTILATION CONTROLS ARE TO BE
 PROVIDED. CARBON MONOXIDE (CO) IS A COLORLESS,
 ODORLESS, AND TASTELESS GAS THAT IS ALSO FLAMMABLE IN
 THE CORRECT CONCENTRATION. NO STORAGE OF FLAMMABLE
 LIQUIDS OR COMBUSTIBLE LIQUIDS IS PERMITTED IN THE
 BUILDING.
  
 6. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR NEW RAILINGS SHOWN ON D-5.
  
 7. PLEASE INDICATE TYPE OF CONSTRUCTION, EXISTING FIRE
 PROTECTION SYSTEMS, AND OTHER DETAILS RELATED TO THE
 PROJECT.
  
 8. IS THERE ANY FIRE SPRINKLER PROTECTION LOCATED OVER
 THE WINDOWS ON THE ALLEY SIDE OF THE BUILDING.
  
 9. THE LONGITUDINAL SECTION ON D-5 DISPLAYS A THIRD
 FLOOR HOWEVER NO STAIRS ARE SHOWN TO REACH THIS LEVEL
 ONLY THE PENTHOUSE LEVEL.
  
 10. IN ACCORDANCE WITH CHAPTER 43 OF THE FLORIDA FIRE
 PREVENTION CODE, PLEASE DECLARE ON THE PLANS A WORK
 CATEGORIES AS DEFINED IN SECTION 43.1.1.
  
 11. MORE DETAILS REQUIRED ON THE DRAWINGS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-02 Cont ID  
Sent By jgomez Date 2010-11-02 Time 10:26 Rev Time 0.00
Received By jgomez Date 2010-10-19 Time 16:19 Sent To  
Notes
2010-11-02 10:35:24ROUTED TO PROCESSING
  
2010-10-19 16:20:301ST RESUB TO C10
  
 CONTRACTOR REQUESTED THAT THIS BE PULLED FROM FIRST
 REVIEW AT HIS RISK (E, P NOT COMPLETED) IN ORDER TO
 ADDRESS B & F COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-07 Cont ID  
Sent By jwitmer Date 2010-10-07 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2010-10-07 Time 07:49 Sent To  
Notes
2010-10-07 07:49:53INCOMING SENT TO C-10

Review Stop P PLUMBING
Rev No 1 Status N Date 2010-11-02 Cont ID  
Sent By jgomez Date 2010-11-02 Time 10:24 Rev Time 0.00
Received By jgomez Date 2010-11-02 Time 10:24 Sent To  
Notes
2010-11-02 10:26:16CAP PLUMBING ONLY. INTERIOR DEMOLITION PERMIT.

Review Stop Z ZONING
Rev No 1 Status N Date 2010-11-01 Cont ID  
Sent By aaponte Date 2010-11-01 Time 15:56 Rev Time 0.00
Received By aaponte Date 2010-11-01 Time 15:55 Sent To  
Notes
***NONE***