Plan Review Details - Permit 10090787
Plan Review Stops For Permit 10090787
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-10-28 Cont ID  
Sent By wjolin Date 2010-10-28 Time 15:07 Rev Time 0.00
Received By wjolin Date 2010-10-28 Time 14:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-10-26 Cont ID  
Sent By wjolin Date 2010-10-26 Time 11:15 Rev Time 0.00
Received By wjolin Date 2010-10-26 Time 10:11 Sent To  
Notes
2010-10-26 11:14:34600 VILLAGE BLVD.
 PERMIT #10090787
  
 PLAN REVIEW COMMENTS
  
 1) ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADDRESSED.
  
 2) NEW COMMENT: HYDRAULIC NODES IN CALCULATIONS DO NOT
 SEEM TO MATCH THE HYDRAULIC NODES SHOWN ON THE PLANS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 561-805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-30 Cont ID  
Sent By wjolin Date 2010-09-30 Time 16:21 Rev Time 0.00
Received By wjolin Date 2010-09-30 Time 14:23 Sent To M
Notes
2010-09-30 16:21:00600 VILLAGE BOULEVARD
 PERMIT #10090787
 MASTER #10070434
  
 1) UPDATE FLOOR PLAN AND SPRINKLER COVERAGE FOR REVISED
 (EXPANDED) PATIO.
  
 2) PROVIDE HYDRAULIC CALCULATIONS ACCOUNTING FOR
 FRICTION LOSS IN FLEXIBLE DROPS AND SYSTEM EXTENSION.
 PROVIDE UPDATED HYDRAULIC PLACARD DATA ON PLAN.
  
 3) PROVIDE VERIFICATION THAT THE AWNING STRUCTURE WILL
 SUPPORT THE LOAD OF WATER-FILLED SPRINKLER PIPING.
  
 4) PROVIDE ADDITIONAL FLEXHEAD INFORMATION STATING
 MAXIMUM NUMBER OF BENDS PERMITTED AND MINIMUM RADIUS
 REQUIRED PER THE LISTING REQUIREMENTS.
  
 5) PROVIDE CURRENT HYDRANT FLOW TEST DATA.
  
 6) PROVIDE LOCKABLE KNOX CAPS ON EXISTING FIRE
 DEPARTMENT CONNECTION.
  
 7) FOR AREAS EXPOSED TO STRUCTURE, PROVIDE THE
 CONSTRUCTION TYPE (OBSTRUCTED/UNOBSTRUCTED) AND THE
 SPRINKLER LOCATION IN REFERENCE TO DISTANCE BELOW THE
 ROOF DECK.
  
 8) EXISTING BRANCH LINE ROUTED THROUGH ELECTRICAL ROOM
 TO BE RE-ROUTED OUTSIDE OF ELECTRICAL ROOM. ONLY THE
 SPRINKLERS PROTECTING THE ELECTRICAL ROOM ARE PERMITTED
 BY NFPA 70.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-10-28 Cont ID  
Sent By lmartine Date 2010-10-28 Time 14:01 Rev Time 0.00
Received By lmartine Date 2010-10-28 Time 14:00 Sent To  
Notes
2010-10-28 14:02:20IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-18 Cont ID  
Sent By lmartine Date 2010-10-18 Time 14:43 Rev Time 0.00
Received By lmartine Date 2010-10-18 Time 14:43 Sent To  
Notes
2010-10-18 14:43:48IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-04 Cont ID  
Sent By hmoser Date 2010-10-04 Time 11:08 Rev Time 0.00
Received By hmoser Date 2010-09-29 Time 13:47 Sent To  
Notes
2010-09-29 13:47:45IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-10-04 Cont ID  
Sent By hmoser Date 2010-10-04 Time 11:08 Rev Time 0.00
Received By hmoser Date 2010-10-04 Time 11:08 Sent To  
Notes
***NONE***