Plan Review Stops For Permit 10090673 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2010-09-28 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-09-28 |
Time |
16:20 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-09-28 |
Time |
16:13 |
Sent To |
M |
|
Notes |
2010-09-28 16:20:27 | 525 OKEECHOBEE BOULEVARD #1100 | | PERMIT #10090673 | | MASTER #10070211 | | | | WHEN SYSTEM PRESSURES EXCEED 100 PSI, ARMOVERS GREATER | | THAN 12-INCHES REQUIRE A HANGER. THIS HANGER SHALL BE | | OF THE TYPE THAT PREVENTS UPWARD MOVEMENT OF THE PIPE. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | (561) 805-6730 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-10-04 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-10-04 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-09-23 |
Time |
15:42 |
Sent To |
|
|
Notes |
2010-09-23 15:43:24 | TO FIRE | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2010-10-04 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-10-04 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-10-04 |
Time |
10:47 |
Sent To |
|
|
Notes |
|
|
|