Plan Review Details - Permit 10090470
Plan Review Stops For Permit 10090470 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2010-11-03 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-11-03 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-11-03 |
Time |
14:48 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2010-09-28 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-09-28 |
Time |
12:31 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-09-28 |
Time |
11:41 |
Sent To |
M |
|
Notes |
2010-09-28 12:29:32 | 222 LAKEVIEW AVENUE, SUITE #1510 | | PERMIT #10090470 | | MASTER #10070806 | | | | 1) WHERE SYSTEM PRESSURES EXCEED 100 PSI, THE | | CUMULATIVE HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER | | TO A SPRINKLER SHALL NOT EXCEED 12-INCHES PER SECTION | | 9.2.3.5.2.1 OF NFPA 13 (2002 ED.). | | | | 2) WHERE SYSTEM PRESSURES EXCEED 100 PSI, THE HANGER | | CLOSEST TO THE SPRINKLER SHALL BE OF A TYPE THAT | | PREVENTS UPWARD MOVEMENT OF THE PIPING PER SECTION | | 9.2.3.5.2.2 OF NFPA 13 (2002 ED.). | | | | 3) PROVIDE HYDRAULIC CALCULATIONS TO SUPPORT THE SIX | | SPRINKLERS (CONFERENCE ROOM AND HALLWAY) THAT ARE BEING | | SUPPLIED BY THE EXISTING 1-INCH OUTLETS ON THE 1-INCH | | BRANCH LINES. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | (561) 805-6730 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-10-27 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-10-27 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-10-27 |
Time |
13:29 |
Sent To |
|
|
Notes |
2010-10-27 13:30:16 | IN FIRE BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-09-29 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-09-29 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-09-20 |
Time |
08:02 |
Sent To |
|
|
Notes |
2010-09-22 08:03:10 | IN FIRE BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2010-11-09 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-11-09 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-11-09 |
Time |
08:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-09-29 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-09-29 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-09-29 |
Time |
11:23 |
Sent To |
|
|
Notes |
2010-09-29 11:26:23 | PLANS DENIED | | PLEASE PROVIDE THE PIPE SIZE ON ALL THE NEW OUTLETS, | | PROVIDE AN (E) BY ALL THE EXISTING OUTLETS . | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
|