Plan Review Details - Permit 10090470
Plan Review Stops For Permit 10090470
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-11-03 Cont ID  
Sent By wjolin Date 2010-11-03 Time 14:48 Rev Time 0.00
Received By wjolin Date 2010-11-03 Time 14:48 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-28 Cont ID  
Sent By wjolin Date 2010-09-28 Time 12:31 Rev Time 0.00
Received By wjolin Date 2010-09-28 Time 11:41 Sent To M
Notes
2010-09-28 12:29:32222 LAKEVIEW AVENUE, SUITE #1510
 PERMIT #10090470
 MASTER #10070806
  
 1) WHERE SYSTEM PRESSURES EXCEED 100 PSI, THE
 CUMULATIVE HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER
 TO A SPRINKLER SHALL NOT EXCEED 12-INCHES PER SECTION
 9.2.3.5.2.1 OF NFPA 13 (2002 ED.).
  
 2) WHERE SYSTEM PRESSURES EXCEED 100 PSI, THE HANGER
 CLOSEST TO THE SPRINKLER SHALL BE OF A TYPE THAT
 PREVENTS UPWARD MOVEMENT OF THE PIPING PER SECTION
 9.2.3.5.2.2 OF NFPA 13 (2002 ED.).
  
 3) PROVIDE HYDRAULIC CALCULATIONS TO SUPPORT THE SIX
 SPRINKLERS (CONFERENCE ROOM AND HALLWAY) THAT ARE BEING
 SUPPLIED BY THE EXISTING 1-INCH OUTLETS ON THE 1-INCH
 BRANCH LINES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-27 Cont ID  
Sent By lmartine Date 2010-10-27 Time 13:29 Rev Time 0.00
Received By lmartine Date 2010-10-27 Time 13:29 Sent To  
Notes
2010-10-27 13:30:16IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-29 Cont ID  
Sent By hmoser Date 2010-09-29 Time 11:26 Rev Time 0.00
Received By hmoser Date 2010-09-20 Time 08:02 Sent To  
Notes
2010-09-22 08:03:10IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-11-09 Cont ID  
Sent By hmoser Date 2010-11-09 Time 08:13 Rev Time 0.00
Received By hmoser Date 2010-11-09 Time 08:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-09-29 Cont ID  
Sent By wjolin Date 2010-09-29 Time 11:23 Rev Time 0.00
Received By hmoser Date 2010-09-29 Time 11:23 Sent To  
Notes
2010-09-29 11:26:23PLANS DENIED
 PLEASE PROVIDE THE PIPE SIZE ON ALL THE NEW OUTLETS,
 PROVIDE AN (E) BY ALL THE EXISTING OUTLETS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732