Plan Review Details - Permit 10090390
Plan Review Stops For Permit 10090390
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-10-08 Cont ID  
Sent By rmcdouga Date 2010-10-08 Time 11:44 Rev Time 0.00
Received By rmcdouga Date 2010-10-08 Time 11:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-11-08 Cont ID  
Sent By rmcdouga Date 2010-11-08 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2010-11-08 Time 08:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-10-08 Cont ID  
Sent By rmcdouga Date 2010-10-08 Time 11:44 Rev Time 0.00
Received By rmcdouga Date 2010-10-08 Time 11:44 Sent To  
Notes
2010-10-08 11:48:12DENIED BY ELECTRICAL
  
 1) SUBMIT 2 SETS OF CUT SHEETS FOR THE ELECTRIC HEAT
 PUMP POOL HEATER.
  
 2) SUBMIT 2 SETS OF LOAD CALCULATIONS FOR THE EXISTING
 ELECTRICAL SERVICE WITH THE ADDITION OF THE NEW POOL
 HEATER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-11-15 Cont ID  
Sent By lmartine Date 2010-11-15 Time 16:25 Rev Time 0.00
Received By lmartine Date 2010-11-15 Time 16:25 Sent To  
Notes
2010-11-15 16:25:25GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-05 Cont ID  
Sent By rmcdouga Date 2010-11-05 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2010-10-20 Time 14:05 Sent To  
Notes
2010-10-20 14:06:00TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-08 Cont ID  
Sent By rmcdouga Date 2010-10-08 Time 11:48 Rev Time 0.00
Received By rmcdouga Date 2010-09-15 Time 07:57 Sent To  
Notes
2010-09-17 07:58:37TO ZONING BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-11-18 Cont ID  
Sent By rmcdouga Date 2010-11-18 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2010-11-18 Time 07:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-11-08 Cont ID  
Sent By rmcdouga Date 2010-11-08 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2010-11-08 Time 08:31 Sent To  
Notes
2010-11-08 16:00:452007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) BECAUSE THE TDH CALCULATIONS FOR EACH OF THE PUMPS
 HAVE NOT BEEN SUBMITTED, THE MAXIMUM FLOW CAPACITIES OF
 THE PUMPS WILL BE USED TO DETERMINE THE WATER VELOCITY
 IN FEET PER SECOND. THE 1.5 HP POOL PUMP HAS A MAXIMUM
 FLOW RATE OF 120 GPM. THE WATER VELOCITY IN 2-1/2" PIPE
 AT 120 GPM IS 7.84 FEET PER SECOND. THIS EXCEEDS THE 6
 FEET PER SECOND MAXIMUM VELOCITY ALLOWED BETWEEN MAIN
 DRAINS BY FBC R4101.6.3 AND ANSI/APSP 7. PLEASE
 CORRECT.
  
 2) THE DRAIN DETAIL FOR THE POOL PUMP DOES NOT SPECIFY
 THE PIPE SIZE FOR THE SDX SIDE MOUNTED SAFETY DRAIN.
 THE PIPING ISOMETRIC SPECIFIES A 2" SDX SIDE MOUNTED
 DRAIN. PLEASE CORRECT.
  
 3) THE PIPING ISOMETRIC SPECIFIES 2" SIDE MOUNTED
 DRAINS FOR THE WATERFALL AND THE DRAIN DETAIL HAS
 2-1/2" BRANCH PIPING BETWEEN THE MAIN DRAINS.
 ANSI/APSP-7 DEFINES BRANCH PIPING AS MULTIPLE SUCTION
 OUTLET COVERS/GRATES: ALL PIPE AND FITTINGS, INCLUDING
 THE TEE, LOCATED BETWEEN COVERS/GRATES AND THE SINGLE
 SUCTION PIPE FEEDING THE PUMP OR PUMPS. THIS REQUIRES
 THE OUTLETS ON THE MAIN DRAIN SUMPS TO ALSO BE 2-1/2".
 PLEASE CORRECT. NOTE: AT MAXIMUM PUMP FLOW 2-1/2" PIPE
 DOESN'T COMPLY. SEE COMMENT 1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-10-07 Cont ID  
Sent By rmcdouga Date 2010-10-07 Time 14:50 Rev Time 0.00
Received By rmcdouga Date 2010-10-07 Time 14:50 Sent To  
Notes
2010-10-07 15:56:16DENIED BY PLUMBING
  
 1) FBC 4101.6 .3 LIMITS THE WATER VELOCITY FOR SUCTION
 PIPING TO 8 FEET PER SECOND AND ANSI/APSP-7 4.4 LIMITS
 THE WATER VELOCITY IN FIELD FABRICATED BRANCH SUCTION
 PIPING TO 6 FEET PER SECOND. THE TWO MAIN DRAINS FOR
 THE WATER FALL HAVE A PUMP WITH A MAXIMUM FLOW RATE OF
 100 GPM. BASED ON THIS FLOW RATE WITHOUT ANY TDH
 REDUCTION FOR THE WATER VELOCITY, THE ALLOWABLE WATER
 VELOCITY IN THE 2-1/2" PIPE EXCEEDS 6 FEET PER SECOND
 AND EXCEEDS 8 FEET PER SECOND IN THE 2" PIPE. PLEASE
 SHOW HOW THE SYSTEM WILL COMPLY WITH THE REQUIRED
 MAXIMUM WATER VELOCITIES. YOU CAN USE ONE OF THE
 FOLLOWING OPTIONS : SUBMIT 2 COPIES OF TDH CALCULATIONS
 SHOWING THE ACTUAL FLOW RATE OF THE SYSTEM OR SPECIFY
 AN UNSTOPPABLE CHANNEL DRAIN OR SPECIFY LARGER PIPE
 SIZES.
  
 2) THE CUT SHEET FOR A CHANNEL DRAIN WAS SUBMITTED,
 HOWEVER, THERE IS NO CHANNEL DRAIN SHOWN ON THE PLANS.
 PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2010-11-03 Cont ID  
Sent By lfranco Date 2010-11-03 Time 13:22 Rev Time 0.00
Received By lfranco Date 2010-11-03 Time 13:22 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-09-28 Cont ID  
Sent By lfranco Date 2010-09-28 Time 18:58 Rev Time 0.00
Received By lfranco Date 2010-09-21 Time 15:29 Sent To  
Notes
2010-09-28 19:03:49PLANNING AND ZONING: *** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW: REFERENCE THIS
 PERMIT AS THE MASTER PERMIT WHEN SUBMITTING FOR THE
 FENCE PERMIT. ADD NOTATION ON THE FENCE PERMIT THAT THE
 APPLICATION OF THE FENCE PERMIT IS TO COMPLY WITH THE
 COMMENTS OF THE POOL PERMIT. SHOW POOL CONFIGURATION
 WITH THE FENCE PERMIT.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B) AND
 (C):
 B. EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  