Plan Review Details - Permit 10090387
Plan Review Stops For Permit 10090387
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-10-01 Cont ID  
Sent By jgomez Date 2010-10-01 Time 12:18 Rev Time 0.00
Received By jgomez Date 2010-10-01 Time 12:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-09-29 Cont ID  
Sent By jgomez Date 2010-09-29 Time 15:46 Rev Time 0.00
Received By jgomez Date 2010-09-29 Time 15:46 Sent To  
Notes
2010-09-29 15:50:43BUILDING REVIEW SECOND CHECKLIST:
  
 1- RAS 117 CALCULATIONS SUBMITTED:
  
 A) ENGINEER NEEDS TO REVISE THE DESIGN PRESSURES.
 ACCORDING TO THE 2009 REVISIONS SEC. R301.2.1.4.3 THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT EXPOSURE "B".
 REVISE THE DESIGN PRESSURES AS REQUIRED.
  
 B) ***NOTE: WHEN REVISING THE FASTENER SPACING TAKE
 INTO CONSIDERATION THAT NAILS CAN'T NOT BE SPACED LESS
 THAN 4" O.C.. SEE RAS 117 SEC. 8.1.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-21 Cont ID  
Sent By jgomez Date 2010-09-21 Time 14:47 Rev Time 0.00
Received By jgomez Date 2010-09-21 Time 09:52 Sent To  
Notes
2010-09-21 14:53:53RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. 301 OF 2007 FLORIDA
 RESIDENTIAL CODE. SEE GENERAL LIMITATION #7 ON LAST
 PAGE OF NOA 09-0323.18 SUBMITTED.
  
 B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C".
  
 2- PROVIDE NEW OWNER'S PROOF OF OWNERSHIP TO UPDATE
 OWNER INFORMATION.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-10-01 Cont ID  
Sent By jgomez Date 2010-10-01 Time 12:18 Rev Time 0.00
Received By jgomez Date 2010-10-01 Time 12:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-29 Cont ID  
Sent By jgomez Date 2010-09-29 Time 15:46 Rev Time 0.00
Received By jgomez Date 2010-09-29 Time 15:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-21 Cont ID  
Sent By jgomez Date 2010-09-21 Time 09:52 Rev Time 0.00
Received By jgomez Date 2010-09-21 Time 09:52 Sent To  
Notes
***NONE***