2010-09-20 07:34:43BUILDING PLAN REVIEW
 PERMIT: 10090366/ 10050105
 ADD: 500 FERN ST
 CONT: MINUTEMAN CON.
 TEL: (772)201-5918
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) MECHANICAL SYSTEM IS DESIGNED BY ARCHITECT ROBERT
 KOLANY WHICH REQUIRES AS BUILTS OR REVISIONS TO BE
 REVEIWED AND SIGNED AND SELED BY THE DESSIGNER OF
 RECORD.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
2010-09-16 12:09:57GAVE TO JIM

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-09-21 Cont ID  
Sent By jwitmer Date 2010-09-21 Time 11:48 Rev Time 0.50
Received By jwitmer Date 2010-09-21 Time 11:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-09-20 Cont ID  
Sent By jwitmer Date 2010-09-20 Time 07:30 Rev Time 0.50
Received By jwitmer Date 2010-09-20 Time 07:08 Sent To  
Notes
2010-09-20 07:36:24BUILDING PLAN REVIEW
 PERMIT: 10090366/ 10050105
 ADD: 500 FERN ST
 CONT: MINUTEMAN CON.
 TEL: (772)201-5918
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) MECHANICAL SYSTEM IS DESIGNED BY ARCHITECT ROBERT
 KOLANY WHICH REQUIRES AS BUILTS OR REVISIONS TO BE
 REVEIWED AND SIGNED AND SELED BY THE DESSIGNER OF
 RECORD.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 JIM WITMER C. B. O.