Plan Review Details - Permit 10090340
Plan Review Stops For Permit 10090340
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2010-10-15 Cont ID  
Sent By mcarsill Date 2010-10-15 Time 14:18 Rev Time 0.00
Received By mcarsill Date 2010-10-15 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-10-15 Cont ID  
Sent By mcarsill Date 2010-10-15 Time 14:17 Rev Time 0.00
Received By mcarsill Date 2010-10-15 Time 14:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-15 Cont ID  
Sent By wjolin Date 2010-09-15 Time 13:21 Rev Time 0.00
Received By wjolin Date 2010-09-15 Time 11:34 Sent To M
Notes
2010-09-15 13:21:08*****REVIEW COMMENTS - FIRE*****
  
 1) THE ADDRESS IN THE TITLEBLOCK SHOWS "407 NORTHWOOD
 ROAD", THE ADDRESS ON THE PERMIT READS "409 NORTHWOOD
 ROAD" AND THE ADDRESS ASSOCIATED WITH THE PARCEL ID ON
 THE PERMIT APPLICATION CORRESPONDS TO "401 NORTHWOOD
 ROAD."
  
 2) WORK SHALL CONFORM TO THE 2002 EDITION OF NFPA 13.
  
 3) INCOMING SPRINKLER SERVICE APPEARS TO ENTER IN AN
 ELECTRICAL ROOM.
  
 4) INDICATE LOCATION OF EXISTING FIRE DEPARTMENT
 CONNECTION, CONTROL VALVES, FLOW SWITCH AND TAMPER
 SWITCHES.
  
 5) INDICATE IF ANY ADJACENT TENANTS SPACES ARE IMPACTED
 BY THE SPRINKLER SYSTEM SHUTDOWN.
  
 6) PROVIDE SPRINKLER PROTECTION FOR OUTDOOR DINING AREA
 COVERED BY AWNING.
  
 7) PROVIDE HYDRAULIC CALCULATIONS FOR NEW LAYOUT.
  
 8) PROTECT KITCHEN AREA AS ORDINARY HAZARD OCCUPANCY.
  
 9) TWO SPRINKLERS IN KITCHEN AREA CURRENTLY LOCATED
 MORE THAN 7'-6" FROM WALL.
  
 10) PROTECT WALK-IN COOLER WITH DRY PENDENT SPRINKLERS.
  
 11) SPRINKLER IN "WAREWASH" LOCATED MORE THAN 7'-6"
 FROM WALL.
  
 12) VERIFY SPRINKLER PROTECTION IN REGARDS TO RESTROOM
 PARTITION HEIGHTS.
  
 13) NO SPRINKLER PROTECTION SHOWN FOR SMALL ELECTRICAL
 CLOSET ADJACENT TO MEN'S RESTROOM.
  
 14) SPRINKLER SPRAY OBSTRUCTED BY WING WALL IN "WAIT
 STATION."
  
 15) SPRINKLER SPRAY OBSTRUCTED NEAR MAIN ENTRY HOSTESS
 STAND.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-15 Cont ID  
Sent By mcarsill Date 2010-10-15 Time 14:17 Rev Time 0.00
Received By mcarsill Date 2010-10-14 Time 14:47 Sent To  
Notes
2010-10-14 14:48:01TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-14 Cont ID  
Sent By shill Date 2010-09-27 Time 14:47 Rev Time 0.00
Received By shill Date 2010-09-14 Time 13:30 Sent To  
Notes
2010-09-14 13:31:06TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-10-18 Cont ID  
Sent By lmartine Date 2010-10-18 Time 10:51 Rev Time 0.00
Received By lmartine Date 2010-10-18 Time 10:51 Sent To  
Notes
2010-10-18 10:52:09ADDRESS ON PLANS MATCH APPLICATION, 409 NORTHWOOD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-09-27 Cont ID  
Sent By hmoser Date 2010-09-27 Time 12:17 Rev Time 0.00
Received By hmoser Date 2010-09-27 Time 12:17 Sent To  
Notes
2010-09-27 12:20:00PLANS DENIED
 THE ADDRESS IN THE TITLEBLOCK DOES NOT MATCH THE
 ADDRESS ON THE PERMIT.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732