Plan Review Details - Permit 10090192
Plan Review Stops For Permit 10090192
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-09-22 Cont ID  
Sent By jwitmer Date 2010-09-22 Time 09:05 Rev Time 2.20
Received By jwitmer Date 2010-09-22 Time 09:05 Sent To  
Notes
2010-09-22 09:07:17BUILDING PROVISO:
 410.3.1 STAGE CONSTRUCTION. STAGES SHALL BE CONSTRUCTED
 OF MATERIALS AS REQUIRED FOR FLOORS FOR THE TYPE OF
 CONSTRUCTION OF THE BUILDING IN WHICH SUCH STAGES ARE
 LOCATED.
 EXCEPTIONS:
 1. STAGES OF TYPE IIB OR IV CONSTRUCTION WITH A NOMINAL
 2-INCH (51 MM) WOOD DECK, PROVIDED THAT THE STAGE IS
 SEPARATED FROM OTHER AREAS IN ACCORDANCE WITH SECTION
 410.3.4.
 2. IN BUILDINGS OF TYPE IIA, IIIA AND VA CONSTRUCTION,
 A FIRE-RESISTANCE-RATED FLOOR IS NOT REQUIRED, PROVIDED
 THE SPACE BELOW THE STAGE IS EQUIPPED WITH AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM IN ACCORDANCE WITH SECTION
 903 OR 904.
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-09-22 Cont ID  
Sent By jwitmer Date 2010-09-22 Time 09:03 Rev Time 2.20
Received By jwitmer Date 2010-09-22 Time 09:03 Sent To  
Notes
2010-09-16 15:20:04PURE VIDA
 700 SOUTH ROSEMARY AVENUE
 PERMIT NUMBER 10090192
  
  
 1. ON SHEET A-1.0 IN THE CODE /PROJECT DESIGN BOX IT
 REFERENCES BB KINGS, 550 SOUTH ROSEMARY AVENUE BUT THE
 PLANS ILLUSTRATE A TENANT SPACE AT 700 SOUTH ROSEMARY
 AVENUE.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEM INSTALLATIONS AND
 REMODELS.
  
 3. SINCE THE OCCUPANT LOAD IS EXPECTED TO BE ABOVE 250
 PERSONS CROWD MANAGEMENT TRAINING IS REQUIRED. PLEASE
 HAVE SELECTED PERSONNEL GO TO WWW.MARYLAND STATE FIRE
 MARSHAL'S OFFICE AND CLICK THE CROWD MANAGEMENT ICON.
 STAFF MEMBERS ARE TO WATCH THE VIDEO AND TAKE THE TEST.
 COPIES OF CERTIFICATES ARE TO BE SUBMITTED TO THE FIRE
 MARSHAL'S OFFICE PRIOR TO OPENING. OVERCROWDING IS NOT
 PERMITTED WITHIN THE ESTABLISHMENT. THE FINAL OCCUPANT
 LOAD WILL BE DETERMINED BY THIS OFFICE AND WILL BE
 REQUIRED TO BE POSTED. STAFF MEMBERS ARE TO CLICK IN
 AND OUTS TO PREVENT OVERCROWDING.
  
 4. ALL RATED FIRE DOORS ARE TO BE EQUIPPED WITH FIRE
 RATED PANIC HARDWARE. OTHER EXIT DOORS ARE TO BE
 EQUIPPED WITH PANIC HARDWARE.
  
 5. IT APPEARS THAT THE LOUNGE/SEATING AREA 105 IS TOO
 CROWDED. PLEASE REVIEW AREA TO DETERMINE ADEQUATE EXIT
 ACCESS.
  
 6. ALL EXISTING FIRE WALLS IF DAMAGED ARE TO BE
 REPAIRED TO PREVIOUS CONDITION. ALL PIPE PENETRATIONS
 ARE TO BE SEALED IN AN APPROVED MANNER WITH APPROVED
 MATERIALS FOR THAT PURPOSE.
  
 7. THE FIRE ALARM SYSTEM IS REQUIRED TO PROVIDE VOICE
 EVACUATION INSTRUCTIONS TO THE OCCUPANTS UPON
 ACTIVATION OF THE FIRE ALARM SYSTEM. PLEASE INDICATE
 WHAT THE VOICE EVACUATION PROMPTS WILL INDICATE TO
 VISITORS TO DO IN THE EVENT OF AN EMERGENCY.
  
 8. ALL COOLERS AND FREEZERS ARE TO BE FIRE SPRINKLER
 PROTECTED.
  
 9. PLEASE DEMONSTRATE COMPLIANCE WITH FIRE RETARDANT
 CRITERIA FOR THE TIKI COVERING MATERIAL SHOWN ON SHEET
 A-5.0.
  
 10. THE INSTALLATION OF ANY SOFFIT MATERIAL SHALL NOT
 INTERFERE WITH THE OPERATION OF ANY FIRE SPRINKLER
 HEADS.
  
  
 DENIED
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-09-16 Cont ID  
Sent By lmartine Date 2010-09-16 Time 12:27 Rev Time 0.00
Received By lmartine Date 2010-09-16 Time 12:27 Sent To  
Notes
2010-09-16 12:28:02PLANS REVIEWED AND APPROVED BY JAKE , SEE PLANS FOR HIS
 SIGNATURE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-09-30 Cont ID  
Sent By mcarsill Date 2010-09-30 Time 11:01 Rev Time 0.00
Received By mcarsill Date 2010-09-30 Time 10:57 Sent To  
Notes
2010-09-30 11:01:21700 SOUTH ROSEMARY AVENUE
 PERMIT NUMBER 10090192
  
  
 ON SEPTEMBER 30, 2010, REVIEWED REVISED SHEETS A-0.0,
 A-1.0, A-2.1, AND E-1.0. REVISED SHEETS STAMPED AND
 APPROVED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-17 Cont ID  
Sent By mcarsill Date 2010-09-17 Time 09:48 Rev Time 0.00
Received By mcarsill Date 2010-09-16 Time 13:47 Sent To  
Notes
2010-09-17 09:48:50PURE VIDA
 700 SOUTH ROSEMARY AVENUE
 PERMIT NUMBER 10090192
  
  
 1. ON SHEET A-0.0 IN THE CODE PROJECT DESIGN BOX BB
 KINGS, 550 SOUTH ROSEMARY AVENUE IS LISTED HOWEVER THE
 DRAWINGS INDICATES THE ADDRESS OF 700 SOUTH ROSEMARY
 AVENUE.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEM INSTALLATIONS AND
 REMODELS.
  
 3. CROWD MANAGEMENT TRAINING WILL BE REQUIRED FOR
 SELECTED STAFF. PLEASE GO TO WWW.MARYLAND STATE FIRE
 MARSHALS WEB-SITE AND CLICK ON THE CROWD MANAGEMENT
 TRAINING ICON, WATCH THE VIDEO, AND TAKE THE TEST.
 COPIES OF CERTIFICATES ARE TO BE SUBMITTED TO THE FIRE
 MARSHALS OFFICE PRIOR TO OPENING. OVERCROWDING IS NOT
 PERMITTED WITHIN THE ESTABLISHMENT. THE FINAL OCCUPANT
 LOAD IS TO BE DETERMINED BY THIS OFFICE. THE FINAL
 OCCUPANT LOAD IS TO BE POSTED WITHIN THE ESTABLISHMENT.
 WHEN OPENED, PERSONS ARE TO BE CLICKED IN AND OUT TO
 ENSURE THAT THE MAXIMUM OCCUPANT LOAD IS FOLLOWED.
  
 4. THE LOUNGE/ SEATING AREA 105 APPEARS CROWDED. PLEASE
 REVIEW THIS AREA FOR AQEQUATE EXIT ACCESS.
  
 5. ALL RATED FIRE DOORS ARE TO BE EQUIPPED WITH RATED
 PANIC HARDWARE.
  
 6. ALL COOLERS AND FREEZERS ARE TO BE FIRE SPRINKLER
 PROTECTED.
  
 7. PLEASE INDICATE WHAT THE VOICE EVACUATION PORTION OF
 THE FIRE ALARM SYSTEM WILL INDICATE WHEN ACTIVATED.
  
 8. ALL FIRE WALL PENTRATIONS ARE TO BE PROPERLY SEALED
 IN AN APPROVED MANNER WITH APPROVED MATERIALS.
  
 9. ALL EXISTING FIRE WALLS SHALL BE IN GOOD CONDITION.
  
 10. PANIC HARDWARE SHALL BE PROVIDED ON EXIT DOORS.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-29 Cont ID  
Sent By lmartine Date 2010-09-29 Time 16:37 Rev Time 0.00
Received By lmartine Date 2010-09-29 Time 16:37 Sent To  
Notes
2010-09-29 16:44:27GAVE TO MIKE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-28 Cont ID  
Sent By hmoser Date 2010-09-28 Time 07:54 Rev Time 0.00
Received By hmoser Date 2010-09-09 Time 08:36 Sent To  
Notes
2010-09-16 12:21:14*****************EXPEDITED******************
 ON 9/14/10
2010-09-09 08:36:26C19

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-09-28 Cont ID  
Sent By hmoser Date 2010-09-28 Time 07:51 Rev Time 0.00
Received By hmoser Date 2010-09-28 Time 07:50 Sent To  
Notes
2010-09-28 07:53:53NO MECHANICAL PLANS SUBMITTED .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-09-17 Cont ID  
Sent By lwagner Date 2010-09-17 Time 11:26 Rev Time 0.00
Received By lwagner Date 2010-09-17 Time 10:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2010-09-20 Cont ID  
Sent By eschneid Date 2010-09-20 Time 13:33 Rev Time 0.25
Received By eschneid Date 2010-09-20 Time 13:33 Sent To  
Notes
2010-09-20 13:34:00NOTE: PROPERTY ADDRESS UNDER "CODE/DESIGN PARAMETERS"
 IS INCORRECT - LISTS B.B KINGS.