Plan Review Details - Permit 10090185
Plan Review Stops For Permit 10090185
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-10-05 Cont ID  
Sent By rmcdouga Date 2010-10-05 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2010-10-05 Time 08:45 Sent To  
Notes
2010-10-05 08:47:14REVISED SHEETS D1, A1.O AND S2.O HAVE BEEN REVIEWED FOR
 CODE COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-01-06 Cont ID  
Sent By jleahy Date 2011-01-06 Time 08:20 Rev Time 0.00
Received By jleahy Date 2011-01-06 Time 08:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-09-29 Cont ID  
Sent By jleahy Date 2010-09-29 Time 07:55 Rev Time 0.00
Received By jleahy Date 2010-09-29 Time 07:55 Sent To  
Notes
2010-09-29 08:47:42BRANCH CIRCUITS SHALL COMPLY WITH 210.12 B
  
 ALL RECEPTACLE OUTLETS SHALL BE TAMPER RESISTANT.
 406.11
  
 MEANS SHALL BE PROVIDED FOR BONDING/GROUNDING OTHER
 SYSTEMS AT THE SERVICE 250.94
  
 OUTDOOR OUTLETS SHALL BE WEATHER RESISTANT. 406.8
  
 DESCRIPTION OF BRACH CIRCUITS NEED TO BE MORE SPECIFIC,
 408.4
  
 OUTLET SPACING AS SHOWN ON DRAWINGS DOES NOT MEET THE
 SPACING REQUIREMENTS OF 210.52 A 1,2
 KITCHEN COUNTER, HALLWAY,BEDROOMS ALL HAVE OUTLET
 SPACING VIOLATIONS.
  
 NO COMPRESSOR CIRCUIT SHOWN ON PANEL SCHEDULE OR
 DRAWING (LOCATION)
  
 EMERGENCY PANEL SCHEDULE NOT SHOWN.
  
 NEED SIZE OF PANEL SIZE OF WIRE, LISTING ON GENERATOR
 RECEPTACLE (EMERGENCY SYSTEM)
  
 OULETS ON OUTSIDE WALLS THAT ARE FACING OUTDOORS SHALL
 BE CONSIDERED A WET/DAMP LOCATION SEE 334.12 B 4
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-03 Cont ID  
Sent By lmartine Date 2011-01-03 Time 13:28 Rev Time 0.00
Received By lmartine Date 2011-01-03 Time 13:28 Sent To  
Notes
2011-01-03 13:28:46GAVE TO JAKE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-05 Cont ID  
Sent By rmcdouga Date 2010-10-05 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2010-09-08 Time 16:56 Sent To  
Notes
2010-09-08 16:56:11R8