Plan Review Details - Permit 10090014
Plan Review Stops For Permit 10090014
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2011-01-10 Cont ID  
Sent By jgomez Date 2011-01-10 Time 14:17 Rev Time 0.00
Received By jgomez Date 2011-01-10 Time 14:17 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-11-19 Cont ID  
Sent By jgomez Date 2010-11-19 Time 13:59 Rev Time 0.00
Received By jgomez Date 2010-11-19 Time 13:12 Sent To PC
Notes
2010-11-19 14:55:34BUILDING REVIEW THIRD CHECKLIST. 2007 FBC W/ 2009
 REVISIONS.
  
 ***ORIGINAL COMMENT:
 1- ENGINEER TO PROVIDE ENGINEERING ANALYSIS SHOWING HOW
 THE AWNING WILL RESIST THE 150 MPH, 3 SECOND GUST LOADS
 IN EXPOSURE "C" WHEN THE COVER IS IN PLACE. SEC.
 106.1.2 CITY AMENDMENTS TO FBC.
  
 ***RESPONSE TO INFORMATION SUBMITTED:
 REVISE GENERAL NOTES ON SHEET #2: (A)NOTE #3 STATES
 THAT COVER MUST BE REMOVED WHEN WINDS IN EXCESS OF 74
 MPH ARE EXPECTED.
  
 (B) NOTE #4 STATES THAT FRAMES WITHOUT FABRIC TO
 WITHSTAND 146 MPH WINDS PER FBC 2004 PER SEC. 1619.
 COVER IS SUPPOSED TO BE ON AND REVISE CODE YEAR AND
 SECTION.
  
 (C) NOTE #5 STATES THAT FRAMES WITH FABRIC COVERS ON
 ARE DESIGNED FOR 90 MPH ONLY.
  
 (D) NOTE #6 STATES THAT FRAMES WITHOUT COVERS DESIGNED
 AS PER ASCE 7-05. NEED TO BE CLEAR IF DESIGNING THE
 FRAME TO HAVE THE COVER OR NOT.
  
 (E) ENGINEER CALCULATIONS PROVIDED ARE DONE FOR 140 MPH
 WIND LOADS. GENERAL NOTES ON SHEET #2 SPECIFY 146 MPH
 WIND LOADS. REVISE CALCULATIONS AS REQUIRED.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-10-13 Cont ID  
Sent By jgomez Date 2010-10-13 Time 13:48 Rev Time 0.00
Received By jgomez Date 2010-10-13 Time 11:36 Sent To PC
Notes
2010-10-13 13:56:15BUILDING REVIEW SECOND CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ENGINEER TO PROVIDE ENGINEERING ANALYSIS SHOWING HOW
 THE AWNING WILL RESIST THE 150 MPH, 3 SECOND GUST LOADS
 IN EXPOSURE "C" WHEN THE COVER IS IN PLACE. SEC.
 106.1.2 CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-01 Cont ID  
Sent By ajones Date 2010-09-07 Time 11:07 Rev Time 0.00
Received By jgomez Date 2010-10-01 Time 11:03 Sent To PC
Notes
2010-10-01 11:30:08NEW AWNING BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PERMIT APPLICATION STATES THAT "AWNING COVER TO BE
 STAPLED TO ALUMINUM FRAME". CLARIFY HOW COMPLYING WITH
 THE QUICK REMOVAL SEC. 3105.4.2.1 AND THE READILY
 VISIBLE DECAL OR PAINTED INSTRUCTIONS TO REMOVE THE
 AWNING AS REQUIRED BY SEC. 3105.5.3 OF 2007 FBC.
  
 2- ENGINEERED DRAWINGS TO INDICATE THE DISTANCE FROM
 GRADE TO THE BOTTOM OF THE AWNING TO VERIFY COMPLIANCE
 WITH SEC. 3105.1.1.1 OF 2007 FBC.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-01-10 Cont ID  
Sent By jgomez Date 2011-01-10 Time 14:19 Rev Time 0.00
Received By jgomez Date 2011-01-10 Time 09:50 Sent To  
Notes
2011-01-10 09:50:55TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-11-19 Cont ID  
Sent By jgomez Date 2010-11-19 Time 15:03 Rev Time 0.00
Received By jgomez Date 2010-11-18 Time 13:12 Sent To  
Notes
2010-11-18 13:12:58TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-12 Cont ID  
Sent By jwitmer Date 2010-10-12 Time 12:51 Rev Time 0.00
Received By jwitmer Date 2010-10-12 Time 12:50 Sent To  
Notes
2010-10-12 12:51:00INCOMING SENT TO J GOMEZ DESK JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-01 Cont ID  
Sent By jgomez Date 2010-10-01 Time 11:30 Rev Time 0.00
Received By jgomez Date 2010-09-01 Time 15:20 Sent To  
Notes
2010-09-01 15:21:06TO ZONING
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-09-07 Cont ID  
Sent By ajones Date 2010-09-07 Time 11:05 Rev Time 0.00
Received By ajones Date 2010-09-02 Time 17:33 Sent To B
Notes
2010-09-07 11:08:52AWNING APPROVAL ONLY FOR ATM