Plan Review Details - Permit 10080805
Plan Review Stops For Permit 10080805
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-05 Cont ID  
Sent By shill Date 2010-10-05 Time 08:21 Rev Time 0.00
Received By shill Date 2010-10-05 Time 08:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-08 Cont ID  
Sent By shill Date 2010-09-08 Time 10:38 Rev Time 0.00
Received By shill Date 2010-09-08 Time 10:38 Sent To  
Notes
2010-09-08 10:44:23****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE OPENING 2, HORIZONTAL INSTALLATION REQUIRES USE
 OF MASONRY SUBSTRATE CHART OR PROVIDE EVIDENCE THAT
 BOTH SIDES ARE FORMED AND POURED CONCRETE. ANCHOR
 SPACING PROPOSED DOES NOT COMPLY WITH REQUIREMENTS OF
 THE PRODUCT APPROVAL.
  
 2. SEE OPENING 3, 16" SPACING DOES NOT COMPLY WITH THE
 REQUIRMENTS OF THE PRODUCT APPROVAL. NOTE THAT TOP AND
 BOTOTM HAVE SAME CONNECTION TYPE, SAME SUBSTRATE, ETC.
 BUT DIFFERENT ANCHOR SPACING.
  
 3. THE INFORMATION HIGHLIGHTED ON THE PRODUCT APPROVAL
 SHOULD CORRELATE WITH THE INSTALLATION SCHEDULE.
 TAPCONS SPECIFIED ON THE INSTALLATION SCHEDULE, ELCO
 PANELMATE HIGHLIGHTED. PLEASE CORRELATE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-20 Cont ID  
Sent By rregueir Date 2010-09-20 Time 16:04 Rev Time 0.00
Received By rregueir Date 2010-09-20 Time 16:04 Sent To  
Notes
2010-10-05 08:22:11TO PROCESSING
  
2010-09-20 16:05:12TO SAMANTHA HILL'S DESK FOR 2ND REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-08 Cont ID  
Sent By shill Date 2010-09-08 Time 10:44 Rev Time 0.00
Received By shill Date 2010-08-31 Time 10:46 Sent To  
Notes
2010-08-31 10:46:28UNDER 5 K BUILDING