Plan Review Details - Permit 10080641
Plan Review Stops For Permit 10080641
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-09-01 Cont ID  
Sent By jwitmer Date 2010-09-01 Time 16:09 Rev Time 2.22
Received By jwitmer Date 2010-09-01 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-09-13 Cont ID  
Sent By jleahy Date 2010-09-13 Time 07:36 Rev Time 0.00
Received By jleahy Date 2010-09-13 Time 07:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-25 Cont ID  
Sent By ddaniels Date 2011-01-25 Time 12:27 Rev Time 0.00
Received By ddaniels Date 2011-01-25 Time 12:27 Sent To  
Notes
2011-01-25 12:28:331/25/11 PLANS REVIEWED BY FIRE ***APPROVED***
  
 CAPTAIN DANIELS
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-09-17 Cont ID  
Sent By mcarsill Date 2010-09-17 Time 12:57 Rev Time 0.00
Received By mcarsill Date 2010-09-17 Time 12:57 Sent To  
Notes
2010-09-17 13:00:22205 DATURA STREET
 PERMIT NUMBER 10080641
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEM REMODELING.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-28 Cont ID  
Sent By jgomez Date 2010-10-25 Time 08:24 Rev Time 0.00
Received By jgomez Date 2010-10-28 Time 08:57 Sent To M
Notes
2010-10-28 08:58:25SENT TO R. REGUEIRO'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-30 Cont ID  
Sent By lmartine Date 2010-09-17 Time 14:15 Rev Time 0.00
Received By lmartine Date 2010-08-24 Time 11:44 Sent To  
Notes
2010-08-24 11:44:55B16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-11-09 Cont ID  
Sent By rregueir Date 2010-11-09 Time 16:03 Rev Time 0.00
Received By rregueir Date 2010-11-09 Time 16:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-09-10 Cont ID  
Sent By rregueir Date 2010-09-10 Time 11:20 Rev Time 0.00
Received By rregueir Date 2010-09-10 Time 10:43 Sent To  
Notes
2010-09-10 11:19:01REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLAN REVIEW COMMENTS:
  
 1. PROVIDE SYMBOL LEGEND FOR ALL HVAC PLANS. SOME
 SYMBOLS ARE IDENTIFIED WITH ARROWS AND NOTES WHILE
 OTHERS ARE NOT. PLEASE CLARIFY PER FBC-B 106.1.1.
  
 2. PLANS INDICATE SEVERAL SPACES ARE BEING
 RECONFIGURED. ALL RECONFIGURED SPACES INTENDED FOR
 OCCUPANCY IN ANY WORK AREA SHALL BE PROVIDED WITH
 MECHANICAL VENTILATION OR EXHAUST IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, MECHANICAL PER FBC-EB 709.1
 SEE FBC-M SECTION 403 FOR MECHANICAL VENTILATION
 REQUIREMENTS AND PROVIDE SPACE-BY-SPACE CALCULATIONS
 BASED ON FBC-M TABLE 403.3. ALSO, PROVIDE AIR
 QUANTITIES ON PLANS TO FACILITATE PROPER TEST AND
 BALANCE OF AIR DISTRIBUTION SYSTEM FOR NEW RATES PER
 FBC-M 403.3.4.
  
 3. PAGE A-11 SHOWS CONFLICTING RETURN GRILLS IN CEILING
 OF THE NEW WAITING ROOM. PLEASE CLARIFY. FBC-B 106.1.1.
  
 4. PAGE A-19: TERMINAL BOX 1-1 APPEARS TO BE ELIMINATED
 FROM REVISED HVAC PLAN WHILE THE DUCT IS STILL SHOWN
 FEEDING NEW OFFICE #2. PLEASE CLARIFY PER FBC-M 603.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2010-09-03 Cont ID  
Sent By aaponte Date 2010-09-03 Time 14:36 Rev Time 0.00
Received By aaponte Date 2010-09-03 Time 14:36 Sent To  
Notes
***NONE***