Plan Review Details - Permit 10080589
Plan Review Stops For Permit 10080589
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2010-11-03 Time   Rev Time 0.00
Received By   Date 2010-11-03 Time   Sent To  
Notes
2010-11-04 08:54:05PASSED PER JIM WITMER. RJR

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-08 Cont ID  
Sent By jwitmer Date 2010-09-08 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2010-09-08 Time 10:00 Sent To  
Notes
2010-09-08 17:54:43BUILDING PLAN REVIEW
 PERMIT: 10080589
 ADD: 1000 45TH ST
 CONT: CATALFUMO
 TEL: (561)694-8853
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS * WEST PALM BEACH AMENDMENTS
 EXISTING BUILDING CODE 2007 W/ 2009 SUPPLEMENTS
  
 EXIST BLDG CODE-912.1.1 COMPLIANCE WITH CHAPTER 8. THE
 REQUIREMENTS OF CHAPTER 8 SHALL BE APPLICABLE
 THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY
 CLASSIFICATION BASED ON THE SEPARATION CONDITIONS SET
 FORTH IN SECTIONS 912.1.1.1(NON-SEPARATED) AND
 912.1.1.2 (SEPARATED).
  
 801.2 COMPLIANCE. IN ADDITION TO THE PROVISIONS OF THIS
 CHAPTER, WORK SHALL COMPLY WITH ALL OF THE REQUIREMENTS
 OF CHAPTERS 6 AND 7.
  
 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 SEE 4 EXCEPTIONS.
  
 1ST REVIEW
 ACTION: DENIED
 BLDG# 1
 1) SHEET LSP-1 THE BUILDING CODE ANALYSIS INDICATES A
 NON-SEPARATED USE PER 508.3.2. PLEASE EXPLAIN THE 2
 HOUR RATED ASSEMBLY BETWEEN THE BUSINESS AND R-1
 OCCUPANCY, PLEASE PROVIDE THE ASSEMBLY TYPE? FBC-B
 TABLE 508.3.3/ FBC-B 712.3.11 & 712.3.1.2.
  
 2 SHEET LSP-1 ROOM 1-117 MEN???S INTAKE 3-BEDS PLEASE
 REVIEW TERMINOLOGY BETWEEN FIRE BARRIER AND FIRE
 PARTITIONS. FBC-B 438.2 REQUIRES EACH SLEEPING UNIT TO
 BE SEPARATED WITH 1 HOUR SEPARATION AS WELL AS FIRE
 RESISTANCE RATED ASSEMBLIES COMPLYING WITH SECTION 711.
 PLEASE REVIEW ALSO CODE COMMENTARY AND SECTION FBC-B
 708 & 711. PLEASE NOTE SECTION FBC-B 708.3EXCEPTION# 2
 REQUIRES THE BUILDING TO BE FIRE SPRINKLERED THROUGHOUT
 TO TAKE THE 1/2 HR REDUCTION, NOT PARTIALLY SPRINKLERED
 AS NOTED IN THE CODE ANALYSIS NOTE NUMBER (4) BUILDING
 # 1.
  
 3) SHEET LSP-1 IN REVIEWING FBC-B 438.2 THE WOMEN???S
 INTAKE 3-BED SLEEPING ROOMS WILL ALSO REQUIRE 1 HR FIRE
 SEPARATION PER FBC-B 708.3 & 711.3. SHEET A-8 DOOR
 SCHEDULE. LADIES INTAKE DOOR # 107 SHOULD ALSO BE A 20
 MINUTE RATED DOOR FBC-B TABLE 715.4.
  
  
 3A) SHEET LSP-1 BUILDING# 1 ISN???T FIRE SPRINKLERED,
 PLEASE REVIEW FBC-B SECTION 508.2, 508.2..2 SEPARATION,
 508.2.2.1 CONSTRUCTION & TABLE 508.2 SEE SEPARATION AND
 OR PROTECTION FOR MECHANICAL ROOMS, LAUNDRY ROOMS
 STORAGE ROOMS AND LINEN ROOMS. PLEASE ALSO REVIEW SHEET
 A-8 DOOR SCHEDULE MISSING FIRE RATINGS PER FBC-B TABLE
 715.4.
  
  
  
 BLDG# 2
 4) SHEET LSP-1 VESTIBULE 2-247 & 2-251 11-4.13.7 TWO
 DOORS IN SERIES. THE MINIMUM SPACE BETWEEN TWO HINGED
 OR PIVOTED DOORS IN SERIES SHALL BE 48 INCHES (1219 MM)
 PLUS THE WIDTH OF ANY DOOR SWINGING INTO THE SPACE.
 DOORS IN SERIES SHALL SWING EITHER IN THE SAME
 DIRECTION OR AWAY FROM THE SPACE BETWEEN THE DOORS [SEE
 FIGURE 26(A)].
  
 5) SHEET LSP-1 11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIGURE 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR.
  
 6) SHEET LSP-1 FAMILY ROOMS 1-3, ARE THESE ROOMS TO BE
 USED AS SLEEPING ROOMS? FBC-438.2/ 708.3 & 711.3.
  
 6A) SHEET LSP-1 BUILDING# 2 ISN???T FIRE SPRINKLERED,
 PLEASE REVIEW FBC-B SECTION 508.2, 508.2..2 SEPARATION,
 508.2.2.1 CONSTRUCTION & TABLE 508.2 SEE SEPARATION AND
 OR PROTECTION FOR MECHANICAL ROOMS, LAUNDRY ROOMS
 STORAGE ROOMS AND LINEN ROOMS.
  
 6B) THE FAMILY ROOMS, LOUNGE (2-200) AND CHILDREN???S/
 RECREATION APPEARS TO BE MISS LABELED AS TO OCCUPANCY,
 BUSINESS OCCUPANCIES USUALLY PROVIDE A TYPE OF SERVICE,
 EXAMPLE HAIR SALON, BARBER SHOP DENTIST OR DOCTOR WHAT
 SERVICES ARE BEING PROVIDED FOR THIS AREA? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 BUILDING # 3
 7) SHEET LSP-2 PLEASE REVIEW THE TERM FIRE BARRIER AND
 FIRE PARTITION AS PER FBC-B 438.2 & 708.3 EXCEPTION# 2.
 ALL SLEEPING ROOMS WILL REQUIRE THE 1/2 HR FIRE RATED
 WALLS.
 PLEASE REVIEW FBC-B 708.4 FOR CONTINUITY AND
 EXCEPTIONS.
  
 8) SHEET LSP-2 438.3 HORIZONTAL SEPARATION.
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS IN
 THE SAME BUILDINGS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING SLEEPING UNITS IN THE SAME BUILDING SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711. 708.3
 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
 EXCEPTIONS:
 2.DWELLING AND SLEEPING UNIT SEPARATIONS IN BUILDINGS
 OF TYPE IIB, IIIB AND VB CONSTRUCTION SHALL HAVE
 FIRE-RESISTANCE RATINGS OF NOT LESS THAN 1/2 HOUR IN
 BUILDINGS EQUIPPED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1.
  
 9) SHEET LSP-2 THE 2ND FLOOR THE WEST SIDE OF THE
 SECOND FLOOR, PLEASE PROVIDE COMPLIANCE WITH SECTION
 FBC-B TABLE 1017.1. IT APPEARS THERE ARE MORE THAN 10
 OCCUPANTS EXITING FROM THE BED ROOM CONFIGURATION THAT
 WOULD REQUIRE THE LOUNGE AREA TO BE CONSIDERED A RATED
 EXIT. PLEASE PROVIDE AN ANALYSIS OF THIS AREA.
  
 10) SHEET LSSP-1 INDICATES THE BUILDING# 2 HAVING A
 HEALTH CLINIC INSIDE. PLEASE REVIEW
 FBC-B 11-4.1.2(5)(D)(I) OUTPATIENT UNITS AND
 FACILITIES: 10 PERCENT OF THE TOTAL NUMBER OF PARKING
 SPACES PROVIDED SERVING EACH SUCH OUTPATIENT UNIT OR
 FACILITY;
  
 11) SHEET A-2 SECOND FLOOR BALCONY. 1-4.3.7 SLOPE. AN
 ACCESSIBLE ROUTE: NOWHERE SHALL THE CROSS SLOPE OF AN
 ACCESSIBLE ROUTE EXCEED 1:50. PLEASE INDICATE HOW MUCH
 THE HEIGHT WILL CHANGE, IT MAY POSSIBLY BE CONSIDERED A
 RAMP, PLEASE PROVIDE SLOPE.
  
 12) SHEET A-2 & A-8/ A-8.1 PLEASE REVIEW THE
 REQUIREMENTS UNDER THE EXISTING BUILDING CODE 705.5 AS
 TO RATINGS FIRE AND SMOKE, CLOSERS AND EXCEPTIONS.
  
 13) SHEET A-7 & A-7.1 RESTROOMS AND SHOWERS WALLS THE
 SCHEDULE INDICATES BACKER BOARD BUT NOT A TYPE PLEASE
 BE AWARE OF:
 GYPSUM BOARDS IN SHOWERS & WATER CLOSETS
 2509.1 WET AREAS. SHOWERS AND PUBLIC TOILET WALLS SHALL
 CONFORM TO SECTION 1210.2 AND 1210.3.
 2509.2 BASE FOR TILE. CEMENT, FIBER-CEMENT OR GLASS MAT
 GYPSUM BACKERS IN COMPLIANCE WITH
 ASTM C 1178-08 STANDARD SPECIFICATION
 FOR COATED GLASS MAT WATER-RESISTANT GYPSUM
 ASTM C 1288-99 STANDARD SPECIFICATION
 FOR DISCRETE NON- ASBESTOS FIBER-CEMENT INTERIOR
 SUBSTRATE SHEETS
 ASTM C 1325-08 STANDARD SPECIFICATION
 FOR NON-ASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS
 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING
 BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 14) SHEET A-3 & A-4 PLEASE PROVIDE COMPLIANCE WITH
 11-9.5.2(2) HOMELESS SHELTERS (E)
 AT LEAST ONE ROUTE CONNECTING ELEMENTS SECTIONS
 11-9.5.2(2)(A),11-9.5.2(2)(B), 11-9.5.2(2)(C),
 11-9.5.2(2)(D), WHICH A PERSON WITH MOBILITY
 IMPAIRMENTS CAN USE, INCLUDING MINIMUM CLEAR WIDTH OF
 36 INCHES (914 MM), PASSING SPACE COMPLYING WITH
 SECTION 11-4.3.4, TURNING SPACE COMPLYING WITH SECTION
 11-4.2.3 AND CHANGES IN LEVELS COMPLYING WITH SECTION
 11-4.3.8. (E) AT LEAST ONE ROUTE CONNECTING ELEMENTS
 SECTIONS 11-9.5.2(2)(A),11-9.5.2(2)(B), 11-9.5.2(2)(C),
 11-9.5.2(2)(D), WHICH A PERSON WITH MOBILITY
 IMPAIRMENTS CAN USE, INCLUDING MINIMUM CLEAR WIDTH OF
 36 INCHES (914 MM), PASSING SPACE COMPLYING WITH
 SECTION 11-4.3.4, TURNING SPACE COMPLYING WITH SECTION
 11-4.2.3 AND CHANGES IN LEVELS COMPLYING WITH SECTION
 11-4.3.8.
  
 15) 11-9.5.3 ACCESSIBLE SLEEPING ACCOMMODATIONS IN NEW
 CONSTRUCTION. ACCESSIBLE SLEEPING ROOMS SHALL BE
 PROVIDED IN CONFORMANCE WITH THE TABLE IN SECTION
 11-9.1.2 AND SHALL COMPLY WITH SECTION 11-9.2 (WHERE
 THE ITEMS ARE PROVIDED). ADDITIONAL SLEEPING ROOMS THAT
 COMPLY WITH SECTION 11-9.3 SHALL BE PROVIDED IN
 CONFORMANCE WITH THE TABLE PROVIDED IN SECTION
 11-9.1.3.
  
 IN FACILITIES WITH MULTIBED ROOMS OR SPACES, A
 PERCENTAGE OF THE BEDS EQUAL TO THE TABLE PROVIDED IN
 SECTION 11-9.1.2 SHALL COMPLY WITH SECTION 11-9.2.2(1).
  
 11-9.3.2 EQUIVALENT FACILITATION. FOR PURPOSES OF THIS
 SECTION, EQUIVALENT FACILITATION SHALL INCLUDE THE
 INSTALLATION OF ELECTRICAL OUTLETS (INCLUDING OUTLETS
 CONNECTED TO A FACILITY'S CENTRAL ALARM SYSTEM) AND
 TELEPHONE WIRING IN SLEEPING ROOMS AND SUITES TO ENABLE
 PERSONS WITH HEARING IMPAIRMENTS TO UTILIZE PORTABLE
 VISUAL ALARMS AND COMMUNICATION DEVICES PROVIDED BY THE
 OPERATOR OF THE FACILITY.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-11-08 Cont ID  
Sent By jdickins Date 2010-11-08 Time 16:55 Rev Time 0.00
Received By jdickins Date 2010-11-08 Time 16:55 Sent To  
Notes
2010-11-08 16:56:45OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-10-04 Cont ID  
Sent By jwitmer Date 2010-10-04 Time 16:19 Rev Time 0.00
Received By jwitmer Date 2010-10-04 Time 16:19 Sent To  
Notes
2010-10-04 16:52:21***************ELECTRICAL PLAN REVIEW
 FAIL***************
  
 1) LIGHTING POWER DENSITIES REQUIRED FOR ALL NON
 RESIDENTIAL AREAS OF ALL THREE BUILDINGS AS PER CHAPTER
 13 2007 FLORIDA BUILDING CODE
  
 2) LIGHTING POWER DENSITIES REQUIRED FOR PARKING LOT
 LIGHTING, AS PER CHAPTER 13 2007 FLORIDA BUILDING CODE
  
 3) PLAN SHOWES PARALLEL FEEDS TO PANEL DH-3, EQUIPMENT
 GROUNDING CONDUCTORS ARE REQUIRED TO BE FULL SIZE IN
 EACH CONDUIT AS PER SIZE OF OVERCURRENT PROTECTIVE
 DEVICE AS PER ARTICLE 250.122(F) 2008 NEC
  
  
 JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE NUMBER
 PX3182
 CELL NUMBER 561 718 3230

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2010-11-10 Cont ID  
Sent By mgonzale Date 2010-11-10 Time 14:54 Rev Time 2.00
Received By mgonzale Date 2010-11-10 Time 14:54 Sent To  
Notes
2010-11-10 14:58:07UTILITY PLANS SUBMITTED NOV 9TH HAVE BEEN REVISED PER
 CWPB COMMENTS (FIRE AND ENGINEERING)
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-10-05 Cont ID  
Sent By mgonzale Date 2010-10-05 Time   Rev Time 1.50
Received By mgonzale Date 2010-10-05 Time   Sent To  
Notes
2010-10-05 10:27:58FAILED:
  
 #1 TRUNCATED DOMES MISSING IN CRITICAL AREAS PLEASE
 REVISE PER MARK-UP. (SEE C2.1)
 #2 CLEAN UP C1.1 AS MARKED (ANY WORK TO BE PERFORMED IN
 WINDSOR AVE ROW WILL REQUIRE A ROW PERMIT.
 SEE INTERNET LINK:
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
 SEE ROW PARMIT APPLICATION DOCUMENT
 #3 DCDA FOR FIRELINE NEEDS TO BE AT PROPERTY LINE. (SEE
 C5.1)
 #4 FIRE HYDRANT ON-SITE WILL BE CONSIDERED "PRIVATE",
 YOU MAY BE REQUIRED TO INSTALL NEW HYDRANT AT PROPERTY
 LINE IF CLOSEST HYDRANT IS MORE THAT 150' FROM FDC
 LOCATION.
 #4A CITY STANDARD DETAIL P-8 IS MISSING. AFTER
 REVISION, FIRE MARSHALL MUST APPROVE PLAN PRIOR TO
 ENGINEERING PASS.
 #5 HYDRANT TEST REQUIRED AT NEAREST FIRE HYDRANT AS
 PART OF THE NEXT REVISION SUBMITTAL.
 TEST CAN BE SCHEDULED THRU THE CITY OF WPB FIRE
 MARSHALL'S OFFICE (561) 822-1200.
 #6 PARKING COUNT IN PARKING AREA CLOSES TO WINDSOR
 AVENUE IS LOWER THAN SHOWN. RECOUNT SPACES. SHT C2.1
 #8 ENTRANCE AT 45TH STREET NEEDS TO BE CLARIFIED OR
 STRIPED TO ACCOMODATE TRAFFIC OPERATION. 1 DRIVE IN 1
 DRIVE OUT. STRIPPING NEEDS TO BE WITHIN A CERTAIN WIDTH
 TO AVOID TWO VEHICLES EXITING AT THE SAME TIME.
 ANY CHANGES FROM THE 1 DRIVE IN AND 1 DRIVE OUT PATTERN
 SHOULD BE DISCUSSED WITH PALM BEACH COUNTY ROADWAY.
 #9 TRUNCATED DOMES AND ADA WILL BE REQUIRED AS THE
 DRIVEWAY IS PART OF YOUR DESIGN RESPONSABILITY.
 (DEPARTMENT OF JUSTICE, ADA
 ACCESSIBILITY GUIDELINES -ADAAG, ACCESSIBLE
 RIGHTS-OF-WAY, CHAPTER 3, SUBSECTION
 3.2)
 #10 STRIPPING HAS BEEN MARKED UP ON SHEET C2.1
 #11 SHEET C3.1 (NEEDS TO REFLECT PERVIOUS AND
 IMPERVIOUS AREAS. TOTAL SITE SF. ALSO)
 #12 CITY STANDARD TAPPING VALVE DETAIL IS MISSING.
 #13 POLLUTION PREVENTION PLAN MISSING WITH DETAILS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-10-29 Cont ID  
Sent By mcarsill Date 2010-10-29 Time 10:10 Rev Time 0.00
Received By mcarsill Date 2010-10-29 Time 09:57 Sent To  
Notes
2010-10-29 10:10:45PALM BEACH COUNTY HOMELESS RESOURCE CENTER
 1000-45TH STREET
 PERMIT NUMBER 10080589
  
  
 1. BUILDING ADDRESSES ARE REQUIRED TO BE POSTED ON THE
 BUILDINGS. THE BUILDING ADDRESS ONLY ON THE MARQUEE
 SIGN DOES NOT MEET CODE REQUIREMENTS. BUILDING
 ADDRESSES SHALL BE A MINIMUM OF AT LEAST 6" HIGH AND AT
 LEAST 1" WIDE THAT CONTRAST TO THE BACKGROUND THAT THEY
 ARE AFFIXED TO.
  
 2. ENSURE THAT EMERGENCY LIGHTS EXIST IN STAIRWELL
 3-125 AND 3-128.
  
 3. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND
 CEILINGS SHALL COMPLY WITH THE FLORIDA BUILDING CODE
 AND THE FLORIDA FIRE PREVENTION CODE.
  
 4. ENSURE PANIC HARDWARE IS PRESENT ON EXIT DOORS IN
 DINING AREA IF OCCUPANT LOADS ARE EXPECTED TO 100 OR
 MORE PERSONS.
  
 5. THE CHILDREN'S WAITING AREA SHALL BE EQUIPPED WITH
 DUPLEX OUTLETS PROTECTIVE COVERS.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 7. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A THIRD
 PARTY APPROVED FOR CENTRAL STATION SERVICE
 REQUIREMENTS.
  
 8. ELECTRONIC LOCKING DEVICES USED ON EXIT DOORS SHALL
 COMPLY WITH CHAPTER 7 OF THE FLORIDA FIRE PREVENTION
 CODE (101 THE LIFE SAFETY CODE, 2006 EDITION)
  
 9. SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-23 Cont ID  
Sent By wjolin Date 2010-09-23 Time 10:11 Rev Time 0.00
Received By wjolin Date 2010-09-13 Time 11:03 Sent To  
Notes
2010-09-23 10:10:481000 45TH STREET
 HOMELESS SHELTER
 PERMIT #10080589
  
 SHEET LSP-2:
  
 -PROVIDE VISUAL FIRE ALARM NOTIFICATION APPLIANCES IN
 ALL RESTROOMS.
  
 -PROVIDE ADDITIONAL INFORMATION ON DETEX DOOR HARDWARE.
  
 -SINGLE STATION SMOKE ALARMS ARE REQUIRED IN EVERY
 GUEST ROOM, LIVING AREA AND SLEEPING ROOM WITHIN A
 GUEST SUITE PER 28.3.4.5 (FFPC).
  
 -BUILDING #3: TRAVEL DISTANCE WITHIN A GUEST SUITE TO A
 CORRIDOR SHALL NOT EXCEED 75 FEET IN BUILDINGS
 PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM PER 28.2.6.2
 (FFPC).
  
 -PERMANENTLY LOCKED DOORS SHALL BE LABELED WITH ???NO
 EXIT??? SIGNS.
  
 WESLEY JOLIN
 CITY OF WEST PALM BEACH
 FIRE & LIFE SAFETY PLAN REVIEW
 561-805-6730
  
  
2010-09-13 12:04:39HOMELESS RESOURCE CENTER
 PERMIT NUMBER 10080589
 1000 BLOCK OF 45TH STREET
  
 1. THE BUILDINGS PRIOR TO THE SUBMITTAL OF THESE PLANS
 WERE BEING USED AS A GROUP "B" OR BUSINESS USE. THE
 PROPOSED BUILDINGS AND DESIGNS ARE DIFFERENT FROM
 PREVIOUSLY USES WHICH SEEMS TO SUGGEST A CHANGE OF USE
 OF SOME OF THESE FACILITIES.
  
 2. KNOX-BOXES WILL BE NEEDED FOR THE BUILDINGS. PLEASE
 GO TO WWW.KNOXBOX.COM TO ORDER THE BOXES.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS
 OFTEN AS NECESSARY.
  
 4. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 5. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 6. SMOKE DETECTION EQUIPMENT SHALL BE INSTALLED A
 MINIMUM OF AT LEAST THREE FEET FROM AIR CONDITIONER
 DIFFUSERS.
  
 7. ELEVATOR WARNING SIGNS ARE NEEDED.
  
 8. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER INSTALLATIONS.
  
 9. AN EMERGENCY PLAN IS TO BE SUBMITTED TO THIS OFFICE.
 THIS EMERGENCY PLAN SHALL BE DEVELOPED USING AN "ALL
 HAZARDS" APPROACH AND SHOULD INCLUDE PLANNING AND
 TRAINING FOR FIRES, INCLEMENT WEATHER, MEDICAL
 EMERGENCIES, ETC.
  
 10. CARD READERS SHALL NOT INTERFERE WITH ANY EXITING
 FROM THE BUILDINGS.
  
 11. ON PAGE E-4 AN ADDITIONAL EXIT SIGN APPEARS TO BE
 NEEDED ON THE OUTSIDE OF THE ADULT INTAKE AREA 1-136.
  
 12. ON PAGE E-7 NO ILLUMINATED EXIT SIGNS OR EMERGENCY
 LIGHTING SHOWN FOR THE BUSINESS AREA.
  
 13. ON SHEET LSP-1 DOORS "THAT ARE TO REMAIN LOCKED AT
 ALL TIMES" ARE PROVIDED WITH EGRESS CAPACITIES BUT ARE
 NOT EQUIPPED WITH EXIT SIGNS. IF THEY ARE NOT REQUIRED
 EXITS, THEN EGRESS CAPACITIES SHOULD NOT BE CALLED OUT.
  
 14. AN EGRESS DOOR APPEARS TO BE IN CLOSE PROXIMITY TO
 AN UNPROTECTED WINDOW OPENING FROM AN ADJACENT BUILDING
 ON PAGE LSP-1.
  
 15. PLEASE INDICATE THE COMBUSTIBILITY FACTOR FOR THE
 PROPOSED MATTRESSES.
  
 16. ALL RATED FIRE DOORS ARE TO BE PROPERLY LABELED AND
 BE EQUIPPED WITH SELF-CLOSING DEVICES TO CAUSE THE
 DOORS TO POSITIVELY LATCH WHEN OPENED.
  
 17. PLEASE INDICATE THE LOCATIONS OF "NO SMOKING" SIGNS
 AND AREAS AND THE LOCATIONS OF DESIGNATED SMOKING AREAS
 AND SIGNAGE.
  
 18. PLEASE EXPLAIN THE TERM "LANDING KITCHEN" AS
 ILLUSTRATED ON THE PLANS.
  
 19. GAS SERVICES SHALL COMPLY WITH NFPA 54, 2006
 EDITION.
  
 20. PLEASE INDICATE CONTENTS AND AMOUNT OF MATERIALS IN
 THE BUFFER TANK ON SHEET M-12.
  
 21. ON LSP-1 "FAMILY ROOMS" ARE NOTED. PLEASE INDICATE
 PURPOSE AND FURNISHINGS PLANNED FOR THESE ROOMS. ARE
 ANY SLEEPING PURPOSES PLANNED FOR THESE ROOMS.
  
 22. FAMILY ROOM # 3 HAS TRAVEL DISTANCE GOING THROUGH A
 DOOR THAT IS NOT IDENTIFIED AS AN EXIT.
  
 23. ON THE LIFE SAFETY SHEETS, SOME SLEEPING ROOMS ARE
 RATED AND EQUIPPED WITH FIRE DOORS AND OTHERS ARE NOT.
 PLEASE EXPLAIN RATIONALE.
  
 24. PLEASE EXPLAIN CHILDREN'S/RECREATION (2-220) AREA.
  
 25. ON THE FIRE SPRINKLER DRAWINGS CHECK VALVES FOR THE
 FIRE DEPARTMENT CONNECTIONS COULD NOT BE LOCATED. ALSO
 THE NEW FIRE HYDRANT IS TO BE LOCATED NO FARTHER THAN
 150 FEET FROM THE FIRE DEPARTMENT CONNECTIONS. PLEASE
 EXPLAIN PURPOSE OF DRY FIRE DEPARTMENT CONNECTION
 LINES.
  
 26. TAMPER SWITCHES, CHAIN AND LOCKS ARE REQUIRED ON
 FIRE LINE BACKFLOW DEVICE.
  
 27. HOW WILL FURNITURE AND CLOTHING BE ARRANGED AND
 MAINTAINED AND PLEASE DOCUMENT STORAGE HEIGHTS IN THE
 STORAGE OR GROUP "S" BUILDING.
  
 28. PLEASE INDICATE PURPOSE AND DURATION OF EXPECTED
 OCCUPANCY OF THE INTAKE AREAS.
  
 29. THE PLANS SEEM TO SUGGEST SMOKE DETECTOR
 INSTALLATIONS WITH NO MENTION OF SMOKE ALARM
 INSTALLATIONS. SMOKE DETECTORS ARE USUALLY CONNECTED TO
 FIRE ALARM SYSTEMS AND SMOKE ALARMS ARE CONNECTED ONLY
 TO THE ELECTRICAL SYSTEM. PLEASE CLARIFY ALL SMOKE
 DETECTION EQUIPMENT.
  
 30. SHEET FP-2 IS NOT VERY CLEAR. IT APPEARS THAT MORE
 THAN TWELVE FIRE SPRINKLER HEADS WILL BE NEEDED.
  
 31. THE PLANS DO NOT SEEM TO CALL OR IDENTIFY
 PROTECTION FROM HAZARDS. ROOMS THAT CAN BE CONSIDERED
 MORE HAZARDOUS SUCH AS BOILER, FURNACE, ELECTRICAL
 ROOMS, ETC. NEED TO BE PROTECTED FROM OTHER PORTIONS OF
 THE BUILDINGS. PLEASE INDICATE HOW THIS IS BEING
 ACCOMPLISHED.
  
 32. PLEASE REVIEW SECTION 310 OF THE FLORIDA BUILDING
 CODE FOR EXPLANATIONS OF R-1 AND R-2 OCCUPANCY TYPES.
 R-1 OCCUPANCIES ARE TRANSIENT AND R-2 OCCUPANCIES ARE
 PERMANENT. IT HAS BEEN SUGGESTED IN MEETINGS THAT
 OCCUPANCY AT THIS FACILITY IS MORE TRANSIENT IN NATURE
 (90) DAYS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2010-11-08 Cont ID  
Sent By lwagner Date 2010-11-08 Time 12:39 Rev Time 0.00
Received By lwagner Date 2010-11-08 Time 11:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2010-10-01 Cont ID  
Sent By lwagner Date 2010-10-01 Time 13:44 Rev Time 0.00
Received By lwagner Date 2010-10-01 Time 13:16 Sent To  
Notes
2010-10-01 13:40:57FBC FUEL GAS 2007 REVIEW #1
 DENIED:
  
 IF FUEL GAS IS INCLUDED WITH PLAN:
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL).
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2007 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ???
 USE OF CAPACITY SECTION A.3.1(4)
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2007 FUEL GAS CODE SEC. 304
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2007 FUEL GAS CODE
 SEC. 502 THRU 505.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2007 FUEL GAS SEC. 402.2
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO:
 CHIEF PLUMBING INSPECTOR (561) 805-6692
 PLUMBING PLANS EXAMINER (561) 805-6721
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2010-11-16 Time   Rev Time 0.00
Received By rregueir Date 2010-10-18 Time 11:30 Sent To  
Notes
2010-11-15 11:31:23**ELECTRONIC PLANS** SEE PROJECTDOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-10-04 Time   Rev Time 0.00
Received By rregueir Date 2010-08-25 Time 13:13 Sent To  
Notes
2010-08-25 13:13:34**ELECTRONIC PLANS** SEE PROJECTDOX

Review Stop L LANDSCAPING
Rev No 3 Status N Date 2010-11-16 Cont ID  
Sent By ajones Date 2010-11-16 Time 15:12 Rev Time 0.00
Received By ajones Date 2010-11-16 Time 15:12 Sent To  
Notes
2010-11-16 15:13:02APPLICANT SUBMITTED SEPERATE LANDSCAPE PERMIT #10110339

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-10-27 Cont ID  
Sent By rkussner Date 2010-10-27 Time 15:25 Rev Time 0.00
Received By rkussner Date 2010-10-27 Time 15:25 Sent To  
Notes
2010-10-27 15:26:50***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: PLEASE APPLY FOR A SEPARATE
 LANDSCAPE PERMIT. SUBMIT THE LANDSCAPE PERMIT
 APPLICATION, TWO (2) SETS OF LANDSCAPE PLANS AND A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 2. REPEAT COMMENT: EVERY LANDSCAPE ISLAND IS REQUIRED
 TO HAVE A SHADE OR FLOWERING TREE. AT LEAST FOUR (4) OR
 MORE ISLANDS ARE MISSING TREES.
  
 3. REPEAT COMMENT: IRRIGATION REQUIRES A SEPARATE
 PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-09-20 Cont ID  
Sent By rkussner Date 2010-09-20 Time 15:41 Rev Time 0.00
Received By rkussner Date 2010-09-20 Time 15:41 Sent To  
Notes
2010-09-20 15:56:00***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT
 THE LANDSCAPE PERMIT APPLICATION, TWO (2) SETS OF
 LANDSCAPE PLANS AND A CERTIFIED COST ESTIMATE THAT
 INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND
 LABOR, BROKEN DOWN INTO UNIT COST.
  
 2. EVERY LANDSCAPE ISLAND IS REQUIRED TO HAVE A SHADE
 OR FLOWERING TREE. AT LEAST FOUR (4) OR MORE ISLANDS
 ARE MISSING TREES.
  
 3. IRRIGATION REQUIRES A SEPARATE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-11-04 Cont ID  
Sent By rregueir Date 2010-11-04 Time 08:50 Rev Time 0.00
Received By rregueir Date 2010-10-20 Time 09:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-09-13 Cont ID  
Sent By rregueir Date 2010-09-13 Time 13:34 Rev Time 0.00
Received By rregueir Date 2010-08-30 Time 15:35 Sent To  
Notes
2010-08-30 15:35:49REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLAN REVIEW COMMENTS:
  
 1. PG M-6 PLAN NOTE #1 CALLS FOR DRYER BOOSTER FAN.
 PROVIDE DRYER MANUFACTURER'S INSTALLATION INSTRUCTIONS
 SHOWING THE USE OF A BOOSTER FAN IS APPROVED BY THE
 DRYER MANUFACTURER. CLOTHES DRYERS SHALL BE EXHAUSTED
 IN ACCORDANCE WITH THE DRYER MANUFACTURER'S
 INSTRUCTIONS PER FBC-M 504.1.
  
 2. PG M-6 AND M-7 PLAN NOTES 2 AND/OR 3 CALL FOR
 OUTSIDE AIR INTAKE LOUVERS. PROVIDE FULL PRODUCT
 APPROVAL DOCUMENTATION WITH INSTALLATION INSTRUCTIONS
 FOR LOUVERS IN ACCORDANCE WITH FBC-B 106.3.3 AND FBC-M
 304.1.
  
 3. PG M-6 BUILDINGS 1 AND 2: EXHAUST AIR FROM SOME FANS
 AND CLOTHES DRYERS ARE SHOWN DISCHARGING DIRECTLY OVER
 SIDEWALKS (SEE DRAWING MARK-UPS). EXHAUST AIR SHALL NOT
 BE DIRECTED ONTO WALKWAYS PER FBC-M 401.4.2.
  
 4. PG M-7 PLAN NOTE #8 ON FIRST FLOOR AND PLAN NOTE #6
 ON SECOND FLOOR CALL FOR DRYER BOOSTER FAN. PROVIDE
 DRYER MANUFACTURER'S INSTALLATION INSTRUCTIONS SHOWING
 THE USE OF A BOOSTER FAN IS APPROVED BY THE DRYER
 MANUFACTURER. CLOTHES DRYERS SHALL BE EXHAUSTED IN
 ACCORDANCE WITH THE DRYER MANUFACTURER'S INSTRUCTIONS
 PER FBC-M 504.1.
  
 5. PG M-13: DETAIL #8 CALLS FOR RUSKIN IBD2 FIRE DAMPER
 AT RATED SUB-CEILING. BASED ON MANUFACTURER'S
 INSTRUCTIONS, THIS DAMPER IS NOT COMPATIBLE WITH THE
 SINGLE-MEMBRANE CEILING ASSEMBLY SHOWN ON PLANS. FIRE
 DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 LISTING AND MANUFACTURER'S INSTRUCTIONS PER FBC-M
 607.2.
  
 6. PG M-13 DETAIL #8 NOTE: FLEXIBLE DUCT CONNECTIONS
 ARE REQUIRED TO BE SEALED AND MECHANICALLY FASTENED.
 THEY ARE NOT INTENDED FOR REMOVAL AND USE FOR FIRE
 DAMPER ACCESS. PROVIDE RIGID DUCT WITH DUCT ACCESS
 DOOR. A SERVICE OPENING SHALL BE PROVIDED IN AIR DUCTS
 ADJACENT TO EACH FIRE DAMPER PER NFPA 90A SECTION
 4.3.4.1.
  
 7. ON ALL FLOOR PLANS: ADDITIONAL RATED SEPARATIONS ARE
 LIKELY AROUND SLEEPING ROOMS AND POSSIBLY EGRESS
 CORRIDORS (SEE BUILDING REVIEW COMMENTS). VERIFY THAT
 ALL PENETRATIONS OF ADDITIONAL RATED ASSEMBLIES ARE
 PROTECTES IN ACCORDANCE WITH FBC-M 607.5.
  
 8. PG M-7: FLOOR PLAN SHOWS RETURN AIR GRILL IN LANDING
 KITCHEN 3-117. RETURN AIR INTAKE IS PROHIBITED IN
 NON-DEDICATED KITCHEN HVAC SYSTEMS PER FBC-M 407.1.
  
 9. PG M-7 FIRST FLOOR PLAN NOTE #5 CALLS FOR FLY FAN AT
 EXTERIOR DOOR FOR LANDING KITCHEN 3-117. THIS FAN IS
 NOT IDENTIFIED ON PLANS TO CORRELATE WITH FAN SCHEDULE.
 PROVIDE MISSING INFORMATION PER FBC-B 106.1.1.
  
 10. PG M-8 THRU M-11: PLAN NOTE #6 CALLS FOR CONDENSATE
 TO DISCHARGE INTO HUB DRAIN. CONDENSATE SHALL NOT
 DISCHARGE INTO SANITARY SEWER PER CITY ORDINANCE AND
 FBC-M 307.2.1.
  
 11. PG M-8 THRU M-11: PLAN NOTE #4 CALLS FOR SMOKE
 DETECTOR TO BE PROVIDED IN SUPPLY AND RETURN DUCTS.
 PLAN AND SECTION VIEWS SHOW SMOKE DETECTORS ONLY IN THE
 SUPPLY DUCT. PLEASE COORDINATE PLANS, SECTIONS AND
 NOTES TO SHOW THE LOCATION OF ALL DUCT SMOKE DETECTORS
 PER FBC-M 106.1.1.
  
 12. PG M-8 THRU M-11: DUCT ACCESS DOOR REQUIRED AT
 SMOKE DETECTORS PER FBC-M 301.15 AND NFPA 90A SECTION
 4.3.4.1.
  
 13. PG M-14 DETAIL #7: FIRE DAMPERS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATIONS AND
 LISTING PER FBC-M 607.2. PROVIDE MANUFACTURER'S
 INSTRUCTIONS IN THE FIELD AND REMOVE ANY CONFLICTIONG
 INFORMATION FROM PLANS.
  
 14. PG M-17 THRU M-19: SEQUENCE FOR FIRE/SMOKE CONTROL
 CALL FOF FAN TO BE SHUT DOWN BY DUCT SMOKE DETECTORS
 ONLY WHILE NOTE #4 ON PAGES M-8 THRU M-11 CALLS FOR
 FANS TO SHUT-DOWN UPON ACTIVATION OF ANY FIRE ALARM
 STATION. PLEASE COORDINATE AND CLARIFY PER FBC-B
 106.1.1.
  
 15. NO ENERGY CODE COMPLIANCE FORM OR COOLING LOAD
 CALCULATIONS PROVIDED FOR REVIEW. FBC-B CHAPTER 13.
  
 16. NO INFORMATION PROVIDED REGARDING KITCHEN EXHAUST
 AND VENTILATION SYSTEMS. PROVIDE SEPARATE PLANS AND
 PERMIT APPLICATION FOR THESE SYSTEMS.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING, INDICIATING
 HOW EACH COMMENT HAS BEEN ADDRESSED AND WHERE THE
 REQUIRED INFORMATION CAN BE FOUND. RESPONSE LETTER MAY
 BE UPLOADED TO THE "SUPPORTING DOCUMENTS" FOLDER UPON
 RESUBMISSION OF CORRECTED PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-11-08 Cont ID  
Sent By lwagner Date 2010-11-08 Time 11:31 Rev Time 0.00
Received By lwagner Date 2010-11-08 Time 10:27 Sent To  
Notes
2010-11-08 10:44:45FBC PLUMBING PLAN REVIEW #2
 APPROVED WITH EXCEPTION:
 REVISION REQUIRED
  
 SHEETS P-7 - P-10 AND FS-3 SHOW A KITCHEN WITH A POT
 SINK, MOP SINK, AREA FLOOR DRAINS, AND DISH WASHER
 WITHOUT A PRE-RINSE SINK.
 FBC PLUMBING 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR
 OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS,
 SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS,
 SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS.
 FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS,
 PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK
 STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE
 DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS
 WITHOUT PRERINSE SINKS.
  
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES AND
 EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE
 DISCHARGED.
  
 1003.3.4.1 GREASE INTERCEPTOR CAPACITY. GREASE
 INTERCEPTORS AND GREASE TRAPS SHALL HAVE THE GREASE
 RETENTION CAPACITY INDICATED IN TABLE 1003.3.4.1 FOR
 THE FLOW-THROUGH RATES INDICATED.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-10-01 Cont ID  
Sent By lwagner Date 2010-10-01 Time 13:16 Rev Time  
Received By lwagner Date 2010-09-17 Time   Sent To  
Notes
2010-09-17 09:33:48FBC PLUMBING PLAN REVIEW #1
 DENIED:
  
 SHEETS P-7 & P-10 SHOW A KITCHEN WITH A POT SINK, ETC
 FBC PLUMBING 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR
 OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS,
 SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS,
 SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS.
 FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS,
 PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK
 STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE
 DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS
 WITHOUT PRERINSE SINKS.
  
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES AND
 EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE
 DISCHARGED.
  
 1003.3.4.1 GREASE INTERCEPTOR CAPACITY. GREASE
 INTERCEPTORS AND GREASE TRAPS SHALL HAVE THE GREASE
 RETENTION CAPACITY INDICATED IN TABLE 1003.3.4.1 FOR
 THE FLOW-THROUGH RATES INDICATED.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-11-10 Cont ID  
Sent By lfranco Date 2010-11-10 Time 22:30 Rev Time 0.00
Received By lfranco Date 2010-11-10 Time 22:30 Sent To  
Notes
2010-11-10 22:32:04PLANNING AND ZONING: **** PASSED WITH
 PROVISO/NOTATIOIN: THE APPLICANT/OWNER WILL NEED TO
 APPLY TO THE PLANNING AND ZONING DEPARTMENT, FOR A
 SEPARATE REVIEW PROCESS FOR THE COMMUNITY GARDEN USE
 THAT MEETS THE EXTRA REQUIREMENTS ("PXR") PRIOR TO THE
 USE BEING ESTABLISHED. *******
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-10-14 Cont ID  
Sent By lfranco Date 2010-10-14 Time 13:32 Rev Time 0.00
Received By lfranco Date 2010-10-14 Time 13:32 Sent To  
Notes
2010-10-14 13:33:54PLANNING AND ZONING: **** PASSED WITH PROVISO - THE
 PROPOSED VEGETABLE GARDEN WILL NOT BE PART OF THIS
 APPROVAL. THE APPLICANT WILL NEED TO APPLY TO THE
 PLANNING AND ZONING DEPARTMENT, FOR A SEPARATE REVIEW
 PROCESS FOR THE COMMUNITY GARDEN USE THAT MEETS THE
 PERMITTED WITH EXTRA REQUIREMENTS ("PXR") PROVISIONS
 AND OBTAIN APPROVAL PRIOR TO THE USE BEING ESTABLISHED.
 NOTE: IF RESUBMITTING PLANS FOR REVIEW - ADD NOTATION
 ON THE PLANS REFERENCING THE ABOVE PROVISO. ****
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]