Plan Review Stops For Permit 10080587 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2010-11-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-11-05 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-11-05 |
Time |
10:44 |
Sent To |
PC |
|
Notes |
2010-11-05 11:13:22 | BUILDING REVIEW APPROVED WITH PROVISO. | | | | 1- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS FOR | | NEW GLASS BLOCK AND NEW WINDOWS. SEC. R301.2.1.2. | | ***NOTE: REVISION REQUIRED TO BE SUBMITTED FOR REVIEW | | AND APPROVAL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2010-10-26 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-10-26 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-10-26 |
Time |
11:48 |
Sent To |
PC |
|
Notes |
2010-10-26 12:00:17 | RESIDENTIAL (R3) REPAIRS/RENOVATION BUILDING REVIEW | | SECOND CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | DCA RULE 9B-72 FOR: | | | | A) GLASS BLOCK. (REPEAT COMMENT. NOT SUBMITTED). | | | | B) WINDOW MULLIONS. AND, CLEARLY MARK ON DRAWINGS | | SPECIFIC MULLION SIZE AND FASTENERS TO BE USED TO | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT. | | NOT SUBMITTED). | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | ( NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. | | | | ***NOTE: ENGINEER LETTER SUBMITTED DOESN'T IDENTIFY | | WHICH SPECIFIC PRODUCT APPROVALS WERE REVIEWED. AND IS | | MISSING THE REVIEW OF THE OTHER PRODUCT APPROVALS LIKE | | THE SINGLE HUNG WINDOWS AND EXTERIOR DOORS. ENGINEER TO | | CLEARLY LIST EACH PRODUCT APPROVAL NUMBER AND SPECIFIC | | MODEL OR USE STANDARD REVIEW STAMP ON EACH PRODUCT | | APPROVAL. | | | | 3- OWNER/AGENT TO SIGN AND DATE THE BOTTOM OF ENERGY | | CALCULATIONS FORM. | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | BY SEC. 713.13 FLORIDA STATUTE. | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | UP. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-09-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-09-28 |
Time |
16:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-09-28 |
Time |
16:03 |
Sent To |
|
|
Notes |
2010-09-28 17:00:37 | RESIDENTIAL (R3) REPAIRS/RENOVATION BUILDING REVIEW | | CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- A) BOTH SETS OF PLANS NEED TO BE SIGNED AND SEALED | | BY THE ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471 | | FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA | | ADMINISTRATIVE CODE.. ONLY ONE SET WAS SIGNED AND | | SEALED. | | | | B) ENGINEER TO HAVE HIS/HER ADDRESS ON THE TITLE BLOCK | | AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA | | ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. | | | | 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | DCA RULE 9B-72 FOR: | | | | A) GLASS BLOCK. | | | | B) WINDOW MULLIONS. AND, CLEARLY MARK ON DRAWINGS | | SPECIFIC MULLION SIZE AND FASTENERS TO BE USED TO | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | ( NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. | | | | 4- REVISE THE ENERGY CALCULATIONS: | | A) R-19 INSULATION DOESN'T FIT ON 2X4 WALLS. REVISE | | INSULATION ON ITEM #9(A) AS REQUIRED. | | | | B) CLARIFY CAPACITY OF HOT WATER TANK. WHY 5 GALLONS | | ONLY? | | | | C) REVISE BUILDER NAME. SEE PERMIT APPLICATION FOR NAME | | OF CONTRACTOR. | | | | 5- SHEET 2.1: R-19 INSULATION DOESN'T FIT ON 2X4 WALLS. | | REVISE ALL DETAILS THAT SPECIFY R-19 ON THE 2X4 WALL. | | | | 6- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | BY SEC. 713.13 FLORIDA STATUTE. | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | UP. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2010-09-30 |
|
|
Cont ID |
|
Sent By |
dwise |
Date |
2010-09-30 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
dwise |
Date |
2010-09-30 |
Time |
16:54 |
Sent To |
|
|
Notes |
2010-09-30 16:55:35 | OK PER JOHN DICKINSON CONTRACT PLAN REVEIWER LICENSE | | NUMBER PX3182 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2010-10-18 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-10-18 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-10-18 |
Time |
15:21 |
Sent To |
|
|
Notes |
2010-10-18 15:21:27 | IN ZONING BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-09-22 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-09-20 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-09-20 |
Time |
08:10 |
Sent To |
|
|
Notes |
2010-09-22 08:11:08 | LANDSCAPE PLAN SENT TO ZONING |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-09-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-10-08 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-23 |
Time |
08:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
2 |
Status |
N |
Date |
2010-10-20 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2010-10-20 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2010-10-20 |
Time |
09:56 |
Sent To |
|
|
Notes |
2010-10-20 16:28:26 | ***LANDSCAPE REVIEW NOT REQUIRED*** | | | | PLEASE REFER TO PERMIT # 10100331 FOR LANDSCAPE PERMIT | | AND PLANS. |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
F |
Date |
2010-09-27 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2010-09-27 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2010-09-27 |
Time |
16:49 |
Sent To |
|
|
Notes |
2010-09-27 17:20:17 | ***LANDSCAPE REVIEW FAILED*** | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | 1. THE SOD, MOST TREES AND THE PLANT MATERIAL IS IN | | POOR CONDITION OR DEAD. THE ENTIRE LOT SHALL BE SODDED. | | | | 2. THE ONLY TREES THAT SHALL REMAIN ARE THE LIVE OAK IN | | FRONT, THE CABAGE PALM IN THE REAR AND THE MANGO IN THE | | REAR. TWO ADDTIONAL CABAGE PALMS WOULD NEED TO BE | | PLANTED ADJACENT TO THE EXISTING PALM FOR IT TO BE | | COUNTED. THE BANANA TREE CANNOT BE COUNTED AS A TREE. | | THE CHINA BERRY ON THE EAST SIDE IS PARTIALLY ON THIS | | SITE AND PARTIALLY ON THE NEIGHBORING PROPERTY, SO IT | | CANNOT BE COUNTED.THE OTHER TREES NEED TO BE REMOVED. | | | | 3. PURSUANT TO SECTION 94-448 (D) (2), ALL OF THE ITEMS | | ENUMERATED IN THIS SECTION SHALL BE PART OF THE | | LANDSCAPE PLAN, INCLUDING A PLANT LIST WITH THE NAMES | | OF ALL EXISTING AND PROPOSED PLANT MATEIAL, THE | | QUANTITY, SIZE AND SPACING. | | | | 4. A SEPARATE LANDSCAPE PERMIT IS REQUIRED. PLEASE | | SUBMIT TWO COPIES OF A LANDSCAPE PLAN AND A COST | | ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE | | MATERIALS AND LABOR, BROKEN DOWN INTO UNIT COST. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ROBERT KUSSNER | | @ (561) 822-1462. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2010-09-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-09-28 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-09-28 |
Time |
17:00 |
Sent To |
|
|
Notes |
2010-09-28 17:02:42 | AS PER CONVERSATION WITH CONTRACTOR (JAMES FLUKE) THERE | | IS NOT A/C ON BOARD YET. A/C CONTRACTOR WILL SUBMIT | | DRAWINGS AND CALCULATIONS UNDER A SEPARATE PERMIT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2010-10-26 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-10-26 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-10-26 |
Time |
11:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2010-09-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-09-28 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-09-28 |
Time |
17:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2010-10-21 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2010-10-21 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2010-09-24 |
Time |
14:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-08-26 |
|
|
Cont ID |
|
Sent By |
kdfreema |
Date |
2010-08-26 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
kdfreema |
Date |
2010-08-26 |
Time |
08:51 |
Sent To |
|
|
Notes |
2010-08-26 09:09:34 | ***FAILED*** | | | | SECTION 94-441(C)(2) OF THE CITY'S ZONING AND LAND | | DEVELOPMENT REGULATIONS REQUIRES THAT THIS PROPERTY BE | | BROUGHT INTO COMPLIANCE WITH THE CITY'S LANDSCAPE | | REGULATIONS AS THE VALUE OF THE PERMIT EXCEEDS 50 | | PERCENT OF THE VALUE OF THE STRUCTURE'S VALUE ON FILE | | WITH THE PBC PROPERTY APPRAISER. | | | | THE REGULATIONS FOR SINGLE FAMILY RESIDENCES ARE AS | | FOLLOWS: | | | | 1 SHADE, FLOWERING, OR FRUIT TREE PER 1,200 SQUARE FEET | | OF OPEN SPACE (AS MEASURED BY TAKING THE LOT AREA AND | | SUBTRACTING THE BUILDING FOOTPRING) OR PORTION THEREOF. | | ASSUMING THE LOT IS 50'X115' (5,750 SQUARE FEET) AND | | THE LISTED FOOTPRINT OF THE STRUCTURE IS 1,456 SQUARE | | FEET THE OPEN SPACE ON THIS LOT IS 4,294 SQUARE FEET. | | THIS YIELDS A REQUIREMENT OF 4 SHADE TREES. | | | | 1 SHRUB PER 500 SQUARE FEET OF OPEN SPACE OR PORTION | | THEREOF. IN THIS CASE, 9 SHRUBS WOULD BE REQUIRED | | | | NOTE THAT LANDSCAPE PLANS FOR SINGLE FAMILY RESIDENCES | | DO NOT NEED TO BE SIGNED AND SEALED BY A REGISTERED | | LANDSCAPE ARCHITECT AND THAT EXISTING MATERIAL ON-SITE | | WHICH IS IN GOOD CONDITION MAY BE COUNTED TOWARD | | MEETING THE REQUIREMENT . | | | | PLEASE CONTACT ROBERT KUSSNER, LANDSCAPE PLANNER, AT | | 561-822-1462 WITH QUESTIONS. |
|
|