Plan Review Details - Permit 10080576
Plan Review Stops For Permit 10080576
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-09-14 Cont ID  
Sent By jwitmer Date 2010-09-14 Time 08:10 Rev Time 1.20
Received By jwitmer Date 2010-09-14 Time 07:00 Sent To  
Notes
2010-09-14 08:11:17BUILDING PLAN REVIEW
 PERMIT: 10080576
 ADD: 2031 PALM BEACH LAKES 2031
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: (561)662-1819
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) PLANS SHEET A-1 TOILET ROOMS INDICATE USE OF TILE ON
 RESTROOM WALLS BUT DO NOT MENTION THE TYPE OF TILE
 BACKING, BE AWARE:
 GYPSUM BOARDS IN SHOWERS & WATER CLOSETS
  
 2509.1 WET AREAS. SHOWERS AND PUBLIC TOILET WALLS SHALL
 CONFORM TO SECTION 1210.2 AND 1210.3.
  
 2509.2 BASE FOR TILE. CEMENT, FIBER-CEMENT OR GLASS MAT
 GYPSUM BACKERS IN COMPLIANCE WITH
  
 ASTM C 1178-08 STANDARD SPECIFICATION
 FOR COATED GLASS MAT WATER-RESISTANT GYPSUM
  
 ASTM C 1288-99 STANDARD SPECIFICATION
 FOR DISCRETE NON- ASBESTOS FIBER-CEMENT INTERIOR
 SUBSTRATE SHEETS
  
 ASTM C 1325-08 STANDARD SPECIFICATION
 FOR NON-ASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS
  
 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 2A) NEW EXTERIOR GLAZED DOOR
 2B) NEW STOREFRONT WINDOWS
 2C) NEW GLASS BLOCK WINDOWS
  
 2D) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-09-02 Cont ID  
Sent By jleahy Date 2010-09-02 Time 10:50 Rev Time 0.00
Received By jleahy Date 2010-09-02 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-10-19 Cont ID  
Sent By mcarsill Date 2010-10-19 Time 12:01 Rev Time 0.00
Received By mcarsill Date 2010-10-19 Time 11:57 Sent To  
Notes
2010-10-19 12:00:562031 PALM BEACH LAKES BOULEVARD
 PERMIT NUMBER 10080576
  
  
 ON OCTOBER 18, 2010, THIS WRITER RECEIVED AN ELECTRONIC
 MAIL REGARDING THE ABOVE REFERENCED PROJECT. A PLAN
 REVIEW RESPONSE COMMENT LETTER WAS RECEIVED ADDRESSING
 THE FIRE COMMENTS.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-08-24 Cont ID  
Sent By mcarsill Date 2010-08-24 Time 13:43 Rev Time 0.00
Received By mcarsill Date 2010-08-24 Time 13:19 Sent To  
Notes
2010-08-24 13:43:042031 PALM BEACH LAKES BOULEVARD
 PERMIT NUMBER 10080576
 "COMMERCIAL INTERIOR ALTERATION"
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. PROPER VENTILATION IS TO BE PROVIDED WHEN GASOLINE
 POWERED EQUIPMENT IS USED INDOORS. CARBON MONOXIDE (CO)
 IS A COLORLESS, ODORLESS, AND TASTELESS GAS THAT IS
 FLAMMABLE IN THE PROPER CONCENTRATION. PROPER
 VENTILATION CONTROLS ARE TO BE PROVIDED TO PREVENT THE
 BUILD-UP OF CARBON MONOXIDE VAPORS.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. NEW ONE HOUR FIRE WALL IS TO BE PROPERLY IDENTIFIED
 AND ALL OPENINGS BE PROTECTED.
  
 5. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED ON THE
 PROPER ELEVATION. NUMBERS ARE TO CONTRAST WITH THE
 BACKGROUND THEY ARE AFFIXED TO.
  
 6. INTERIOR WALL AND CEILING FINISHES IN EXITS AND EXIT
 ACCESS CORRIDORS SHALL BE CLASS A OR B, NOT CLASS C.
  
 7. WRONG EDITIONS OF FIRE CODES NOTED IN TITLE BLOCKS.
 SHOULD READ 2006 EDITIONS NOT 2003 EDITIONS.
  
 8. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-01 Cont ID  
Sent By lmartine Date 2010-10-01 Time 16:34 Rev Time 0.00
Received By lmartine Date 2010-10-01 Time 16:34 Sent To  
Notes
2010-10-01 16:41:27C--25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-27 Cont ID  
Sent By shill Date 2010-09-27 Time 10:05 Rev Time 0.00
Received By shill Date 2010-08-24 Time 11:26 Sent To  
Notes
2010-08-24 11:34:52C18

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2010-08-25 Cont ID  
Sent By rkussner Date 2010-08-25 Time 17:37 Rev Time 0.00
Received By rkussner Date 2010-08-25 Time 17:37 Sent To  
Notes
2010-08-25 17:44:00***LANDSCAPE REVIEW PASSED WITH PROVISO***
  
 ALL LANDSCAPING SHOWN ON THE SUBMITTED LANDSCAPE PLAN
 SHALL BE IN PLACE AND IN GOOD CONDITION. ANY TREES,
 SHRUBS OR SOD THAT IS DEAD, MISSING OR NOT FLORIDA #1
 GRADE OR BETTER SHALL BE REPLACED. CORRECTIVE TREE
 PRUNING BY A CERTIFIED ARBORIST MAY BE REQUIRED IF ANY
 OF THE EXISTING TREES SHOW ANY DEFECTS. A FINAL
 LANDSCAPE INSPECTION SHALL BE REQUIRED AND APPROVED
 PRIOR TO C/O.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-09-13 Cont ID  
Sent By rregueir Date 2010-09-13 Time 09:34 Rev Time 0.00
Received By rregueir Date 2010-09-10 Time 14:09 Sent To  
Notes
2010-09-10 14:10:04**PROVISO**
  
 1. FLEXIBL DUCT DETAIL: HANGER SPACING IS MAXIMUM 5
 FEET AND FIRST HANGER SHALL BE WITHIN 6 INCHES OF THE
 TAP PER FBC-M 603.5.6.6.
  
 2. SIGNED AND SEALED STRUCTURAL ENGINEERING DETAIL IS
 REQUIRED FOR ATTACHMENT OF RTUS TO BUILDING STRUCTURE
 PER FBC-M 301.12.
  
 3. MECHANICAL PERMIT MUST BE ISSUED TO ALTMAN BROTHERS
 AIR CONDITIONING ONLY SINCE THEY HAVE SUBMITTED THE
 DESIGN FOR THIS JOB. ONLY THE INSTALLING CONTRACTOR MAY
 DESIGN THE SYSTEM IN LIEU OF A MECHANICAL ENGINEER PER
 FBC-B 105.3.1.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-10-13 Cont ID  
Sent By lwagner Date 2010-10-13 Time 09:42 Rev Time 0.00
Received By lwagner Date 2010-10-13 Time 09:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-09-13 Cont ID  
Sent By lwagner Date 2010-09-13 Time 14:34 Rev Time 0.00
Received By lwagner Date 2010-09-13 Time 13:50 Sent To  
Notes
2010-09-13 14:26:02FBC 2007 PLUMBING PLAN REVIEW #1
 DENIED:
  
 1.RESTROOM #115 & EWC ARE MISSING FROM SANITARY RISER.
  
 2. FBC PLUMBING 406.3 AUTOMATIC CLOTHES WASHERS- WASTE
 CONNECTION: THE TRAP AND FIXTURE DRAIN SHALL BE A
 MINIMUM 2".
 THE FIXTURE DRAIN SHALL CONNECT TO A BRANCH OR STACK OF
 3".
  
 3. 1" COLD WATER PIPE WOULD BE REQUIRED UP TO THE 2ND
 RESTROOM BRANCH - 604.1 AND TABLE 603.1
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-08-30 Cont ID  
Sent By astelly Date 2010-08-30 Time 14:37 Rev Time 0.00
Received By astelly Date 2010-08-30 Time 14:37 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved