Plan Review Details - Permit 10080533
Plan Review Stops For Permit 10080533
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-09-01 Cont ID  
Sent By wjolin Date 2010-09-01 Time 13:38 Rev Time 0.00
Received By wjolin Date 2010-09-01 Time 13:22 Sent To M
Notes
2010-09-01 13:38:04*****APPROVED W/ COMMENTS*****
  
 1) NFPA 13D, SECTION 6.3(2) REQUIRES SMOKE DETECTORS TO
 BE PROVIDED WHEN THE SPRINKLER SYSTEM IS TIED INTO THE
 DOMESTIC WATER SUPPLY.
  
 2) THE "DESIGN CRITERIA" INFORMATION BOX SHOULD REFER
 TO A K-FACTOR OF 4.9 FOR THE PENDENT STYLE SPRINKLERS
 USED IN THE CALCULATION.
  
 3) THE "TYPES OF SPRINKLERS" INFORMATION BOX SHOULD
 SHOW THE ORIFICE SIZES AS 7/16-INCH (K=4.9) AND
 3/8-INCH (K=4.3).
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WBP FIRE PLAN REVIEW
 561-805-6730
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-01 Cont ID  
Sent By jgomez Date 2010-10-01 Time 14:28 Rev Time 0.00
Received By jgomez Date 2010-10-01 Time 14:28 Sent To  
Notes
2010-10-01 14:29:01SENT TO FIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-13 Cont ID  
Sent By hmoser Date 2010-09-13 Time 15:11 Rev Time 0.00
Received By hmoser Date 2010-08-19 Time 09:47 Sent To  
Notes
2010-08-19 09:47:33TO FIRE BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-09-13 Cont ID  
Sent By hmoser Date 2010-09-13 Time 15:11 Rev Time 0.00
Received By hmoser Date 2010-09-13 Time 15:11 Sent To  
Notes
***NONE***