Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-01-28 Cont ID  
Sent By jgomez Date 2011-01-28 Time 15:13 Rev Time 0.00
Received By jgomez Date 2011-01-28 Time 15:08 Sent To  
Notes
2011-01-28 15:36:13MASTER PLAN (MODEL A.1) FOR NEW SINGLE FAMILY RESIDENCE
 (R3), BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 SUPPLEMENTS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES. NOA 07-1120.14 SUBMITTED WAS
 SUPERSEDED ON THE MIAMI DADE WEBSITE. PROVIDE CURRENT
 NOA.
  
 B) SINGLE HUNG WINDOWS. NOA 07-0322.06 SUBMITTED
 EXPIRES ON MARCH 23, 2011. MASTER PLAN WILL HAVE TO BE
 REVISED FOR FUTURE SUBMITTAL AFTER THIS DATE.
  
 C) WINDOW MULLIONS. NOA 06-0125.06 SUBMITTED EXPIRES ON
 JUNE 28, 2011. MASTER PLAN WILL HAVE TO BE REVISED FOR
 FUTURE SUBMITTAL AFTER THIS DATE.
  
 D) ENTRY DOOR. TWO DIFFERENT NOA'S WERE SUBMITTED. NOA
 06-0501.02 WHICH REQUIRES SHUTTERS AND NOA 07-0629.10
 WHICH DOESN'T REQUIRE SHUTTERS. CLARIFY WHICH ONE IS
 GOING TO BE USED.
  
 E) REAR DOOR BY KITCHEN AREA AS SHOWN ON PLANS.
  
 F) STORAGE DOUBLE DOORS AS SHOWN ON PLANS.
  
 G) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 H) STORM SHUTTERS. COORDINATE WITH ITEM # 2D ABOVE. AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE. ALSO, MARK ON
 SHUTTERS DRAWING SPECIFIC MOUNTING CONDITION AND ANCHOR
 TYPE AND SPACING.
  
 I) TRUSS CONNECTORS. PROVIDE ONLY THE FRONT PAGE OF
 PRODUCT APPROVAL AND PAGE SHOWING THE CONNECTOR.
  
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 4- DESIGN CRITERIA: BUILDING EXPOSURE WAS REVISED TO
 EXPOSURE "C" BUT THE DESIGN PRESSURES ON SHEETS A-3.0,
 A-4.0, A-5.0 AND A-7.0 WERE NOT CHANGED TO REFLECT
 EXPOSURE "C".
  
 5- TRUSS PACKAGE:
 A) REVISE BUILDING EXPOSURE. NEED TO DESIGN TRUSSES TO
 EXPOSURE "C". REVISE TRUSS LAYOUT PAGE AND INDIVIDUAL
 TRUSSES ACCORDINGLY.
  
 B) TRUSS COVER SHEET TO PROVIDE ALL THE INFORMATION,
 INCLUDING THE ARCHITECT OF RECORD INFORMATION.
  
 C) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT
 COPY) AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 6- SHEET A-2.0:
 A) WALL SECTION A: SPECIFY CORRECT SECTION FOR THE
 ATTIC VENTILATION. SEE 2007 FLORIDA RESIDENTIAL CODE.
  
 B) WALL SECTION A: REVISE NOTE REGARDING TRUSS ANCHORS.
 USING SIMPSON NOT USP, AND REFER TO CORRECT SHEET.
  
 C) DETAIL 1, DETAIL 5 AND WALL SECTION A SPECIFY 10 MIL
 VAPOR BARRIER, WHILE FOUNDATION PLAN SPECIFIES 6 MIL
 VAPOR BARRIER. REVISE AS REQUIRED TO MATCH.
  
 7- REVISE HANDRAIL DETAIL #2 ON SHEET A-5.0. GUARDS
 CAN'T BE LOWER THAN 36" IN HEIGHT. SEE SEC. R312.1.
  
 8- SHEET A-6.0:
 A) COORDINATE DETAIL 4/A-6.0 WITH CONNECTORS SPECIFIED
 ON STRUCTURAL CONNECTORS SCHEDULE. REVISE AS REQUIRED
 TO MATCH.
  
 B) CONNECTOR SPECIFIED ON DETAIL 5/A-6.0 CAN'T BE USED
 BECAUSE IT DOESN'T PROVIDE ANY UPLIFT LOADS. SEE
 CATALOG AND REVISE AS REQUIRED.
  
 C) DETAILS 2/A-6.0, 3/A-6.0 AND 4/A-6.0 SHOWN ON THE
 GABLE END SIDE OF THE ROOF FRAMING PLAN DON'T
 CORRESPOND TO THIS MODEL. REVISE AS REQUIRED.
  
 D) PROVIDE DETAIL 4/A-6.0 THAT REFLECTS ACTUAL
 CONNECTION AS SHOWN ON THE ROOF FRAMING PLAN. GABLE END
 TRUSS AND TRUSS GIRDERS FTG2 AND FTG3 ARE RESTING ON AN
 8"X8" CONCRETE COLUMN BELOW. DETAIL 4/A-6.0 SHOWN
 DOESN'T REFLECT THIS CONDITION. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 COMBINATION COMMERCIAL PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-01 Cont ID  
Sent By jgomez Date 2010-09-23 Time 15:51 Rev Time 0.00
Received By jgomez Date 2010-09-23 Time 15:51 Sent To  
Notes
2010-12-01 15:51:59RESIDENTIAL (R3) MASTER PERMIT, BUILDING REVIEW
 CHECKLIST
 2007 FBC WITH 2009 REVISIONS.
  
  
 1- PACKAGE SUBMITTED NEED TO BE PROPERLY COORDINATED.
 MASTER PERMIT #09120243 IS ONLY FOR MODEL "B" AND THE
 ADDRESS IS 1107 22 ST. PACKAGE SUBMITTED SHOWS MODELS
 A, A1, A2 AND B. ALL THE PERMIT APPLICATIONS SUBMITTED
 SHOW THE SAME MASTER NUMBER (09120243) AND THE SAME
 ADDRESS (1107 22 ST). PLEASE COORDINATE EACH MASTER
 PERMIT NUMBER WITH EACH MASTER MODEL AND EACH ADDRESS
 AS REQUIRED.
  
 2- LUIS MARTINEZ TALKED TO DON WOODS SO CONTRACTOR
 COORDINATES PERMIT APPLICATIONS AND PLANS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-02-01 Cont ID  
Sent By rlecky Date 2011-02-01 Time 11:56 Rev Time 0.00
Received By rlecky Date 2011-02-01 Time 10:48 Sent To  
Notes
2011-02-01 11:57:53PROVIDE THE INTERRUPTING (AIC) CURRENT RATING FOR THE
 SERVICE. NEC 110.9
 CORRECT NOTES TO REFLECT THE CURRENT ELECTRIC CODE:
 2008 NEC
 PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94
 RECEPTACLE REQUIRED IN HALLWAY. NEC 210.52 (H)
 A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR
 ELEVATION. NEC 210.8, 210.52 (E) (1)
 NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT
 RECEPTACLES. NEC 406.11
 AT LEAST ONE SWITCH CONTROLLED LIGHTING OUTLET SHALL BE
 PROVIDED ON THE EXTERIOR SIDE OF THE REAR ENTRANCE. NEC
 210.70 (A) (2) (B).
 BEDROOM RECEPTACLES MUST BE PROTECTED WITH COMBINATION
 - TYPE AFCI'S. NEC 210.12 (B)
  
 ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-18 Cont ID  
Sent By shill Date 2011-11-18 Time 14:30 Rev Time 0.00
Received By shill Date 2011-11-18 Time 14:30 Sent To  
Notes
2011-11-18 14:32:3211/17/11 CLOSED "I" STOP FOR REPORTING PURPOSES
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-02 Cont ID  
Sent By rlecky Date 2011-02-02 Time 07:55 Rev Time 0.00
Received By rlecky Date 2011-01-28 Time 15:09 Sent To  
Notes
2011-01-28 15:09:38SENT TO R19.

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2011-01-18 Cont ID  
Sent By rkussner Date 2011-01-18 Time 15:27 Rev Time 0.00
Received By rkussner Date 2011-01-18 Time 15:27 Sent To  
Notes
2011-01-18 15:27:49***LANDSCAPE REVIEW NOT REQUIRED***
  
 WHEN SITE SPECIFIC PLANS ARE SUBMITTED FOR PERMIT
 REVIEW, SEPARATE LANDSCAPE PERMITS WILL BE REQUIRED. AT
 THAT TIME, PLEASE SUBMIT A LANDSCAPE APPLICATION, TWO
 SETS OF LANDSCAPE PLANS AND A CERTIFED COST ESTIMATE
 THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS
 AND LABOR BROKEN DOWN INTO UNIT COST.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-01-28 Cont ID  
Sent By jgomez Date 2011-01-28 Time 15:38 Rev Time 0.00
Received By jgomez Date 2011-01-28 Time 15:38 Sent To  
Notes
2011-01-28 15:46:19MASTER FOR NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL
 REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE COOLING AND HEATING LOAD CALCULATIONS AS
 REQUIRED BY SEC. N1107.AB OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 3- SPECIFY SUPPLY AND RETURN CFM'S ON EACH ROOM ROOM.
 COORDINATE WITH THE HEATING AND COOLING CALCULATIONS
 REQUIRED BY SEC. N1100.AB.
  
 4- SHEET A-8.0:
 A) REVISE MECHANICAL NOTE #3:. REVISE MINIMUM SEER AND
 COORDINATE EQUIPMENT MODEL WITH LOAD CALCULATIONS
 REQUIRED ON ITEM #2 ABOVE.
  
 B) REVISE OUTSIDE AIR CALCULATIONS NOTE: SEE 2007
 FLORIDA RESIDENTIAL CODE. CITE CORRESPONDING SECTION
 AND MAKE SURE CONDITIONED FLOOR AREA MATCHES FLOOR AREA
 SPECIFIED ON THE ARCHITECTURAL PLANS. CLARIFY WHY
 CITING THIS CODE SECTION. USING NATURAL OR MECHANICAL
 VENTILATION?
  
 5- REVISE DUCTWORK LAYOUT. FLOOR PLAN IS MISSING SOME
 DUCTWORK CONNECTIONS. SEE SUPPLY DUCTWORK ON BEDROOM
 #2. THERE ARE 2 RETURN AIR GRILLS ON BEDROOM #3.
 MISSING DUCTWORK ON BEDROOM #1 BATHROOM. REVISE AS
 REQUIRED TO PROVIDE COMPLETE A/C LAYOUT.
  
 6- MISSING RETURN AIR GRILL ON BEDROOM #1.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-01-28 Cont ID  
Sent By jgomez Date 2011-01-28 Time 15:53 Rev Time 0.00
Received By jgomez Date 2011-01-28 Time 15:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-01-14 Cont ID  
Sent By lfranco Date 2011-01-14 Time 17:43 Rev Time 0.00
Received By lfranco Date 2011-01-14 Time 17:43 Sent To  
Notes
2011-01-19 16:44:17PLANNING AND ZONING: **** ZONING REVIEW NOT REQUIRED
 FOR MASTER BUILDING PERMIT FOR SINGLE FAMILY HOME. DUE
 TO NO SPECIFIC SITE LOCATION, THE PLANNING AND ZONING
 DEPARTMENT CANNOT REVIEW FOR SETBACKS, HEIGHT,
 DRIVEWAY, LANDSCAPING OR ANY ZONING AND LAND
 DEVELOPMENT REGULATIONS ("ZLDR") THAT MAY PERTAIN TO A
 SPECIFIC LOCATION. WHEN A SITE IS ASSOCIATED TO THIS
 MASTER BUILDING PERMIT, THEN A ZONING REVIEW WILL BE
 REQUIRED. *****
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  