2010-08-25 10:06:46 | RESIDENTIAL (R3) MECHANICAL PLAN REVIEW. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- PROVIDE HEALING AND COOLING DESIGN LOAD CALCULATIONS |
| AS REQUIRED BY SEC. N1107.AB.1 ( PROVIDE TWO COPIES). |
| ***NOTE: COORDINATE WITH ENERGY CALCULATIONS SUBMITTED. |
| |
| 2- PROVIDE 2 COPIES OF MECHANICAL PLANS. ONLY ONE WAS |
| SUBMITTED. |
| |
| 3- PLANS SUBMITTED SPECIFY FIRST FLOOR FOR BOTH FLOORS. |
| REVISE AS REQUIRED TO IDENTIFY WHICH ONE IS THE FIRST |
| FLOOR AND WHICH ONE IS THE SECOND FLOOR. |
| |
| 4- FIRST FLOOR MECHANICAL PLAN IS MISSING INFORMATION. |
| SEC. 106.1.1 CITY AMENDMENTS TO FBC: |
| A) RETURN AIR TO THE CONDENSER UNIT IS SHOWN ON THE |
| WALL. FLOOR PLAN SHOWS A POCKET DOOR ON THIS WALL. |
| CLARIFY HOW IS THE RETURN AIR GOING TO BE INSTALLED. |
| |
| B) SPECIFY SIZE OF RETURN AIR. |
| |
| C AIR RETURN IS NOT ALLOWED FROM THE LAUNDRY AREA. DOOR |
| LEADING TO LAUNDRY AREA WILL NEED THRESHOLD GASKET. |
| |
| D) PROVIDE RETURN AIR FROM THE FAMILY ROOM. SPECIFY |
| SIZE AND LOCATION. |
| |
| E) SHOW CLOTHES DRYER EXHAUST LOCATION AND SIZE. |
| |
| 5) SECOND FLOOR MECHANICAL PLAN IS MISSING INFORMATION. |
| SEC. 106.1.1 CITY AMENDMENTS TO FBC: |
| A) 3"X7" DUCT IN WALL IS NOT SHOWN ON FIRST FLOOR PLAN. |
| |
| B) CLARIFY IF USING METAL DUCTWORK FOR 3"X7" DUCT IN |
| WALL?. AND SPECIFY PROVISIONS TO PREVENT THE FORMATION |
| OF CONDENSATION AS REQUIRED BY SEC. M1601.3.9 |
| |
| C) CLARIFY HOW INSTALLING 8X8 GRILL ON 3"X7" DUCT?. |
| SEC.1601.3. |
| |
| D) SPECIFY RETURN AIR SIZE ON MASTER BEDROOM. |
| |
| E) RETURN AIR DUCT FROM MASTER BEDROOM IS NOT SHOWN ON |
| FIST FLOOR. |
| |
| F) NO DUCTWORK SIZE AND LOCATION IS SHOWN FOR THE TWO |
| BATHROOMS. (60CFM AND 80CFM). |
| |
| G) 4X10 DUCTWORK SHOWN ON WALL IS NOT SHOWN ON FIRST |
| FLOOR. |
| |
| H) CLARIFY HOW INSTALLING 6X6 AND 10X6 GRILLS ON 4X10 |
| DUCTWORK. SEC. M1601.3. |
| |
| I) CLARIFY IF USING METAL DUCTWORK FOR 4X10 DUCTWORK IN |
| WALL?. AND SPECIFY PROVISIONS TO CONTROL CONDENSATION. |
| SEC. M1601.3.9 |
| |