Plan Review Details - Permit 10080498
Plan Review Stops For Permit 10080498
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-17 Cont ID  
Sent By lmartine Date 2010-09-13 Time 13:39 Rev Time 0.00
Received By lmartine Date 2010-09-13 Time 13:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-25 Cont ID  
Sent By jgomez Date 2010-08-25 Time 09:32 Rev Time 0.00
Received By jgomez Date 2010-08-18 Time 13:32 Sent To  
Notes
2010-08-18 13:31:03TO J. GOMEZ' DESK.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-09-17 Cont ID  
Sent By hmoser Date 2010-09-17 Time 10:17 Rev Time 0.00
Received By hmoser Date 2010-09-17 Time 10:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-08-25 Cont ID  
Sent By jgomez Date 2010-08-25 Time 09:33 Rev Time 0.00
Received By dwise Date 2010-09-13 Time 13:02 Sent To PC
Notes
2010-08-25 10:06:46RESIDENTIAL (R3) MECHANICAL PLAN REVIEW.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE HEALING AND COOLING DESIGN LOAD CALCULATIONS
 AS REQUIRED BY SEC. N1107.AB.1 ( PROVIDE TWO COPIES).
 ***NOTE: COORDINATE WITH ENERGY CALCULATIONS SUBMITTED.
  
 2- PROVIDE 2 COPIES OF MECHANICAL PLANS. ONLY ONE WAS
 SUBMITTED.
  
 3- PLANS SUBMITTED SPECIFY FIRST FLOOR FOR BOTH FLOORS.
 REVISE AS REQUIRED TO IDENTIFY WHICH ONE IS THE FIRST
 FLOOR AND WHICH ONE IS THE SECOND FLOOR.
  
 4- FIRST FLOOR MECHANICAL PLAN IS MISSING INFORMATION.
 SEC. 106.1.1 CITY AMENDMENTS TO FBC:
 A) RETURN AIR TO THE CONDENSER UNIT IS SHOWN ON THE
 WALL. FLOOR PLAN SHOWS A POCKET DOOR ON THIS WALL.
 CLARIFY HOW IS THE RETURN AIR GOING TO BE INSTALLED.
  
 B) SPECIFY SIZE OF RETURN AIR.
  
 C AIR RETURN IS NOT ALLOWED FROM THE LAUNDRY AREA. DOOR
 LEADING TO LAUNDRY AREA WILL NEED THRESHOLD GASKET.
  
 D) PROVIDE RETURN AIR FROM THE FAMILY ROOM. SPECIFY
 SIZE AND LOCATION.
  
 E) SHOW CLOTHES DRYER EXHAUST LOCATION AND SIZE.
  
 5) SECOND FLOOR MECHANICAL PLAN IS MISSING INFORMATION.
 SEC. 106.1.1 CITY AMENDMENTS TO FBC:
 A) 3"X7" DUCT IN WALL IS NOT SHOWN ON FIRST FLOOR PLAN.
  
 B) CLARIFY IF USING METAL DUCTWORK FOR 3"X7" DUCT IN
 WALL?. AND SPECIFY PROVISIONS TO PREVENT THE FORMATION
 OF CONDENSATION AS REQUIRED BY SEC. M1601.3.9
  
 C) CLARIFY HOW INSTALLING 8X8 GRILL ON 3"X7" DUCT?.
 SEC.1601.3.
  
 D) SPECIFY RETURN AIR SIZE ON MASTER BEDROOM.
  
 E) RETURN AIR DUCT FROM MASTER BEDROOM IS NOT SHOWN ON
 FIST FLOOR.
  
 F) NO DUCTWORK SIZE AND LOCATION IS SHOWN FOR THE TWO
 BATHROOMS. (60CFM AND 80CFM).
  
 G) 4X10 DUCTWORK SHOWN ON WALL IS NOT SHOWN ON FIRST
 FLOOR.
  
 H) CLARIFY HOW INSTALLING 6X6 AND 10X6 GRILLS ON 4X10
 DUCTWORK. SEC. M1601.3.
  
 I) CLARIFY IF USING METAL DUCTWORK FOR 4X10 DUCTWORK IN
 WALL?. AND SPECIFY PROVISIONS TO CONTROL CONDENSATION.
 SEC. M1601.3.9
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  