Plan Review Details - Permit 10080492
Plan Review Stops For Permit 10080492
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-25 Cont ID  
Sent By hmoser Date 2010-08-25 Time 15:23 Rev Time 0.00
Received By hmoser Date 2010-08-19 Time 17:29 Sent To  
Notes
2010-08-19 17:29:42TO MECHANICAL
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-09-08 Cont ID  
Sent By hmoser Date 2010-09-08 Time 09:57 Rev Time 0.00
Received By hmoser Date 2010-09-08 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-08-25 Cont ID  
Sent By hmoser Date 2010-08-25 Time 15:05 Rev Time 0.00
Received By hmoser Date 2010-08-25 Time 15:05 Sent To  
Notes
2010-08-25 15:16:17PLAN DENIED
 REFER TO SECTION 601.4 BALANCED RETURN AIR .
 PLEASE PROVIDE CFM WITH GRILL SIZE ON THE PLANS .
 PLEASE PROVIDE EQUIPMENT SCHEDULE ON THE PLANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732