Plan Review Details - Permit 10080482
Plan Review Stops For Permit 10080482
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-09-30 Cont ID  
Sent By mcarsill Date 2010-09-30 Time 14:12 Rev Time 0.00
Received By mcarsill Date 2010-09-30 Time 13:46 Sent To  
Notes
2010-09-30 13:49:02A PERMIT REVISION TRACKING NUMBER OF 10090584 WAS
 ESTABLISHED FOR THIS PERMIT APPLICATION.
  
 PERMIT APPLICATION 10080482 APPROVED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-02 Cont ID  
Sent By wjolin Date 2010-09-02 Time 12:20 Rev Time 0.00
Received By wjolin Date 2010-09-01 Time 14:01 Sent To  
Notes
2010-09-02 12:20:14*****REVIEW COMMENTS - FIRE*****
  
 1) PROVIDE VISUAL NOTIFICATION APPLIANCES FOR WORKROOMS
 #609 AND #614.
  
 2) PROVIDE NOTIFICATION APPLIANCE CIRCUIT WIRING,
 CANDELA RATINGS ETC.
  
 3) "SCOPE OF JOB" NOTE STATES THREE HORN STROBE UNITS
 ARE BEING ADDED. THESE DEVICES SHOULD BE
 SPEAKER-STROBES.
  
 4) DRAWING SCALE NOT FOUND.
  
 5) PROVIDE MANUAL PULL STATION AT EACH EXIT.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-02 Cont ID  
Sent By wjolin Date 2010-09-02 Time 12:20 Rev Time 0.00
Received By wjolin Date 2010-08-17 Time 14:51 Sent To  
Notes
2010-08-17 14:51:37IN FIRE BOX