Plan Review Stops For Permit 10080482 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2010-09-30 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2010-09-30 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2010-09-30 |
Time |
13:46 |
Sent To |
|
|
Notes |
2010-09-30 13:49:02 | A PERMIT REVISION TRACKING NUMBER OF 10090584 WAS | | ESTABLISHED FOR THIS PERMIT APPLICATION. | | | | PERMIT APPLICATION 10080482 APPROVED. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2010-09-02 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-09-02 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-09-01 |
Time |
14:01 |
Sent To |
|
|
Notes |
2010-09-02 12:20:14 | *****REVIEW COMMENTS - FIRE***** | | | | 1) PROVIDE VISUAL NOTIFICATION APPLIANCES FOR WORKROOMS | | #609 AND #614. | | | | 2) PROVIDE NOTIFICATION APPLIANCE CIRCUIT WIRING, | | CANDELA RATINGS ETC. | | | | 3) "SCOPE OF JOB" NOTE STATES THREE HORN STROBE UNITS | | ARE BEING ADDED. THESE DEVICES SHOULD BE | | SPEAKER-STROBES. | | | | 4) DRAWING SCALE NOT FOUND. | | | | 5) PROVIDE MANUAL PULL STATION AT EACH EXIT. | | | | MIKE CARSILLO, BATTALION CHIEF | | & WESLEY JOLIN | | WPB FIRE PLAN REVIEW | | 561-805-6730 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-09-02 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-09-02 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-08-17 |
Time |
14:51 |
Sent To |
|
|
Notes |
2010-08-17 14:51:37 | IN FIRE BOX |
|
|
|