Plan Review Details - Permit 10080396
Plan Review Stops For Permit 10080396
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2011-04-15 Cont ID  
Sent By jwitmer Date 2011-04-15 Time 08:40 Rev Time 0.00
Received By jwitmer Date 2011-04-15 Time 08:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-04-01 Cont ID  
Sent By jwitmer Date 2011-04-01 Time 08:47 Rev Time 3.00
Received By jwitmer Date 2011-04-01 Time 08:47 Sent To  
Notes
2011-04-01 09:14:55BUILDING PLAN REVIEW
 PERMIT: 10080396
 ADD: 2100 N FLORIDA MANGO
 CONT: TO BE DETERMINED
 CONTACT: PBA JOINT VENTURE INC
 TEL: (561)689-3745
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 APRIL 01/2011
 3RD REVIEW/ 2ND REVIEW OF 1 STORY BUILDING
  
 ACTION: DENIED
  
 1) COVERSHEET:
  
 1A-C) COMPLIED.
  
 2) SECOND REQUEST THE SURVEY THE FLOOD DATA IS
 BLANK!!!!!!
 , FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A-9" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 MINIMUM ELEVATION FOR FINISH FLOOR TO BE ELEVATION
 13'-6" NGVD.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3A) SECOND REQUEST!!!!! THIS AREA IS THE FRONT ENTRY,
 AND THE CANOPY MAY HAVE BEEN A ZONING REQUIREMENT BUT
 WILL ALSO BE USED AS A DROP OFF ZONE AS A PASSENGER
 LOADING ZONE. PLEASE REVIEW SP-1 THE PLANS INDICATE A
 PASSENGER LOADING ZONE VERSES A FLARED CURB 2007/ 2009
 FBC-B 11-4.6.6 SEE FIGURE 11-10.
 PLEASE SEE 11-6.3 ACCESS AISLE SHALL BE STRIPED
 DIAGONALLY TO DESIGNATE IT AS A NO-PARKING ZONE.CURB
 RAMPS MUST BE LOCATED OUTSIDE OF THE DISABLED PARKING
 SPACES AND ACCESS AISLES. PLEASE BE AWARE OF 11-4.29.5
 DETECTABLE WARNINGS AT HAZARDOUS VEHICLAR AREAS.
  
 3B) COMPLIED.
  
 4) SHEET A-4.0;
 4A) SECOND REQUEST!!! DETAILS 3 & 4 BOTH INDICATE THE
 USE OF GALVANIZED WIRE LATH OVER TYVAK WRAP, PLEASE
 REVIEW FBC-B 1404.2.1 NEW TO THE 2007 FBC A BOND BREAK
 WILL BE REQUIRED BETWEEN THE WIRE LATH AND TYVAK WRAP.
 PLEASE REVIEW THE THREE METHODS OF ACHIVING THIS, A
 PAPER BACK LATH AND TYVAK SYSTEM WILL ACHIEVE THIS
 REQUIREMENT.
  
 4B) SECOND REQUEST!!!! THE PLANS INDICATE THE USE OF
 USE OF HORIZONTAL RIB-LATH BEING ATTACHED TO METAL HIGH
 HAT, PLEASE PROVIDE TYPE OF FASTENER AND SPACING, FBC-B
 2510.3. ASTM C 926 AND ASTM C 1063.
  
 4C)COMPLIED.
  
 5-6) COMPLIED.
  
 7) PRODUCT APPROVALS:
 7A) SEMI-COMPLIED ENGLERT METAL ROOFING FL 11727.
 MISSING THE INSTALATION PORTION OF THE REPORT.
  
 7B) SEMI-COMPLIED JOHNMANVILLE NOA 06-0417.09 THE SAME
 REPORT IS FILED TWICE IN THE BACK UP DOCUMENT FOLDER.
 THE ONE REPORT THAT HAS IDENTIFIED WHICH SUB-SYSTEM IS
 TO BE INSTALLED ON PAGE 15. PLEASE PROVIDE WHICH OPTION
 FOUND ON PAGE 15 IS A NON-INSULATED ROOF WILL BE
 INSTALLED. THERE ARE THREE OPTIONS . OPTION# 1 HAS LOW
 PRESSURES AND LIMITATION #9. OPTIONS 2& 3 LIMITATION# 7
 WHICH ALLOWS FOR ENHANCED FASTENING, PLEASE CICCLE
 WHICH SYSTEM TO BE INSTALLED ANAD PROVIDE CALCULATIONS
 FOR ZONES 2 & 3.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-02-11 Cont ID  
Sent By jwitmer Date 2011-02-11 Time 01:45 Rev Time 6.00
Received By jwitmer Date 2011-02-11 Time 07:29 Sent To  
Notes
2011-02-11 14:38:05BUILDING PLAN REVIEW
 PERMIT: 10080396
 ADD: 2100 N FLORIDA MANGO
 CONT: TO BE DETERMINED
 CONTACT: PBA JOINT VENTURE INC
 TEL: (561)689-3745
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 FEB. 11/ 2011
 2ND REVIEW/ 1ST REVIEW OF 1 STORY BUILDING
  
 ACTION: DENIED
  
 1) COVERSHEET:
  
 1A) PLANS INDICATE THIS BUILDING TO BE FULLY FIRE
 SPRINKLERED BUT NO PLANS WERE SUBMITTED FOR THIS
 REVIEW. THE LIFE SAFETY REQUIREMENTS
 INDICATE THAT AREA INCREASES WERE TAKEN UNDER 2007
 FBC-B 506.3.
  
 1B) THE COVER SHEET LIFE SAFETY REQUIREMENTS UNDER THE
 HEADING OCCUPANCY INDICATE THIS TO BE A MIXED USE,
 NON-SEPARARTED OCCUPANCY. THE PLANS DO INDICATE A 1
 HOUR RATED CORRIDOR FOR THE ASSEMBLY OCCUPANCY, BUT
 FAIL TO TAKE INTO ACCOUNT :
 1B)(1) NO FIRE SPRINKLER PLANS SUBMITTED TO BE ABLE TO
 TAKE CREDIT FOR INCIDENTAL USE AREAS, (FBC-BTABLE 502).
 1B)(2) THE PLANS DO NOT ADDRESS THE REQUIREMENTS FOR
 STORAGE ROOM > 100 SQ FT TO RESIST THE PASSAGE OF
 SMOKE, THE DOORS ARE TO BE SELF CLOSING OR AUTOMATIC
 CLOSING UPON DETECTION OF SMOKE IN ACCORDANCE WITH
 SECTION 715.4.7.3.
  
 1C)THE COVER SHEET LIFE SAFETY REQUIREMENTS UNDER THE
 HEADING OCCUPANCY INDICATE THIS TO BE A MIXED USE,
 NON-SEPARARTED OCCUPANCY. THE PLANS DO INDICATE A 1
 HOUR RATED CORRIDOR FOR THE ASSEMBLY OCCUPANCY, BUT
 FAIL TO TAKE INTO ACCOUNT :
 1B)(1) NO FIRE SPRINKLER PLANS SUBMITTED TO BE ABLE TO
 TAKE CREDIT FOR INCIDENTAL USE AREAS, (FBC-BTABLE 502).
 1B)(2) THE PLANS DO NOT ADDRESS THE REQUIREMENTS FOR
 STORAGE ROOM > 100 SQ FT TO RESIST THE PASSAGE OF
 SMOKE, THE DOORS ARE TO BE SELF CLOSING OR AUTOMATIC
 CLOSING UPON DETECTION OF SMOKE IN ACCORDANCE WITH
 SECTION 715.4.7.3.
  
  
 2) SURVEY THE FLOOD DATA IS BLANK, FBC BUILDING
 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A-9" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. MINIMUM
 ELEVATION FOR FINISH FLOOR TO BE ELEVATION 13'-6" NGVD.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3A) PLEASE REVIEW SP-1 THE PLANS INDICATE A PASSENGER
 LOADING ZONE VERSES A FLARED CURB 2007/ 2009 FBC-B
 11-4.6.6 SEE FIGURE 11-10.
 PLEASE SEE 11-6.3 ACCESS AISLE SHALL BE STRIPED
 DIAGONALLY TO DESIGNATE IT AS A NO-PARKING ZONE.CURB
 RAMPS MUST BE LOCATED OUTSIDE OF THE DISABLED PARKING
 SPACES AND ACCESS AISLES. PLEASE BE AWARE OF 11-4.29.5
 DETECTABLE WARNINGS AT HAZARDOUS VEHICLAR AREAS.
  
 3B) SHEET SP-1 ALSO INDICATES 2 HANDICAPPED SPACES BUT
 THERE IS NO CUT DETAILS FROM THE ACCESS AISLE TO
 SIDEWALK AND CURB CUTS, SHEET SP-2 INDICATES TWO STYLES
 OF CURB CUTS, WHICH TYPE IS TO BE USED FOR THIS
 INSTALATION, PLEASE KEEP IN MIND CROSS SLOPE OF AN
 ACCESSIBLE ROUTE SHALL NOT EXCEED 1:50. 2007/ 2009
 FBC-B 11-4.3.7. PLEASE BE AWARE OF 11-4.29.5 DETECTABLE
 WARNINGS AT HAZARDOUS VEHICLAR AREAS.
  
 4) SHEET A-4.0;
 4A) DETAILS 3 & 4 BOTH INDICATE THE USE OF GALVANIZED
 WIRE LATH OVER TYVAK WRAP, PLEASE REVIEW FBC-B 1404.2.1
 NEW TO THE 2007 FBC A BOND BREAK WILL BE REQUIRED
 BETWEEN THE WIRE LATH AND TYVAK WRAP. PLEASE REVIEW THE
 THREE METHODS OF ACHIVING THIS, A PAPER BACK LATH AND
 TYVAK SYSTEM WILL ACHIEVE THIS REQUIREMENT.
  
 4B) THE PLANS INDICATE THE USE OF USE OF HORIZONTAL
 RIB-LATH BEING ATTACHED TO METAL HIGH HAT, PLEASE
 PROVIDE TYPE OF FASTENER AND SPACING, FBC-B 2510.3.
 ASTM C 926 AND ASTM C 1063.
  
 4C) R-19 UNFACED BATT INSULATION VERSES THE ENERGY
 CALCS CELOUSE R-20 INSULATION. PLEASE ALSO REVIEW A-8.2
 THE REQUIREMENTSPACING FOR HIHAT WHEN INSULATION BATT
 OR BLANKET IS LAIDED DIRECTLY ON TOP OF THE HI-HAT.
  
 5) SHEET A8-0 DETAIL# 3 A 1 HOUR RATED WALL DETAIL
 INDICATES THE ROOF DECK TO BE A METAL DECK, PLEASE
 CORRECT AND PROVIDE A DETAIL FOR SYSTEM UL DESIGN NO.
 HW-D-0011 .
  
 6) THE PLANS DO NOT PROVIDE THE MEAN ROOF HEIGHT IN
 EITHER S.01 WIND DESIGN CRITERIA NOR ON S0.2 THE DESIGN
 PRESSURE TABLES, HAS THE HEIGHT FACTOR BEEN TAKEN INTO
 ACCOUNT IN THE DESIGN PRESSURES?
  
 7) PRODUCT APPROVALS:
 7A) FL 11727 PLEASE PROVIDE WHICH SUB-SYSTEM WILL
 INSTALLED CIRCLE SYSTEM.
 7B) NOA 06-0417.09 PLEASE PROVIDE WHICH SUB-SYSTEM TO
 BE INSTALLED. NOTE ONLY PAGE 15 IS A NON-INSULATED ROOF
 THERE ARE THREE OPTIONS . OPTION# 1 HAS LOW PRESSURES
 AND LIMITATION #9. OPTIONS 2& 3 LIMITATION# 7 WHICH
 ALLOWS FOR ENHANCED FASTENING, PLEASE CICCLE WHICH
 SYSTEM TO BE INSTALLED ANAD PROVIDE CALCULATIONS FOR
 ZONES 2 & 3.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-26 Cont ID  
Sent By jwitmer Date 2010-08-26 Time 07:31 Rev Time 4.33
Received By jwitmer Date 2010-08-23 Time 09:53 Sent To  
Notes
2010-08-26 13:37:22BUILDING PLAN REVIEW
 PERMIT: 10080396
 ADD: 2100 N FLORIDA MANGO
 CONT: TO BE DETERMINED
 CONTACT: PBA JOINT VENTURE INC
 TEL: (561)689-3745
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 26/2010
 1ST REVIEW
 ACTION: DENIED
  
 1) NOTE PAARKING, LANDSCAPE, GENERATORS AND COVERED
 PARKING STRUCTURE REQUIRE SEPERATE PERMITS, REVIEWS,
 FEES AND APPLICATIONS.
  
 2) A/C CONDENSOR PADS AND GENERATOR PADS ARE LOCATED
 WITHIN A A-9 FLOOD ZONE REQUIRING A MINIMUM BASE FLOOD
 ELEVATION OF 13'-6", TO BE INCLUDED ON THE FINAL
 SURVEY.
 THE FIRST FLOOR ELEVATION TO BE AT A MINIMUM OF 13'-6"
 AND WILL REQUIRE SURVEYS WITH ELEVATION OF THE FIRST
 FLOOR LEVEL AT TIME OF FIRST FLOOR SLAB POUR AND AT
 FINAL BEFORE A C.C. OR C.O CAN BE ISSUED.
  
 3) SHEET LS1 THE SOUTH EXIT STAIR #102 IS WITHIN A 1
 HOUR ENCLOSURE THAT EXITS INTO A UNRATED LOBBY# 100 AND
 CONTAINING A ELEVATOR. AS DISCUSSED WITH B O DOUG WISE
 THIS CONDITION DOES MEET THE EXCEPTION 1020.1 EXCEPTION
 # 8. WE CONTACTED GS&P OFFICE MIKE ROSSIN ABOUT THE
 ISSUE OF THE LOBBY STILL REQUIRING A ONE HOUR FIRE
 RATING BECAUSE OF IT BEING THE EXIT CORRIDOR FOR THE
 LOUGE #112. THE LOUGE HAS AN ASSEMBLY OCCUPANT LOAD OF
 GREATER THAN 30 WHICH REQUIRES A 1 HR FIRE RATING PER
 TABLE 1017.1.
 WHEN WE SPOKE WITH MR. ROSSIN HE SUGESTED THEY WILL
 MAKE ONE OF THE TWO WINDOWS INTO THE 2ND EXIT FOR THIS
 SPACE ALLOWING THE LOBBY TO REMAIN UNRATED, PLANS WILL
 NEED TO BE UPDATED TO REFLECT THIS CHANGE. PLEASE BE
 AWARE OF A ONE FOOT ELEVATION CHANGE FROM THE NEW EXIT
 LANDING CREATED BY THIS DOORWAY AND SIDEWALK AND THE
 ELECTRICAL ROOM 136 LOCATED AT ELEVATION 14.91 NGVD.
 SHEET A1.1.
  
 4) PLEASE NOTE 11-4.1.3(8)(II) ACCESSIBLE ENTRANCES
 MUST BE PROVIDED IN A NUMBER AT LEAST EQUIVALENT TO THE
 NUMBER OF EXITS REQUIRED BY THE APPLICABLE BUILDING /
 FIRE CODES.
  
 5) ANOTHER AREA OF CONCERN IS THE FRONT ENTRY SHEET
 A1.1. PLEASE REVIEW THTE CROSS SLOPE, THE AREA JUST IN
 FRONT OF THE EGRESS DOORS INDICATES A ELEVATION OF
 15.91 NGVD AND A SECOND ELEVATION OF THE SIDEWALK
 12'-0" AWAY ADJACENT TO THE CURB A ELEVATION OF 15'-41"
 OR A GRADE CHANGE OF 6 INCHES IN 12'-0". 11-4.3.7 CROSS
 SLOPE ONLY ALLOWS A CROSS SLOPE 0F 1:50.
  
 6) SHEET A.20 PORTABLE STAGE DOE NOT INDICATE VERTICAL
 ACCESSIBLITY,11-4.1.6(1)(K)(III).
  
 7) SHEET A2.1 & A2.2 DORRWAYS LEADING TO EXTERIOR DECKS
 INDICATE A CUT SECTION 3/A6.1 WHEN YOU GO THERE IT
 REFERES YOU TO DETAIL 8/A3.0 A WALL SECTION , PLEASE
 PROVIDE A SECTION THROUGH AT TTHE DOOR FOR ACCESSIBILTY
 REQUIREMENTS. PLEASE ALSO INCLUDE WHICH OF THE PRODUCT
 APPROVALS THIS WILL BE. 11-4.13.8.
  
 8) SHEET A-3.0 THE ROOF PLAN AND DETAILS INDICATE TWO
 WALKABLE DECKS WITH ROOF DRAINS & NO OVER FLOWS THE
 DETAILS INDICATE THE ROOF DRAIN IS AT ELEVATION 17'-8"
 AS WELL AS THE PARAPET WALL WHICH WOULD ALLOW THE WATER
 TO OVERFLOW DOWN THE SIDE OF THE WALL. PLEASE SEE FBC-B
 1503.6. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL
 BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 9) SHEET A-6.1 NOTE UPPER RIGHT HAND CORNER OF PLAN
 INDICATES "LIGHT -WEIGHT CONCRETE ON METAL DECK W/
 AVERAGE R-30 VALUE. THE TERM AVERAGE CAN NOT BE USED.
 THERE ARE THREE INFORMAL INTERPRETATIONS THROUGH BOAF (
 BUILDING OFFICIALS ASSOCIATION OF FLORIDA THAT ARE
 RECOGNIZED THROUGH THE DEPARTMENT OF COMMUNITY AFFAIRS
 THAT IS EXPLICITE THE MINIMUM R-VALUE IS TO OCCUR AT
 THE ROOF DRAINS NOT A AVERAGE.
 SECTION 13-404.1ABCD.1 REPORT 3746
 SECTION 13-404 REPORT 3731
 SECTION 13-404.1.A REPORT 5438
  
 10) SHEET A-6.0 & A-6.1 BOTH HAVE WALL SECTIONS THAT
 INDICATE THE USE OF WIRE LATH OVER GRACE ICE/WATER
 MEMBRANE, THE CODE INDICATES A CHANGE IN 1404.2.1
 REQUIRING A SEPERATE BOND BREAK BETWEEN THE WATER
 RESISTIVE BARRIER AND THE CEMENT PLASTER (STUCCO).
 PLEASE REVIEW THE 3 OPTIONS.
  
 11) SHEET A-6.4 PLEASE PROVIDE COMPLIANCE WITH 11-4.4.2
 WHEN THERE IS LESS THAN 80 INCHES ( VERTICAL NOMINAL
 DIMENSION) HEAD ROOM, A BARRIER TO WARN BLIND OR
 VISUALLY - IMPAIRED PERSONS.
  
 12) THIS SAME SHEET A-6.4 INDICATES A HANDRAIL AT THE
 BOTTOM OF THE STAIR THE HANDRAIL THAT IS NOT ATTACHED
 TO THE WALL, THE HORIZONTAL EXTENSION WILL NEED TO WRAP
 BACK ONTO ITSELF AS PER 11-4.8.5(6) ENDS OF HANDRAILS
 SHALL BE EITHER ROUNDED OR RETURNED SMOOTHLY TO FLOOR,
 WALL, OR POST. ALSO SEE 11-4.4.1 PROTRUDING OBJECTS.
  
 13) IN NONE OF THE STAIR DETAILS IN A-6.2, A-6.3 &
 A-6.4 INDICATE ROOF DRAINS WITHIN THE STAIRWELL, THE
 PLUMBING PLANS INDICATE A 3" RAIN WATER PIPE. THE
 ARCHITECTURAL SHEETS INDICATE A LAY IN CEILING SYSTEM.
 FBC-B 1020.1.2 PENETRATIONS INTO THE STAIRWELL CAN ONLY
 WHAT IS REQUIRED FOR THE STAIRWELL. PLEASE PROVIDE
 DOCUMENTATION THAT THE LAY IN CEILING WILL HAVE A 1
 HOUR FIRE RATING, PROVIDE MANUFACTURERS SPEC ON THE
 CEILING TILE AND GRID SYSTEM FOR RATING.
  
 14) PRODUCT APPROVAL: YKK "#%" ALUMINUM OUTSWING
 ENTRANCE DOOR NOA 09-0518.09 PLEASE CIRCLE TYPE OF
 GLASS TO BE INSTALLED, NOTE DESIGN PRESSURES TO BE
 DIVIDED BY 1.33.
  
 15) PRODUCT APPROVAL SIPLAST NOA 09-0901.14 PLEASE
 PROVIDE WHICH SUB-SYSTEM IS TO BE INSTALLED ON THE
 ROOF, PLEASE ALSO BE AWARRE OF LIMITATIONS WITHIN EACH
 SUB-SYSTEM.
 LIMITATION #7 INDICATES ENHANCED FASTENING CAN OCCUR
 USING RAS 117 BY DESIGN PROFESSIONAL.
 LIMITATION #9 THE MAXIMUM DESIGN PRESSURES INDICATED
 ARE FOR ALL ROOF ZONES, NO ENHANCED FASTENING ALLOWED.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-03-28 Cont ID  
Sent By rlecky Date 2011-03-28 Time 13:08 Rev Time 0.00
Received By rlecky Date 2011-03-28 Time 13:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-03-04 Cont ID  
Sent By rlecky Date 2011-02-24 Time 14:53 Rev Time 0.00
Received By rlecky Date 2011-02-23 Time 15:50 Sent To  
Notes
2011-02-24 09:16:21SHEET 053 E1-2
 PLEASE PROVIDE A SPECIFICATION FOR THE LIGHT POLE
 DESIGN AND FOUNDATION.
  
 SHEET 055 E3-1
 GFCI PROTECTION IS REQUIRED FOR RECEPTACLES WITHIN 6
 FEET OF THE BAR SINK. NEC 210.8(B)(5)
  
 SHEET 056 E5-1
 MINIMUM SIZE SERVICE GROUNDING ELECTRODE CONDUCTOR HAS
 BEEN MISLABELED ON THE RISER DIAGRAM. NEC T. 250.66
 PANEL A AND B FEEDER OVERCURRENT PROTECTION SHOULD BE
 NO GREATER THAN THE PANELBOARD RATING. NEC 408.36
  
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-09-21 Cont ID  
Sent By jleahy Date 2010-09-21 Time 06:34 Rev Time 0.00
Received By jleahy Date 2010-09-21 Time 06:34 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2011-05-10 Cont ID  
Sent By mgonzale Date 2011-05-10 Time   Rev Time 0.50
Received By mgonzale Date 2011-05-10 Time   Sent To  
Notes
2011-05-10 16:06:17PLANS IN PROJECT DOX APPEAR TO BE AS PER LATEST
 SUBMITTAL TO ENGINEERING SERVICES DEPARTMENT
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2011-05-17 Cont ID  
Sent By mcarsill Date 2011-05-17 Time 10:33 Rev Time 0.00
Received By mcarsill Date 2011-05-17 Time 10:33 Sent To  
Notes
2011-05-17 10:34:07PLANS PREVIOUSLY APPROVED IN PROJECT DOX.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2011-04-04 Cont ID  
Sent By mcarsill Date 2011-04-04 Time 07:34 Rev Time 0.00
Received By mcarsill Date 2011-04-04 Time 07:31 Sent To  
Notes
2011-04-04 07:34:182100 NORTH FLORIDA MANGO ROAD
 PERMIT NUMBER 10080396
  
 1. THE SIGN WITH THE MALTESE CROSS WITH THE LETTER R
 NEEDS TO BE INSTALLED ON THE OUTSIDE OF THE BUILDING.
 (A-1.0)
  
 2. COULD NOT LOCATE ANY FIRE SPRINKLER DRAWINGS WITH
 THE PLANS.
  
 3. THE CANOPY WILL BE REQUIRED TO BE FIRE SPRINKLER
 PROTECTED IN COMBUSTIBLES ARE TO BE STORED OR HANDLED.
 SOME OF IT APPEARS TO BE COMBUSTIBLE.
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-02-16 Cont ID  
Sent By mcarsill Date 2011-02-16 Time 14:22 Rev Time 0.00
Received By mcarsill Date 2011-02-16 Time 14:14 Sent To  
Notes
2011-02-16 14:22:272100 NORTH FLORIDA MANGO ROAD
 PERMIT NUMBER 10080396
  
  
 1. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR LOCATIONS.
  
 2. A KNOX-BOX AND KNOX LOCKING CAPS WILL BE REQUIRED
 FOR THE PROJECT.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM INSTALLATION. THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM SHALL BE MONITORED BY A THIRD PARTY
 APPROVED FOR CENTRAL STATION SERVICE.
  
 4. FIRE ALARM STROBE MISSING FROM RESTROOM 44.
  
 5. NOTE # 17 IS INCORRECT ON SHEET FAO.1. DUCT SMOKE
 DETECTORS WHEN ACTIVATED SHALL CAUSE THE BUILDING FIRE
 ALARM TO ACTIVATE.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEM.
  
 7. ALL NEW FIRE AND SMOKE DAMPERS ARE TO BE DROP TESTED
 AFTER INSTALLATION TO ENSURE PROPER FUNCTION.
  
 8. THE KEYPAD/ACCESS CONTROL FOR DOOR DEVICES SHOWN ON
 SHEET A-1.O SHALL NOT INTERFERE WITH EXITING.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR GENERATOR.
  
 10. A MALTESE CROSS IDENTIFIED WITH THE LETTER R IS TO
 BE PROVIDED NEAR THE MAIN DOOR SIGNIFYING THAT A WOOD
 TRUSS IS PRESENT.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-15 Cont ID  
Sent By wjolin Date 2010-09-15 Time 10:27 Rev Time 0.00
Received By wjolin Date 2010-09-09 Time 10:08 Sent To M
Notes
2010-09-14 18:26:50*****REVIEW COMMENTS - FIRE*****
  
 WATER PLAN 6 OF 9: SHIFT FIRE HYDRANT, BACKFLOW
 PREVENTER, AND FDC 30-FEET TO THE SOUTH TO AVOID
 DAMAGED FIRE PROTECTION EQUIPMENT IN A WALL COLLAPSE
 EVENT SINCE 40-FEET OF CLEARANCE CANNOT BE MAINTAINED
 BETWEEN THE BUILDING AND EQUIPMENT. POSSIBLE SHIFT MAY
 AFFECT LANDSCAPE PLANS.
  
 WATER PLAN 7 OF 9: ADDRESS SHOULD READ "2100 NORTH
 FLORIDA MANGO ROAD."
  
 WATER DETAILS 8 OF 9: BACKFLOW PREVENTER SHALL BE UL
 LISTED FOR FIRE PROTECTION SYSTEMS. PROVIDE TAMPER
 SWITCHES ON GATES VALVES. CHAIN/LOCK GATE VALVES IN
 OPEN POSITION. PROVIDE CHECK VALVE AND LOCKABLE KNOX
 CAPS ON FIRE DEPARTMENT CONNECTION.
  
 SHEET D-1.0: DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 SHEET LS-1:
 - FLORIDA FIRE PREVENTION CODE SHOULD BE THE 2007
 EDITION.
 - DOOR SWINGS BLOCK MORE THAN 50% OF EXISTING CORRIDORS
 #116 AND #124 PER 7.2.1.4.4 OF NFPA 101.
 - NORTH STAIR INTERMEDIATE LANDING DECREASES IN WIDTH
 NEAR LOWER LANDING.
 - PROVIDE TACTILE SIGNAGE AT FIRST FLOOR EXITS.
  
 SHEET LS-2: IF BOTH DOORS OF ROOMS #219 AND #220 ARE
 OPEN AT THE SAME TIME, MORE THAN 50% OF THE GALLERY
 CORRIDOR IS OBSTRUCTED.
  
 SHEET A-2:
 - FESTIVAL SEATING IN ASSEMBLY OCCUPANCIES WITH
 OCCUPANT LOADS GREATER THAN 250 PERSONS REQUIRE AN
 APPROVED LIFE SAFETY EVALUATION PER 12.2.5.4 OF NFPA
 101.
 - MOVEABLE CHAIRS ARE REQUIRED TO BE SECURED TOGETHER
 IN GROUPS OF 3-7 PER 12.7.9.1.1 OR IF CHAIRS ARE NOT
 SECURED TOGETHER, AN AREA OF 15 SQ.FT. PER SEAT IS
 REQUIRED PER 12.7.9.2.2 OF NFPA 101.
 - ASSEMBLY OCCUPANCIES GREATER THAN 250 OCCUPANTS
 REQUIRE CROWD MANAGERS PER 12.7.6 AND FIRE DRILLS PER
 12.7.7 OF NFPA 101.
 - THE OCCUPANT LOAD OF THE ASSEMBLY SPACE SHALL BE
 POSTED NEAR THE MAIN ENTRANCE/EXIT OF THE ROOM PER
 12.7.9.3 OF NFPA 101.
  
 SHEET E1.01A: MAIN ENTRANCE FEATURES A "REQUEST TO
 EXIT" BUTTON. ALL THE REQUIREMENTS OF 7.2.1.6.2 (NFPA
 101) TO BE MET FOR ACCESS-CONTROLLED EGRESS DOORS.
  
 SHEET FA1.01A:
 - THE FIRE ALARM CONTROL PANEL (ELECTRICAL #136) IS
 SHOWN IN A DIFFERENT LOCATION FROM ELECTRICAL SHEET
 E1.02B (ROOM #216). COORDINATE LOCATION.
 - DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM CONDITION.
 - SMOKE DETECTOR AT TOP OF ELEVATOR SHAFT NOT PERMITTED
 UNLESS AUTOMATIC SPRINKLER IS PROTECTING TOP OF
 ELEVATOR SHAFT.
  
 GENERAL:
 - SIGNED/SEALED FIRE PROTECTION ENGINEERING DOCUMENTS
 PER FAC 61G15-32.001 ARE REQUIRED FOR A BUILDING
 PERMIT.
 - PROVIDE KNOX KEY SWITCH TO ALLOW FIRE DEPARTMENT
 ACCESS THROUGH ELECTRIC GATE
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-04 Cont ID  
Sent By rregueir Date 2011-03-04 Time 15:32 Rev Time 0.00
Received By rregueir Date 2011-02-08 Time 16:20 Sent To  
Notes
2011-02-08 16:21:21**DIGITAL PLANS** SEE PROJECTDOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-09-20 Time   Rev Time 0.00
Received By lmartine Date 2010-08-17 Time 10:18 Sent To  
Notes
2010-08-17 10:22:29C--3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2011-09-21 Cont ID  
Sent By jwitmer Date 2011-09-21 Time 13:49 Rev Time 0.00
Received By jwitmer Date 2011-09-21 Time 13:49 Sent To  
Notes
2011-09-21 13:51:45IMPACT FEES;
 RECEIPT NUMBER: MU-2011-003746-0000
 $23,214.90

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-04-15 Cont ID  
Sent By jwitmer Date 2011-04-15 Time 08:47 Rev Time 0.00
Received By jwitmer Date 2011-04-15 Time 08:47 Sent To  
Notes
2011-04-15 08:48:13BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop L LANDSCAPING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2011-05-12 Time   Rev Time 0.00
Received By   Date 2011-05-12 Time   Sent To  
Notes
2011-05-12 13:54:23SEPARATE PLANS AND PERMIT REQUIRED PER RKUSSNER.

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2011-03-31 Cont ID  
Sent By rkussner Date 2011-03-31 Time 09:57 Rev Time 0.00
Received By rkussner Date 2011-03-31 Time 09:57 Sent To  
Notes
2011-03-31 09:59:01***LANDSCAPE REVIEW FAILED***
  
 1. LANDSCAPING IS REQUIRED TO BE PERMITTED SEPARATELY.
 PLEASE SUBMIT A LANDSCAPE PERMIT APPLICATION WITH TWO
 COPIES OF THE LANDSCAPE PLAN. A CERTIFIED COST ESTIMATE
 THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS
 AND LABOR BROKEN DOWN INTO UNIT COST SHALL BE SUBMITTED
 WITH THE APPLICATION. LANDSCAPE WILL BE REVIEWED ONCE
 WE RECEIVE THE SEPARATE LANDSCAPE PERMIT.
  
 2. IRRIGATION IS ALSO REQUIRED TO BE PERMITTED
 SEPARATELY. PLEASE SUBMIT AN IRRIGATION APPLICATION AND
 TWO SETS OF IRRIGATION PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2011-02-15 Cont ID  
Sent By rkussner Date 2011-02-15 Time 15:31 Rev Time 0.00
Received By rkussner Date 2011-02-15 Time 15:31 Sent To  
Notes
2011-02-15 15:31:47***LANDSCAPE REVIEW FAILED***
  
 1. LANDSCAPING IS REQUIRED TO BE PERMITTED SEPARATELY.
 PLEASE SUBMIT A LANDSCAPE PERMIT APPLICATION WITH TWO
 COPIES OF THE LANDSCAPE PLAN. A CERTIFIED COST ESTIMATE
 THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS
 AND LABOR BROKEN DOWN INTO UNIT COST SHALL BE SUBMITTED
 WITH THE APPLICATION.
  
 2. IRRIGATION IS ALSO REQUIRED TO BE PERMITTED
 SEPARATELY. PLEASE SUBMIT AN IRRIGATION APPLICATION AND
 TWO SETS OF IRRIGATION PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-09-02 Cont ID  
Sent By rkussner Date 2010-09-02 Time 11:45 Rev Time 0.00
Received By rkussner Date 2010-09-02 Time 11:36 Sent To  
Notes
2010-09-02 11:51:33***LANDSCAPE REVIEW FAILED***
  
 1. LANDSCAPING IS REQUIRED TO BE PERMITTED SEPARATELY.
 PLEASE SUBMIT A LANDSCAPE PERMIT APPLICATION WITH TWO
 COPIES OF THE LANDSCAPE PLAN. A CERTIFIED COST ESTIMATE
 THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS
 AND LABOR BROKEN DOWN INTO UNIT COST SHALL BE SUBMITTED
 WITH THE APPLICATION.
  
 2. IRRIGATION IS ALSO REQUIRED TO BE PERMITTED
 SEPARATELY. PLEASE SUBMIT AN IRRIGATION APPLICATION AND
 TWO SETS OF IRRIGATION PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2011-04-15 Cont ID  
Sent By rregueir Date 2011-04-15 Time 15:22 Rev Time 0.00
Received By rregueir Date 2011-04-15 Time 15:21 Sent To  
Notes
2011-04-15 15:36:25**PROVISO**
  
 STORAGE ROOM 019 IS NOT PERMITTED TO BE USED FOR MOTOR
 VEHICLE ENTRY OR STORAGE. THE VENTILATION REQUIREMENTS
 OF FBC-M SECTION 404 HAVE NOT BEEN MET FOR GARAGE
 VENTILATION. A NOTE FROM THE OWNER ACKNOWLEDGING THE
 SAME HAS BEEN SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2011-03-30 Cont ID  
Sent By rregueir Date 2011-03-30 Time 14:44 Rev Time 0.00
Received By rregueir Date 2011-03-30 Time 10:36 Sent To  
Notes
2011-03-30 14:44:03REVIEW #: 2ND (FOR NEWLY DESIGNED BUILDING)
 ACTION:DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THESE COMMENTS ARE NUMBERED TO CORRESPOND WITH PREVIOUS
 REVIEW FOR CONTINUITY. ANY ADDITIONAL NEW COMMENTS WILL
 BE ADDED TO THE END OF THE REVIEW.
  
 1. OK
  
 2. OK
  
 3. OK
  
 4. EF-3 AND EF-5 ON PAGE M6-1 APPEAR TO HAVE THE ROOM
 NUMBER AND THE CFM REVERSED. PLEASE CORRECT TO
 CORRESPOND WITH THE FLOOR PLAN. FBC-M 304.11.
  
 5. OK
  
 6. OK
  
 7. OK
  
 8. OK
  
 9. OK
  
 10. OK
  
 11. OK
  
 12. OK
  
 13. NOT ADEQUATELY ADDRESSED: FBC-M SECTION 404
 REQUIRES A MINIMUM VENTILATION RATE OF 1.5 CFM/SQ.FT.
 THE VENTILATION RATE IS ALLOWED TO BE INTERMITTENT IF
 THE FAN IS CONTROLLED BY CARBON MONOXIDE SENSORS. PAGE
 M2-1 SHOWS THE FAN BEING CONTROLLED BY CARBON DIOXIDE
 SENSORS. THIS DOES NOT MEET THE REQUIREMENT OF THE CODE
 FOR AN ENCLOSED PARKING GARAGE. ALSO, SECTION 404
 REQUIRES THAT IF INTERMITTENT VENTILATION IS USED, A
 MINIMUM CONTINUOUS VENTILATION RATE OF 0.05 CFM/SQ.FT
 BE PROVIDED. SHOW HOW THIS MINIMUM CONTINUOUS RATE IS
 TO BE PROVIDED. IN ADDITION, WHAT IS THE SIZE OF THE
 INTAKE LOUVER? NO SIZE IS GIVEN ON THE PLANS. THE SIZE
 MUST BE LARGE ENOUGH TO PROVIDE AT LEAST 1000 CFM OF
 MAKE-UP AIR FOR THE EXHAUST FAN BEING PROPOSED.
  
 NOTE: PROVIDE SIZES FOR ALL OUTDOOR LOUVERS.
  
 14. NEW COMMENT: AHU-10 RETURN AIR SYSTEM IS
 REDESIGNED, ELIMINATING DUCTED RETURN AND UTILIZING
 TRANSFER DUCTS FROM OFFICES INTO ADJACENT HALL 37.
 THERE DOES NOT APPEAR TO BE A CENTRALIZED R/A INTAKE
 ASSOCIATED WITH AHU-10 LARGE ENOUGH TO DRAW ALL THE
 RETURN AIR FROM THESE TRANSFER DUCTS BACK TO THE AHU.
 PLEASE SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN
 THIS AREA PER FBC-M 601.4. ALSO, THE TRANSFER DUCTS
 FROM THE OFFICE ARE NOT SIZED PER THE BALANCED RETURN
 AIR EXCEPTIONS UNDER FBC-M 601.4. THE TRANSFER DUCT
 MUST BE MINIMUM 1.5 TIMES THE SIZE OF THE SUPPLY DUCT.
 IN MOST CASES THE PLAN SHOWS A DUCT WITH APPROXIMATELY
 THE SAME SQUARE INCHES. SHOW HOW COMPLIANCE WITH FBC-M
 601.4 IS TO BE ACHIEVED IN THESE AREAS.
  
 NOTE: THE KITCHEN HOOD EXHAUST SYSTEM IS EXCLUDED FROM
 THE SCOPE OF THIS REVIEW. SEPARATE PLANS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR THE HOOD SYSTEM AND THE
 FIRE SUPPRESSION SYSTEM.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-02-15 Cont ID  
Sent By rregueir Date 2011-02-15 Time 15:54 Rev Time 0.00
Received By rregueir Date 2011-02-08 Time 16:21 Sent To  
Notes
2011-02-15 15:54:09REVIEW #: 1ST (FOR NEWLY DESIGNED BUILDING)
 ACTION:DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SOME DUCTS PENETRATING THE SMOKE PARTITION AT
 STORAGE ROOM 18 AND A/V 17 ARE SHOWN WITH SMOKE DAMPERS
 WHILE OTHERS ARE NOT. DESIGN INTENT IS NOT CLEAR. IN
 SMOKE PARTITIONS, SMOKE DAMPERS ARE ONLY REQUIRED IN
 AIR TRANSFER OPENINGS AND ARE NOT REQUIRED AT DUCT
 PENETRATIONS PER FBC-B 710.7.
  
 2. RETURN DUCT SERVING ROOM A/V 17 IS MISSING SIZE, CFM
 AND GRILL DESIGNATION. PROVIDE MISSING INFO ON PLANS
 PER FBC-M 603.1.
  
 3. DUCTS PENETRATING THE FIRE RATED CORRIDOR SHALL BE
 PROTECTED WITH FIRE AND SMOKE DAMPERS PER FBC-M 607.5.3
 AND 607.5.4.
  
 4. TWO FANS MARKED AS EF-3 ON FLOOR PLAN AND ON THE FAN
 SCHEDULE, BUT THEY DO NOT SHOW THE SAME CFM ON THE
 FLOOR PLAN. PLEASE COORDINATE FLOOR PLANS AND
 SCHEDULES. CONSIDER NAMING EACH FAN INDIVIDUALLY TO
 INDICATE THE AREAS BEING SERVED BY EACH PER FBC-M
 304.11.
  
 5. RESTROOMS 39 AND 40 SERVE A LARGE ASSEMBLY SPACE AND
 SHALL BE CAPABLE OF PROVIDING A HIGHER VENTILATION RATE
 DURING PEAK USAGE TIMES OF 70 CFM PER WATER CLOSET
 AND/OR URINAL PER ASHRAE 62.1 TABLE 6-4, NOTE D. THE
 SIX FIXTURES IN THE MEN'S WOULD REQUIRE 420 CFM AND THE
 7 IN THE WOMEN'S WOULD REQUIRE 490 CFM DURING PEAK
 USAGE TIMES. A LOWER RATE OF 50 CFM PER FIXTURE MAY BE
 PROVIDED (300 CFM MEN'S AND 350 CFM WOMEN'S) DURING
 LOWER USAGE TIMES.
  
 6. THE EXHAUST FAN SERVING ROOM JANITOR 22 HAS NO DATA,
 IS NOT LABELED ON PLANS AND DOES NOT APPEAR ON FAN
 SCHEDULE. PROVIDE MISSING DATA PER FBC-M 501.1.
  
 7. AHU-5 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE FLOOR
 PLAN CALLS FOR 1925 CFM. WHICH IS CORRECT? COORDINATE
 FLOOR PLANS AND SCHEDULES. FBC-M 603.1.
  
 8. AHU-7 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE FLOOR
 PLAN CALLS FOR 1975 CFM. WHICH IS CORRECT? COORDINATE
 FLOOR PLANS AND SCHEDULES. FBC-M 603.1.
  
 9. AHU-7 ON FLOOR PLAN SHOWS 1975 CFM OF SUPPLY AND
 2000 CFM OF RETURN. HOW WILL OUTSIDE AIR BE INTRODUCED
 IF THE SYSTEM IS DESIGNED TO RETURN 100% OF THE SUPPLY
 QUANTITY? THIS CONDITION APPEARS ON SEVERAL SYSTEMS.
 THIS WOULD ALSO CREATE A NEGATIVE PRESSURE. BUILDINGS
 SHALL BE PRESSURIZEDIN ACCORDANCE WITH FBC-B
 13-409.AB.2. SHOW HOW VENTILATION AIR IS TO BE
 INTRODUCED INTO EACH OF THESE SYSTEMS PER FBC-M 401.1.
  
 10. AHU-8 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE
 FLOOR PLAN CALLS FOR 2075 CFM. WHICH IS CORRECT?
 COORDINATE FLOOR PLANS AND SCHEDULES. FBC-M 603.1.
 ALSO, SUPPLY AIR SYSTEMS EXCEEDING 2000 CFM SHALL BE
 PROVIDED WITH FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC-M
 606.2.1.
  
 11. AHU-9 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE
 FLOOR PLAN CALLS FOR 2000 CFM PLUS ONE GRILL SERVING
 ROOM RECEPTION 49 WHICH IS MISSING CFM AND GRILL
 DESIGNATION. WHICH IS CORRECT? COORDINATE FLOOR PLANS
 AND SCHEDULES. PROVIDE MISSING GRILL DATA. FBC-M 603.1.
 ALSO, SUPPLY AIR SYSTEMS EXCEEDING 2000 CFM SHALL BE
 PROVIDED WITH FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC-M
 606.2.1.
  
 12. AHU-11 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE
 FLOOR PLAN CALLS FOR 2075 CFM. WHICH IS CORRECT?
 COORDINATE FLOOR PLANS AND SCHEDULES. FBC-M 603.1.
 ALSO, SUPPLY AIR SYSTEMS EXCEEDING 2000 CFM SHALL BE
 PROVIDED WITH FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC-M
 606.2.1.
  
 13. STORAGE ROOM 19 IS CONFIGURED FOR VEHICLE
 ENTRY/PARKING. ENCLOSED PARKING GARAGE SHALL BE
 PROVIDED WITH MECHANICAL VENTILATION IN ACCORDANCE WITH
 FBC-M SECTION 404.
  
 NOTE: THE KITCHEN HOOD EXHAUST SYSTEM IS EXCLUDED FROM
 THE SCOPE OF THIS REVIEW. SEPARATE PLANS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR THE HOOD SYSTEM AND THE
 FIRE SUPPRESSION SYSTEM.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-09-16 Cont ID  
Sent By rregueir Date 2010-09-16 Time 17:03 Rev Time 0.00
Received By rregueir Date 2010-09-16 Time 14:14 Sent To  
Notes
2010-09-16 17:03:54REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVIEW COMMENTS:
  
 1. PG M1.01A: OFFICE 107 SHOWS A TRANSFER DUCT FOR
 BALANCED RETURN. WHILE THE TRANSFER DUCT IS PROPERLY
 SIZED UNDER EXCEPTION 1 OF FBC-M 601.4, A ONE INCH
 UNDERCUT DOOR IS ALSO REQUIRED. THE LOCATION OF THE
 DOOR IN THIS ROOM DOES NOT COMMUNICATE WITH THE
 CENTRALIZED RETURN OF THE AHU SERVING THIS ROOM. SHOW
 HOW BALANCED RETURN IS TO BE ACHIEVED IN THIS AREA PER
 FBC-M 601.4.
  
 2. PG M1.01A: BREAK ROOM 111 SHOWS A TRANSFER DUCT FOR
 BALANCED RETURN. THE TRANSFER DUCT SHOWN IS NOT
 PROPERLY SIZED UNDER ECEPTION 1 OF FBC-M 601.4, WHICH
 REQUIRES THE TRANSFER DUCT TO BE MINIMUM 1.5 TIMES THE
 AREA OF THE SUPPLY DUCT. THE TWO 10 INCH SUPPLY DUCTS
 SERVING THIS ROOM HAVE A TOTAL OF 157 SQUARE INCHES. IN
 ORDER TO MEET THE EXCEPTION, THE TRANSFER DUCT MUST
 HAVE A MINIMUM CROSS-SECTIONAL AREA OF 235.5 SQUARE
 INCHES, PLUS A 1 INCH UNDERCUT AT THE DOOR. SHOW HOW
 BALANCED RETURN IS TO BE ACHIEVED IN THIS ROOM PER
 FBC-M 601.4.
  
 3. PG M1.01A AND P1.01A: CONDENSATE FOR AHU-5 IS SHOWN
 DISCHARGING ONTO A CONCRETE WALKWAY. THIS LOCATION WILL
 CAUSE A NUISANCE AND A HAZARDOUS CONDITION FOR
 PEDESTRIANS. CONDENSATE SHALL BE CONVEYED FROM THE
 DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL.
 CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY OR
 OTHER AREAS SO AS TO CAUSE A NUISANCE PER FBC-M
 307.2.1.
  
 4. PG M1.02A: VESTIBULE 200 IS SERVING AS PART OF A
 FIRE RATED EXIT ACCESS CORRIDOR. THE 18X10 AND 16X10
 SUPPLY DUCT PENETRATIONS AT THIS LOCATION ARE REQUIRED
 TO BE PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY FIRE
 DAMPERS ARE CURRENTLY SHOWN ON THE PLAN. SHOW
 COMPLIANCE WITH FBC-M 607.5.4.
  
 5. PG M1.02A: LOBBY 204 IS SERVING AS PART OF A FIRE
 RATED EXIT ACCESS CORRIDOR. THE 22X14 SUPPLY DUCT
 PENETRATION AT THIS LOCATION IS REQUIRED TO BE
 PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY A FIRE DAMPER
 IS CURRENTLY SHOWN ON THE PLAN. SHOW COMPLIANCE WITH
 FBC-M 607.5.4.
  
 6. PG M1.02B: GALLERY IS SERVING AS PART OF A FIRE
 RATED EXIT ACCESS CORRIDOR. THE 18X14 AND 14X12 RETURN
 DUCT PENETRATIONS AT THIS LOCATION ARE REQUIRED TO BE
 PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY FIRE DAMPERS
 ARE CURRENTLY SHOWN ON THE PLAN. SHOW COMPLIANCE WITH
 FBC-M 607.5.4.
  
 7. PG M1.02B: LOBBY 204 IS SERVING AS PART OF A FIRE
 RATED EXIT ACCESS CORRIDOR. THE 20X14 SUPPLY DUCT
 PENETRATION AT THIS LOCATION IS REQUIRED TO BE
 PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY A FIRE DAMPER
 IS CURRENTLY SHOWN ON THE PLAN. SHOW COMPLIANCE WITH
 FBC-M 607.5.4.
  
 8. PG M1.02B: VESTIBULE 211 IS SERVING AS PART OF A
 FIRE RATED EXIT ACCESS CORRIDOR. THE 12X12 SUPPLY DUCT
 PENETRATION AT THIS LOCATION IS REQUIRED TO BE
 PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY A FIRE DAMPER
 IS CURRENTLY SHOWN ON THE PLAN. SHOW COMPLIANCE WITH
 FBC-M 607.5.4.
  
 9. PG M1.02B: VESTIBULE 211 IS SERVING AS PART OF A
 FIRE RATED EXIT ACCESS CORRIDOR. THE TWO 8 INCH ROUND
 AND ONE 4 INCH ROUND SUPPLY DUCT PENETRATIONS AT THIS
 LOCATION ARE REQUIRED TO BE PROTECTED BY A FIRE DAMPER
 PER FBC-M 607.5.3 OR A THROUGH-PENETRATION FIRESTOP
 SYSTEM PER FBC-M 607.1.1. THEY ALSO REQUIRE SMOKE
 DAMPERS PER FBC-M 607.5.4.
  
 10. PG M1.102B: THE 4 INCH ROUND EXHAUST DUCT SERVING
 CUSTODIAL 214 SHALL BE PROTECTED WITH A FIRE DAMPER PER
 FBC-M 607.5.3 OR A THROUGH-PENETRATION FIRESTOP SYSTEM
 PER FBC-M 607.1.1.
  
 11. PG ME1.01: ELEVATIONS SHOWN ON PLAN INDICATE THAT
 IT WOULD BE NECESSARY TO CLIMB A HEIGHT OF AT LEAST 4
 FEET (OVER A PARAPET) TO GET FROM THE LOWER ROOF WHERE
 THE ROOF ACCESS HATCH IS LOCATED TO THE MAIN ROOF WHERE
 THE MECHANICAL APPLIANCES ARE LOCATED. SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES HIGH PER FBC-M 306.5. PROVIDE A
 PERMANENT MEANS OF ACCESS OVER THIS OBSTRUCTION.
  
 12. PG ME1.01: CU-6 AND EF-2 ARE BOTH SHOWN LESS THAN
 10 FEET FROM THE ROOF EDGE. THE ROOF HATCH OPENING IS
 ALSO LESS THAN 10 FEET FROM THE ROOF EDGE. GUARDS SHALL
 BE PROVIDED AT THESE LOCATIONS IN ACCORDANCE WITH FBC-M
 304.10.
  
 13. PG M2.02: PROVIDE WIND RESISTANT INSTALLATION
 DETAIL FOR ROOF MOUNTED EXHAUST FAN(S) PER FBC-M
 301.12.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-04-07 Cont ID  
Sent By lwagner Date 2011-04-07 Time 11:36 Rev Time 0.00
Received By lwagner Date 2011-04-07 Time 10:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-02-28 Cont ID  
Sent By lwagner Date 2011-02-28 Time 11:25 Rev Time 0.00
Received By lwagner Date 2011-02-28 Time 10:07 Sent To  
Notes
2011-02-28 10:55:50FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 1. A UNISEX RESTROOM WILL BE REQUIRED:
 403.7 UNISEX TOILET AND BATHING ROOMS. IN ASSEMBLY AND
 MERCANTILE OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET
 ROOM SHALL BE PROVIDED WHERE AN AGGREGATE OF SIX OR
 MORE MALE AND FEMALE WATER CLOSETS IS REQUIRED. IN
 BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE WATER CLOSETS
 REQUIRED FOR THE ASSEMBLY OR MERCANTILE OCCUPANCY SHALL
 BE USED TO DETERMINE THE UNISEX TOILET ROOM
 REQUIREMENT. IN RECREATIONAL FACILITIES WHERE
 SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE
 UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED
 WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE
 INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED
 IN AN OCCUPANCY.
  
 2. SHEET 2-1 DOES NOT PROVIDE ENOUGH INFORMATION AS TO
 A POINT OF USE GREASE TRAP FOR THE 3 COMPARTMENT SINK
 ONLY BEING CONNECTED. THE OTHER TWO SINKS AND MOP SINK
 WITH FLOOR DRAIN MAY NEED TO BE CONNECTED ALSO
 DEPENDING UPON THE USE OF THE FOOD PREP AREA.
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR OR
 AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS,
 SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS,
 SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS.
 FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS,
 PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK
 STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE
 DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS
 WITHOUT PRERINSE SINKS. GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE
 ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS
 OR GREASE TO BE DISCHARGED.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-09-02 Cont ID  
Sent By lwagner Date 2010-09-02 Time 12:48 Rev Time 0.00
Received By lwagner Date 2010-09-01 Time 09:48 Sent To  
Notes
2010-09-01 15:07:38FBC PLUMBING 2007
 REVIEW #1
 DENIED:
  
 1. SHEET A-2.2 FBC BUILDING 11-4.17.3 (2) THE
 ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO THE DOOR. WOMENS ROOM #213
  
 2.SHEET A-2.2 11-4.17.3 2ND FLOOR MENS ROOM #212 ADA
 COMPARTMENT DOES NOT CONFORM WITH FIGURE 30E TOILET
 STALL NEW CONSTRUCTION.
  
 3. SHEET P 1.01 A - SHOWS ELEVATOR SUMP LINE CONNECTED
 TO THE SITE DRAINAGE. THE ELEVATOR SUMP SHALL NOT
 CONNECT TO THE SITE DRAINAGE DUE TO THE POSSIBILITY OF
 HYDRAULIC FLUID CONTAMINATION. ONE OPTION WOULD BE TO
 ROUTE THE PUMP LINE TO THE SANITARY THROUGH AN OIL
 INTERSEPTOR SIZED TO CONTAIN THE OIL
 FBC PLUMBING 701.4 SEWAGE TREATMENT. SEWAGE OR OTHER
 WASTE FROM A PLUMBING SYSTEM THAT IS DELETERIOUS TO
 SURFACE OR SUBSURFACE WATERS SHALL NOT BE DISCHARGED
 INTO THE GROUND OR INTO ANY WATERWAY UNLESS IT HAS
 FIRST BEEN RENDERED INNOCUOUS THROUGH SUBJECTION TO AN
 APPROVED FORM OF TREATMENT
 FBC BUILDING 3004.4 PLUMBING AND MECHANICAL SYSTEMS.
 PLUMBING AND MECHANICAL SYSTEMS SHALL NOT BE LOCATED IN
 AN ELEVATOR SHAFT.
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE
 INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM.
 701.5 DAMAGE TO DRAINAGE SYSTEM OR PUBLIC SEWER. WASTES
 DETRIMENTAL TO THE PUBLIC SEWER SYSTEM OR TO THE
 FUNCTIONING OF THE SEWAGE-TREATMENT PLANT SHALL BE
 TREATED AND DISPOSED OF IN ACCORDANCE WITH SECTION 1003
 AS DIRECTED BY THE CODE OFFICIAL.
  
 4. SHEET P 1.01B PLUMBING 314.2.2 CONDENSATE DRAIN PIPE
 MATERIALS AND SIZES. WHERE THE DRAIN PIPES FROM MORE
 THAN ONE UNIT ARE MANIFOLDED TOGETHER FOR CONDENSATE
 DRAINAGE, THE PIPE OR TUBING SHALL BE SIZED IN
 ACCORDANCE WITH AN APPROVED METHOD. 3/4" PIPE APPEARS
 TO BE TOO SMALL FOR 7 TONS OF CONDENSATE.
 A 3.0 ROOF DETAIL
  
 5. SHEET P 1.02 B & P 2.01 THE CIRCUIT VENT FOR THE
 RESTROOMS REQUIRES A DRY VENT BETWEEN THE LAST TWO MOST
 UPSTREAM WC'S PLUMBING 911.2 VENT CONNECTION. THE
 CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN THE
 TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  
 6. SHEET P 2.01 4" SANITARY PIPE IS REQUIRED UP TO THE
 LAST 4 WATER CLOSETS. TABLE 710.1(2)
  
 7. IRRIGATION PLAN - IF IRRIGATION IS CONNECTING TO THE
 DOMESTIC WATER SERVICE DOWNSTREAM OF THE RPZ BACKFLOW
 PREVENTOR, THE IRRIGATION LINE WILL REQUIRE A PRESSURE
 VACUUM BREAKER OR AN RPZ BACKFLOW PREVENTOR 608.16.5
  
 ****NOTE***** FROM SHEET P1.01A - A SEPERATE
 APPLICATION, DRAWINGS, AND GAS PERMIT WILL BE REQUIRED
 FOR THE RELOCATED GENERATOR.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2011-08-30 Cont ID  
Sent By rregueir Date 2011-08-30 Time 11:55 Rev Time 0.00
Received By rregueir Date 2011-08-30 Time 11:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2011-04-14 Cont ID  
Sent By jroach Date 2011-04-14 Time 08:35 Rev Time 0.00
Received By jroach Date 2011-04-14 Time 08:35 Sent To  
Notes
2011-04-14 08:51:49ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.14.2011
 PERMIT NO.: 10080396
 ADDRESS: 1590 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW OFFICE BUILDING.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS PERMIT HAS BEEN PASSED, SUBJECT OT THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE TEN (10) FOOT DRAINAGE EASEMENT RUNNING ALONG THE
 NORTH AND EAST PROPERTY LINES SHALL BE ABANDONED.
 PLEASE PROVIDE A COPY OF THE RECORDED EASEMENT
 ABANDONMENT. CONTACT VINCE NOEL, CITY SURVEYOR, AT
 494-1096 FOR INFORMATION PERTAINING TO THIS.
  
 2. PER SECTION 94-481(C) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS, A FINAL CERTIFICATE OF
 OCCUPANCY WILL NOT BE ISSUED FOR THE NEW BUILDING UNTIL
 THE OLD BUILDING HAS BEEN DEMOLISHED AND REMAINING SITE
 IMPROVEMENTS (I.E. PARKING, LANDSCAPING, ETC.) HAVE
 BEEN INSTALLED ACCORDING TO THE APPROVED PLANS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 4 Status F Date 2011-04-07 Cont ID  
Sent By jroach Date 2011-04-07 Time 11:56 Rev Time 0.00
Received By jroach Date 2011-04-07 Time 11:55 Sent To  
Notes
2011-04-07 11:56:54ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.07.2011
 PERMIT NO.: 10080396
 ADDRESS: 1590 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW OFFICE BUILDING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ON SHEET 4 OF 13 OF THE CIVIL DRAWINGS, THE DIAGONAL
 STRIPING FOR THE HANDICAP ACCESS AISLE SHOULD BE 4 INCH
 WHITE STRIPES, NOT BLUE. SEE PARKING STRIPING DETAIL.
  
 2. THE PARKING DETAIL ON SHEET 6 OF 13 MAY NEED TO BE
 ADJUSTED TO SHOW WHITE STRIPES IN THE HANDICAP ACCESS
 AISLE...IT IS LABELED AS SUCH, BUT BECAUSE IT IS SHADED
 A DARK COLOR, IT MAY BE CONFUSING.
  
 3. PRIOR TO THE SUBMISSION OF ANY BUILDING PERMIT FOR
 THE PROPOSED OFFICE BUILDING, THE CITY OF WEST PALM
 BEACH POLICE DEPARTMENT - CRIME PREVENTION UNIT SHALL
 REVIEW AND APPROVE ALL CONSTRUCTION DRAWINGS TO ENSURE
 THE ADHERENCE TO GENERALLY-ACCEPTED CRIME PREVENTION
 THROUGH ENVIRONMENTAL DESIGN PRINCIPLES.
  
 4. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE TEN
 (10) FOOT DRAINAGE EASEMENT RUNNING ALONG THE NORTH AND
 EAST PROPERTY LINES SHALL BE ABANDONED. PLEASE PROVIDE
 A COPY OF THE RECORDED EASEMENT ABANDONMENT. CONTACT
 VINCE NOEL, CITY SURVEYOR, AT 494-1096 FOR INFORMATION
 PERTAINING TO THIS.
  
 5. PER SECTION 94-481(C) OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS, A FINAL CERTIFICATE OF
 OCCUPANCY WILL NOT BE ISSUED FOR THE NEW BUILDING UNTIL
 THE OLD BUILDING HAS BEEN DEMOLISHED AND REMAINING SITE
 IMPROVEMENTS (I.E. PARKING, LANDSCAPING, ETC.) HAVE
 BEEN INSTALLED ACCORDING TO THE APPROVED PLANS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 3 Status F Date 2011-03-31 Cont ID  
Sent By jroach Date 2011-03-31 Time 16:45 Rev Time 0.00
Received By jroach Date 2011-03-31 Time 16:45 Sent To  
Notes
2011-03-31 16:46:08ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.31.2011
 PERMIT NO.: 10080396
 ADDRESS: 1590 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW OFFICE BUILDING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE LANDSCAPE PLANS DO NOT MATCH REGARDING THE
 DRIVEWAY APPROACH ON WITT STREET, CONNECTING INTO THE
 BUILDING. THE CIVIL DRAWINGS AND SITE PLANS SHOW THE
 APRON (OR TAPER) EXTENDING SIGNIFICANTLY CLOSER TO THE
 BUILDING. THE LANDSCAPE PLANS SHOW PLANTING BEING
 PLACED BETWEEN THE BUILDING AND THE SIDEWALK. PLEASE
 ENSURE ALL PLANS ARE CONSISTENT.
  
 2. ON SHEET 4 OF 13 OF THE CIVIL DRAWINGS, THE DIAGONAL
 STRIPING FOR THE HANDICAP ACCESS AISLE SHOULD BE 4 INCH
 WHITE STRIPES, NOT BLUE. SEE PARKING STRIPING DETAIL.
  
 3. THE LANDSCAPE PLANS DO NOT MATCH REGARDING THE
 DRIVEWAY APPROACH ON WORTHINGTON STREET.
  
 4. THE PARKING DETAIL ON SHEET 6 OF 13 MAY NEED TO BE
 ADJUSTED TO SHOW WHITE STRIPES IN THE HANDICAP ACCESS
 AISLE...IT IS LABELED AS SUCH, BUT BECAUSE IT IS SHADED
 A DARK COLOR, IT MAY BE CONFUSING.
  
 5. THE LANDSCAPE PLANS DO NOT MATCH REGARDING THE
 PLACEMENT AND QUANTITY OF MECHANICAL UNITS LOCATED ON
 THE NORTH AND SOUTH SIDES OF THE BUILDING.
  
 6. THE LANDSCAPE PLANS DO NOT MATCH REGARDING THE
 LOCATION OF THE WATER LINE AND FIRE LINE (AND
 ASSOCIATED EQUIPMENT). PLEASE ADJUST AND SCREEN ALL
 EQUIPMENT ACCORDINGLY.
  
 7. PRIOR TO THE SUBMISSION OF ANY BUILDING PERMIT FOR
 THE PROPOSED OFFICE BUILDING, THE CITY OF WEST PALM
 BEACH POLICE DEPARTMENT - CRIME PREVENTION UNIT SHALL
 REVIEW AND APPROVE ALL CONSTRUCTION DRAWINGS TO ENSURE
 THE ADHERENCE TO GENERALLY-ACCEPTED CRIME PREVENTION
 THROUGH ENVIRONMENTAL DESIGN PRINCIPLES.
  
 8. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE TEN
 (10) FOOT DRAINAGE EASEMENT RUNNING ALONG THE NORTH AND
 EAST PROPERTY LINES SHALL BE ABANDONED. PLEASE PROVIDE
 A COPY OF THE RECORDED EASEMENT ABANDONMENT. CONTACT
 VINCE NOEL, CITY SURVEYOR, AT 494-1096 FOR INFORMATION
 PERTAINING TO THIS.
  
 9. PER SECTION 94-481(C) OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS, A FINAL CERTIFICATE OF
 OCCUPANCY WILL NOT BE ISSUED FOR THE NEW BUILDING UNTIL
 THE OLD BUILDING HAS BEEN DEMOLISHED AND REMAINING SITE
 IMPROVEMENTS (I.E. PARKING, LANDSCAPING, ETC.) HAVE
 BEEN INSTALLED ACCORDING TO THE APPROVED PLANS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 2 Status F Date 2011-02-11 Cont ID  
Sent By jroach Date 2011-02-11 Time 16:43 Rev Time 0.00
Received By jroach Date 2011-02-11 Time 16:43 Sent To  
Notes
2011-02-11 16:43:39ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.11.2011
 PERMIT NO.: 10080396
 ADDRESS: 2100 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW OFFICE BUILDING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ON SHEET 4 OF 13 OF THE CIVIL DRAWINGS, THE DRIVEWAY
 APPROACH ON WITT STREET, CONNECTING INTO THE BUILDING,
 DOES NOT APPEAR CORRECT, AND DOES NOT MATCH THE SITE OR
 LANDSCAPE PLANS. THE CIVIL DRAWINGS SHOW THE APRON (OR
 TAPER) EXTENDING SIGNIFICANTLY CLOSER TO THE BUILDING.
 THE LANDSCAPE PLANS SHOW PLANTING BEING PLACED BETWEEN
 THE BUILDING AND THE SIDEWALK. PLEASE CLARIFY IF THIS
 SIGNIFICANT OF AN APRON IS NECESSARY.
  
 2. ON SHEET 5 OF 13 OF THE CIVIL DRAWINGS, THE DRIVEWAY
 APPROACH ON WORTHINGTON STREET DOES NOT MATCH THE SITE
 OR LANDSCAPE PLANS. THE SITE/LANDSCAPE PLANS INDICATE
 ???EXISTING CURB CUT TO REMAIN???. PLEASE CLARIFY.
  
 3. ON SHEET 6 OF 13 OF THE CIVIL DRAWINGS, THE PARKING
 DETAIL SHOULD REFLECT TWO (2) FEET TO THE BACK OF THE
 WHEEL STOP, NOT THE FRONT OF THE WHEEL STOP. PLEASE
 ADJUST ACCORDINGLY.
  
 4. ON SHEET 10 OF 13 OF THE CIVIL DRAWING, THE LOCATION
 OF THE WATER LINE AND FIRE LINE DOES NOT MATCH THAT
 SHOWN ON THE LANDSCAPE PLAN. PLEASE ADJUST ACCORDINGLY.
  
 5. ON SHEET SP-1, THE PROPOSED FREESTANDING SIGN IS
 LOCATED WITHIN THE VISIBILITY TRIANGLE. PLEASE ADJUST
 ACCORDINGLY.
  
 6. ON SHEET SP-1, PLEASE NOTE THE PROPOSED CMU TO BE
 PROVIDED AROUND THE A/C UNITS ALONG WORTHINGTON ROAD.
  
 7. ON SHEET SP-2, PLEASE PROVIDE A DETAIL OF THE
 PROPOSED CMU WALL THAT IS TO SURROUND THE A/C UNITS
 ALONG WORTHINGTON ROAD. ADDITIONALLY, PROVIDE A DETAIL
 OF THE CMU WALL THAT IS PROPOSED TO SURROUND THE
 GENERATOR.
  
 8. ON SHEET M2.1, THE QUANTITY AND CONFIGURATION OF THE
 CONDENSING UNITS DOES NOT MATCH THAT SHOWN ON THE
 SITE/LANDSCAPE PLANS. PLEASE ADJUST ACCORDINGLY.
  
 9. ON SHEET E1.2, THE LOCATION OF THE LIGHT POLES IN
 THE PARKING LOT DOES NOT MATCH THAT SHOWN ON THE
 SITE/LANDSCAPE PLANS. PLEASE ADJUST ACCORDINGLY.
  
 10. A SITE PHOTOMETRIC PLAN SHALL BE PROVIDED.
  
 11. PRIOR TO THE SUBMISSION OF ANY BUILDING PERMIT FOR
 THE PROPOSED OFFICE BUILDING, THE CITY OF WEST PALM
 BEACH POLICE DEPARTMENT ??? CRIME PREVENTION UNIT SHALL
 REVIEW AND APPROVE ALL CONSTRUCTION DRAWINGS TO ENSURE
 THE ADHERENCE TO GENERALLY-ACCEPTED CRIME PREVENTION
 THROUGH ENVIRONMENTAL DESIGN PRINCIPLES.
  
 12. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE TEN
 (10) FOOT DRAINAGE EASEMENT RUNNING ALONG THE NORTH AND
 EAST PROPERTY LINES SHALL BE ABANDONED.
 13. PER SECTION 94-481(C) OF THE CITY???S ZONING AND
 LAND DEVELOPMENT REGULATIONS, A FINAL CERTIFICATE OF
 OCCUPANCY WILL NOT BE ISSUED FOR THE NEW BUILDING UNTIL
 THE OLD BUILDING HAS BEEN DEMOLISHED AND REMAINING SITE
 IMPROVEMENTS (I.E. PARKING, LANDSCAPING, ETC.) HAVE
 BEEN INSTALLED ACCORDING TO THE APPROVED PLANS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-09-01 Cont ID  
Sent By jroach Date 2010-09-01 Time 10:47 Rev Time  
Received By jroach Date 2010-09-01 Time   Sent To  
Notes
2010-09-01 10:47:27ZONING PLAN REVIEW
  
 PERMIT NO.: 10080396
 ADDRESS: 2100 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: ADDITION OF A SECOND STORY TO AN
 EXISTING ONE STORY OFFICE BUILDING, PARKING AND
 LANDSCAPE MODIFICATIONS.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) AS PROVIDED IN THE APPROVAL LETTER FOR INFORMAL SITE
 PLAN REVIEW CASE NO. 10-01, PRIOR TO THE SUBMISSION OF
 ANY BUILDING PERMIT, THE CITY OF WEST PALM BEACH POLICE
 DEPARTMENT ??? CRIME PREVENTION UNIT SHALL REVIEW AND
 APPROVE ALL CONSTRUCTION DRAWINGS TO ENSURE THE
 ADHERENCE TO GENERALLY-ACCEPTED CRIME PREVENTION
 THROUGH ENVIRONMENTAL DESIGN PRINCIPLES. PLEASE PROVIDE
 A LETTER OF APPROVAL FROM OFFICER KELLY CARSILLO
 INDICATING SUCH.
  
 2) ON SHEET 2 OF 9 OF THE PAVING & DRAINAGE, THE
 DIMENSIONS OF THE NORTHERN HALF OF THE PARKING LOT DO
 NOT MATCH THAT PROVIDED ON THE SITE PLAN (SHEET SP-1),
 AND DO NOT MEET THE MINIMUM DIMENSIONS REQUIRED. PLEASE
 ADJUST ACCORDINGLY SO THAT ALL SHEETS ARE CONSISTENT
 AND MEET THE MINIMUM DIMENSION REQUIREMENTS FOR PARKING
 SPACES AND DRIVE AISLES. ADDITIONALLY, IT APPEARS THAT
 THE DIMENSIONS SHOWN FOR THE LANDSCAPE BUFFER ALONG THE
 SOUTH PROPERTY LINE DO NOT MATCH THAT SHOWN ON THE SITE
 PLAN.
  
 3) AS PROVIDED IN THE APPROVAL LETTER FOR INFORMAL SITE
 PLAN REVIEW CASE NO. 10-01, PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY, A UTILITY EASEMENT SHALL BE
 RECORDED IN THE PUBLIC RECORDS OF PALM BEACH COUNTY FOR
 THE PROPOSED FIRE HYDRANT ALONG NORTH FLORIDA MANGO
 ROAD. AN APPLICATION FOR SUCH EASEMENT SHALL BE
 SUBMITTED TO THE CITY???S ENGINEERING SERVICES
 DEPARTMENT.
  
 4) PLEASE UPDATE PARKING STALL DETAIL SHOWN ON SHEET 3
 OF 9 OF THE PAVING & DRAINAGE TO REFLECT THE CURRENT
 REQUIREMENTS (I.E. LOCATION OF HC SYMBOL, COLORS OF
 STRIPING, ETC.). PLEASE EMAIL ME ([email protected]) TO
 OBTAIN A COPY OF THE CURRENT DETAIL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved